Installation of the multi-axis system PSD1-M
52 (109)
192-011006N8 2019-07
09.10.19 09:27
2)
Minimum rotating field frequency for peak current at 15 A & 30 A output stages:
f > 3 Hz; with a rotating field frequency of f <3 Hz the maximum peak current duration is 100 ms
3)
Output current bei verschiedenen switching frequency. The default settings of the currents und switching
frequencies are grayed out & in bold.
5.8.3.
X45: Motor connection (PSD1-M)
Motor connection for 3 axes
The respective pins are not assigned with 1- or 2-axis devices!
Designation
Axis
Motor cable lead designation*
CU
3
U / L1
1
U1
CV
3
V / L2
2
U2
CW
3
W / L3
3
U3
FE & PE
3
YE / GN
BU
2
U / L1
1
U1
BV
2
V / L2
2
U2
BW
2
W / L3
3
U3
FE & PE
2
YE / GN
AU
1
U / L1
1
U1
AV
1
V / L2
2
U2
AW
1
W / L3
3
U3
FE & PE
1
YE / GN
* Depending on cable type.
FE: Functional ground
PE: Protective earth
Shielding connection of
the motor cable
The outer shielding of the motor cable must be correctly connected to PE both on
the
drive side
(see page 46, see page 59, see page 30) as well as on the motor
side. Shielding may not be interrupted.
Please observe the notes in chapter “
Operating conditions for CE-conform
operation
(see page 13)“.
5.8.3.1
Motor connection with self-made motor cable
Please consider special features of the
DSL
motor connection with:
•
EX motors,
•
EY motors,
•
NK motors,
•
NV motors and
•
NX motors!
With
these motors with DSL feedback, the outputs U & V are reversed in the PSD
via the motor configuration
This has no effect on the wiring with Parker motor cables,
you can connect them as shown in the table.