Parker RE06M T Series Скачать руководство пользователя страница 20

20

Proportional Pressure Valves

Series RE*T / R*V

Operation Manual

Parker Hannifin Corporation

RE_-R_V obe_24-45-A-B 5715-651 UK 29.01.19

Failure message

Description/corrective action

The Com Port is not available! Terminate the other program, or quit the message and select ano-

ther RS232C port via the menu “Options > Port”. Afterwards recon-
nect the parametrizing cable.

Unable to open COM port

Com port is not available. Quit the message and select another 
RS232C port via the menu “Options > Port”. Afterwards reconnect 
the parametrizing cable.

There is no module/valve 
connected or the communica-
tion is disturbed! Please check 
also the interface!

No data exchange possible. Either the electronic has been remo-
ved, the port is mismatched, or the connection will be disturbed by 
strong electrical fields. Check if the Com port is set for “9600, 8, 1. 
none, none” via the menu “Options > Port”.

Wrong password

Retype the password, notice the exact spelling (case sensitivity).

Wrong input

An unvalid character or a value outside the permitted range has 
been used at parameter entry.

Keep the entered para-me-
ters?

During parameter loading from the electronics memory the preset 
parameters from the left hand screen display may be rejected or 
maintained.

The chosen module/valve 
isn´t the same as the connec-
ted hardware. Attention! Unsa-
ved parameters will be lost.

In principle, parameters dedicated to a type which deviates from 
the connected valve may be edited. However, for data transmitting 
the correct valve has to be connected. If parameters will be loaded 
from a valve which deviates from the selected one, the parameters 
from the left hand side screen display of the program will be ove-
rwritten.

The chosen hardware isn´t 
the same as the connected 
module/valve.

The wrong valve type has been selected from the database, afte-
rwards the function “send all” has been executed.

Attention! Factory settings 
will be changed! Transmit 
anyhow?

Default parameters has been read out from the database instead 
from the valve via the function “receive all”.

file name.pxd already exists. 
Do you want to replace the 
file?

The file name already exists within the indicated directory. Select 
another name, another directory or overwrite the existing file with 
“OK”.

Error messages

Malfunctions when using the ProPxD software program will be indicated via appropriate failure mes-
sages.

Failure messages and corrective actions:

Содержание RE06M T Series

Страница 1: ...R5V Design A R6V Design B Operation Manual Proportional Pressure Valves with integrated Electronics Parker Hannifin Manufacturing Germany GmbH Co KG Industrial Systems Division Europe Gutenbergstr 38...

Страница 2: ...on of the system and components and assuring that all performance endurance maintenance safety and warning requirements of the application are met The user must analyze all aspects of the application...

Страница 3: ...Usage 11 Common Instructions 11 Liability 11 Storage 11 4 Mounting Installation 12 Scope of Supply 12 Mounting 12 Bolt kits 12 Operation Limits 12 Pressure Fluids 13 Air Bleeding of Hydraulic System 1...

Страница 4: ...e Code Interface M Subplate mounting ISO 6264 R 1 1 external drain with pipe only Ordering Code RE T Proportional pressure relief valve Normaly open Seal Design series not required on ordering Onboard...

Страница 5: ...ssure relief valve Normaly open Seal Design series not required on ordering Onboard electronics Nominal size Electronic attachment Command signal RE E T 1 1 0 Slip in mounting Pressure stage Pilot oil...

Страница 6: ...350 bar Code Command signal 10V 0 10 V reference output 10 V 4MA 4 20 mA R V P Interface Pressure stage Code Seal 1 NBR 5 FPM Code Nominal size 03 NG10 06 NG25 10 NG32 Drain port Options Max pressure...

Страница 7: ...1 NBR 5 FPM Body Options SAE interface Code Options PN w o mechanical max adjustment PM with mechanical max adjustment 2 Pilot oil Code Nominal size 06 SAE 08 SAE 1 10 SAE 1 12 1 SAE 1 SAE 61 Code Si...

Страница 8: ...Valve Driver The described integral electronic driver combines all necessary functions for the optimal operation of the valve The most important features are digital circuit design high dynamic const...

Страница 9: ...ize 12 210 30 port Y1 Electrical Duty ratio ED 100 Supply voltage Ub VDC 18 30 ripple 5 eff surge free Current consumption max A 2 0 Pre fusing A 2 5 medium lag Potentiometer supply Up V 10 5 max 10 m...

Страница 10: ...10 Proportional Pressure Valves Series RE T R V Operation Manual Parker Hannifin Corporation RE_ R_V obe_24 45 A B 5715 651 UK 29 01 19 Signal flow diagram...

Страница 11: ...intended The manufacturer is not liable for warranty claims resulting from this Common Instructions We reserve the right for technical modifications of the described product Illustrations and drawings...

Страница 12: ...the insurance company and the supplier Valve type Bolt dimensions Torque value Ordering number RE06M T 4 pcs M5x30 mm 7 6 Nm BK375 RE10M T R4V03 4 pcs M10x35 mm 63 Nm BK505 RE25M T R4V06 4 pcs M10x45...

Страница 13: ...luids note VDMA document 24317 as well as DIN 51524 51502 Special gaskets may be available depending on the utilized fluid In case of insecurity please consult Parker Air Bleeding of Hydraulic System...

Страница 14: ...mbled according the outline below The backshell nut of the cable gland has to be tighten with a suitable tool The target value for the tightening torque is 4 Nm Tighten the cap nut with a torque of ap...

Страница 15: ...mination follows the NA MUR specification NE43 NAMUR is an association of users of process control technology Electrical Interfacing Supply Voltage The supply voltage for the valve has to cover the ra...

Страница 16: ...of voltage command input 0 10 V via potentiometer code F 10V The external potentiometer is fed via the output potentiometer supply To prevent this output from overload the resistance value of the pot...

Страница 17: ...odule storage requirement approx 40 MB If your PC has no serial interface according to RS232C standard you require in addition an USB RS232C adapter Parametrizing cable Ordering code 40982923 The cove...

Страница 18: ...eparameters may be adapted via the expert mode The operating mode may be selected from the Options menu and remains after terminating and re start of the program Changing of expert parameters is only...

Страница 19: ...to the valve operating range P7 MIN Adjustment for positive output signal step at 0 1 command signal To compensate for the operate threshold of the valve function P11 command signal polarity Adjustmen...

Страница 20: ...During parameter loading from the electronics memory the preset parameters from the left hand screen display may be rejected or maintained The chosen module valve isn t the same as the connec ted hard...

Страница 21: ...x filter contaminated replace filter x x x x supply voltage too low keep supply voltage range x supply voltage carries too much ripple reduce ripple x x command signal too low increase command signal...

Страница 22: ...rst Germany Tel 49 181 99 44 43 0 E mail valvesisde parker com 1 Please combine seal kit of one size with seal kit of pro portional section P2 for complete seal kit NBR S26 58473 0 FPM S26 58473 5 Val...

Отзывы: