Parker Siemens APOGEE P1 Скачать руководство пользователя страница 17

 11

 

Siemens APOGEE P1 Communications Interface   

 

 

Point Database for Siemens APOGEE P1 

Point 

Number 

Point 

Type 

Subpoint Name 

Factory Default

(SI Units)

 

Engr. Units

(SI Units)

 

Slope 

(SI Units)

Intercept 

(SI Units)

 

On Text 

Off Text 

1 LAO 

CTRL 

ADDRESS 

2 LAO  ED_HVAC10 

2731 

3 LAI Freq 

Output 

Hz  0.1 0  -  - 

LAI 

Freq 

Demand 

Hz 0.1 0 -  - 

5 LAI 

Speed 

RPM  0.1  0  - 

6 LAI 

Current 

0.1 

-1638.3 - 

7 LAI 

Torque 

PCT  0.1 

-1638.3 - 

8 LAI 

Power 

Kw  0.1  0  - 

10 LAI  Drive 

KWH 

KWh  0.1  0 

12 LAI 

Runtime 

Hrs 

13 

LAI 

DC Bus Volts 

Volts 

14 LAI  Output 

Volts 

Volts 

20 LAO  OVRD 

Time 

 

21 LDI 

Direction 

FWD 

0  REV FWD 

22 LDO  Direction 

SP 

FWD 

0  REV  FWD 

23 LDI 

RUN 

STOP 

0  RUN STOP 

24 LDO 

RUN 

SP 

STOP 

0  RUN STOP 

25 LAO  Stop 

Mode 

27 LDO  Coast 

Stop 

FALSE 

0  TRUE FALSE 

28 LDO 

Fast 

Stop 

FALSE 

0  TRUE FALSE 

29 LDO 

Day.Night 

DAY 

30 LAO 

Curr 

Limit 

150.0 

PCT 

0.1  0 

31 

LAO 

Accel Time 1 

10.0 

SECS 

0.1 

32 

LAO 

Decel Time 1 

10.0 

SECS 

0.1 

33 

LAO 

Stop Decel T 

10.0 

SECS 

0.1 

34 

LAO 

Fast Decel T 

0.1 

SECS 

0.1 

35 LDO  Run 

Enable 

ENABLE 

0 ENABLE 

DISABL 

37 LAO  Reference 

SP 

PCT 

0.1 -1683.3  - 

40 

LDI 

O/P Relay 1 

OFF 

ON 

OFF 

41 

LDI 

O/P Relay 2 

OFF 

ON 

OFF 

42 

LDI 

O/P Relay 3 

OFF 

ON 

OFF 

44 LDO  Flycatch 

EN 

FALSE 

0  TRUE FALSE 

45 LDI  Flycatching 

FALSE 

0  TRUE 

FALSE 

 
a. Points not listed are not used in this application. 

b. A single value in a column means that the value is the same in English units and in SI units. 

 

continued on next page…

Содержание Siemens APOGEE P1

Страница 1: ...ltd Automation Group SSD Drives Europe cannot accept responsibility for damage injury or expenses resulting there from WARRANTY Parker Hannifin Ltd Automation Group SSD Drives Europe warrants the good...

Страница 2: ...all performance endurance maintenance safety and warning requirements of the application are met The user must analyze all aspects of the application follow applicable industry standards and follow th...

Страница 3: ...for your own information Unit used as a refer to Certification for the Inverter Component Relevant Apparatus Unit fitted Wall mounted Enclosure Application Area The equipment described is intended for...

Страница 4: ...or the product s operation are correctly installed All control and signal terminals are SELV i e protected by double insulation Ensure all external wiring is rated for the highest system voltage Therm...

Страница 5: ...0 2 User Connections to the Main Serial Port P1 3 DIL Switch SW1 Settings 3 Terminal Block TB1 Connections 4 Fitting and Connecting to the Technology Box 4 Wiring Diagrams 5 Initial Check for Connecti...

Страница 6: ......

Страница 7: ...ed twisted pair RS485 Configured using Function Block inputs Protocol tag access for defined P1 parameters Size Notation Part Numbers Size 1 HVAC10 drives use the 6053 APOG APOGEE Technology Box All S...

Страница 8: ...drives by linking a Master PLC or APOGEE controller to one or more HVAC10 drives fitted with this module Plug this Communication Module on to the front of the HVAC10 drive by removing its terminal cov...

Страница 9: ...th 4000ft 1200 metres Technology Box 6053 6055 Technology Box 1 2 3 4 5 6 TB1 Terminal Block 1 2 1 2 PLG1 BI SYNCH 1 Switch SW1 Figure 1 Option showing Terminal Block TB1 and DIL Switch SW1 DIL Switch...

Страница 10: ...you must mount the Operator Station remotely using the Panel Mounting Kit with connecting lead 6052 The connecting lead enters the HVAC10 drive through the gland plate Remove the terminal cover and s...

Страница 11: ...ON OFF 1 2 1 2 0V A B GND APOGEE Controller FL1 FL2 or FL3 connections Figure 3 2 Wire Wiring Diagram for the HVAC10 Size 2 3 Drive 0V DRIVE slave 1 2 3 4 5 6 B A 0V SCR B A 1 2 3 4 5 6 B A 0V SCR B A...

Страница 12: ...C10 Size 2 3 6055 Technology Box The board does not have its own Health or Run LEDs The LEDs are either on the Operator Station or blank cover Module LED This indicates the set up state of the Technol...

Страница 13: ...OT READY DISABLED Initialising FLASH IDLE No data is being received from Network Control Module LONG FLASH SOFT TIMEOUT Drive not addressed in the last 10 seconds ON OK Device has been addressed Note...

Страница 14: ...rameter Select the node ADDRESS 0 to 31 Select the BAUD RATE default is 4800 Check the FAULT parameter for error messages and rectify if necessary When setting values for parameters from DSE Lite or o...

Страница 15: ...fault external 5 MISSING no option fitted Also refer to Module LED page 6 VERSION Range 0x0000 to 0xFFFF The version of the Technology Option card If no option is fitted then the version is reset to z...

Страница 16: ...Option Incorrect Technology Box Option fitted or selected Fit the correct Technology Box Option or select the matching value for the TYPE parameter in the TEC OPTION function block TYPE RS485 Set up...

Страница 17: ...SP FWD 1 0 REV FWD 23 LDI RUN STOP 1 0 RUN STOP 24 LDO RUN SP STOP 1 0 RUN STOP 25 LAO Stop Mode 0 1 0 27 LDO Coast Stop FALSE 1 0 TRUE FALSE 28 LDO Fast Stop FALSE 1 0 TRUE FALSE 29 LDO Day Night DA...

Страница 18: ...2 0 PCT 0 1 0 69 LAO Preset Spd 3 0 PCT 0 1 0 75 LDO Preset Sel MAIN 1 0 PRESET MAIN 77 LDI Purge NORMAL 1 0 PURGE NORMAL 79 LDI Tripped FALSE 1 0 TRUE FALSE 80 LDO Reset Fault OK 1 0 RESET OK 81 LAO...

Страница 19: ...Reference Stop Run Stop Mode 27 Coast Stop Setup Seq Ref Sequencing Logic Not Coast Stop 28 Fast Stop Setup Seq Ref Sequencing Logic Not Fast Stop 29 Day Night Setup Communications Tec Option Night 3...

Страница 20: ...reset Sel Setup Setpoint Funcs Preset Preset 1 Select Input 77 Purge Setup Misc Value Func Value Func 3 Input C 79 Tripped Setup Seq Ref Sequencing Logic Tripped 80 Reset Fault Setup Seq Ref Sequencin...

Отзывы: