Evaporator

DI1

1- = Black

1S = Green

1+ = Red

R = Red

G = Green

W = White

B = Black

TS2 - Temp. Sensor 2

TS1 - Temp. Sensor 1

PB1 PB2

8.8.

Temperature

Sensor

SEI/SEH

TS2

TS1

B

W

G

R

1+ 1S

1-

DI1

24

 V

AC

24 VAC

40 VA

Transformer

Pumpdown

Relay

(optional)

Pressure

Transducer

Valve 2 connections

on left block when used

SD-252-408

Pressing the 

UP

 button will increase the set point by 1 unit.

Pressing the 

DOWN

 button will decrease the set point by 1 unit.

Pressing the 

ENTER

 button will change the flashing digit from 1’s digit 

to the 100’s digit.
Press and hold the 

UP

 button and 

ENTER

 button together for 5 seconds to 

save the set point. The digits will stop blinking.

CHANGING

 

REFRIGERANTS

Press and hold the 

UP

 button and 

ENTER

 button simultaneously for 5 

seconds to enable the controller to change to another type of refrigerant. 

All 4 digits will start to blink.
Pressing the 

UP

 button or the 

DOWN

 button will change the display to 

other refrigerants.
When  the  display  shows  the  desired  refrigerant,  press  and  hold  the 

UP

 

button and 

ENTER

 button for together 5 seconds. The controller will save 

and use the selected refrigerant’s table for saturated temperature. The digits 

will stop blinking.

CHANGING VALVE TYPES – LGE1, SML1, or MED1

Press and hold the 

UP

 button and 

ENTER

 button for 5 seconds to enable 

the controller to change to the other type of valves. All 4 digits will start 

to blink.
Pressing either the 

UP

 button or the 

DOWN

 button will change the dis-

play between the different valve types. Press and hold the 

UP

 button and 

ENTER

 button together for 5 seconds to save the selection. The digits 

will stop blinking.
Pressing the 

UP

 button and the 

DOWN

 button simultaneously will toggle 

the display between AC circuit 1 and AC circuit 2.

AC CIRCUIT 2 MENU

The preceding instructions apply to AC circuit 2 as well as AC circuit 1:

SUP2

  Superheat read by controller for AC circuit 2

POS2

  Number of steps valve is open (0-6386) for AC circuit 2

PRS2

  Pressure read by the transducer (0-153 PSI, gauge) for AC

 

circuit 2

TMP2

  Temperature read by the temperature sensor (-50 to 103°F) for 

AC circuit 2

TST2

  Saturated temperature for AC circuit 2

AC2, PDN2

 

AC2 when in normal operation, PDN2 when in pumpdown for 

AC circuit 2

R22, 134A, 407C, 404A, R507

 

R22 for refrigerant R-22, 134A for refrigerant R-134a, 407C for 

refrigerant R-407C, and 404A for refrigerant R-404A and R507 

for refrigerant R-507. 

Note:

 

Not all controllers have both 

R-507 and R-407C.

LGE2, SML2, MED2, ESX2

 

LGE2 if the EEV used is an SEI-50 or larger for AC circuit 2. 

 

SML2 if the EEV used is smaller than an SEI-25 for AC circuit 2. 

 

MED2 if the EEV used is a SEI-25 for AC circuit 2. 

 

ESX2 if the EEV used is a ESX for AC circuit 2. 

SSP2

  Superheat set point (0 to 16°F) for AC circuit 2. Default is 

10°F.

MOP2

  Maximum operating suction pressure set point (0 to 153 PSI) 

for AC circuit 2. Default is 153 PSI.

CTS2

  Cut out suction pressure set point for AC circuit 2 (0 to 153 PSI)

CLP2

  Calibrate pressure transducer for AC circuit 2

CLT2

  Calibrate temperature sensor for AC circuit 2

PRO2

  Proportional gain set point for AC circuit 2. Number of steps 

per degree that superheat is above or below the superheat set 

point (5 to 255 steps per degree). Default is 45 for the LGE2 

setting, 22 for the MED2 setting, or 11 for the SML2 setting.

INT2

  Integral set point for AC circuit 2. Number of seconds the con-

troller waits to update the reference valve position. (1 to 120 

seconds). Default is 10 seconds.

DER2

  Derivative setpoint for valve 2. Advanced algorithm parameter 

that determines the slope of the change control point. Default is 

zero.

DON2

  Time delay in seconds between end of pumpdown and com-

pressor start when Relay 1 is used to pilot the compressor con-

tactor. The pre-opens the valve before compressor start to avoid 

nuisance low pressure safety trips. 2 seconds.

DOF2

  Time in seconds that the valve is shut before the compressor 

Relay 1 opens to stop the compressor. Allows refrigerant pump-

down/pumpout. Default is 2 seconds.

DST2

  Used with DON2. Number of steps to pre-open the valve before 

compressor start. Default varies with valve size.

Page 4

CHILLER P/T CONTROLLER WIRING SCHEMATIC*

© 2008 Sporlan Division, Parker Hannifin Corp., 206 Lange Drive, Washington, Missouri 63090

*Only valve 1 shown, valve 2 connected in similarly.