In this chapter you can read about:
•
Conditions of utilization for CE-conform operation .................................................................... 11
•
CE declaration of conformity PSD1-M ...................................................................................... 13
•
Conditions of utilization for the cUL certification of PSD1-S ...................................................... 13
3.1
Conditions of utilization for CE-conform operation
3.1.1.
- Industry and trade -
- Industry and trade -
The EC guidelines for electromagnetic compatibility 2014/30/EU and for electrical
operating devices for utilization within certain voltage limits 2014/35/EU are fulfilled
when the following boundary conditions are observed:
Operation of devices only in the state in which they are delivered.
Contact protection mating plug
In order to ensure contact protection, all mating plugs must be present on the device
connections even if they are not wired.
Instructions for this manual
Please respect the specifications of the manual resp. of the help function, especially the
technical characteristics (mains connection, circuit breakers, output data, ambient
conditions,...).
3.1.2.
Mains filter for use in industrial areas
A mains filter is required in the mains input line if the motor cable exceeds a certain
length. Filtering can be provided centrally at the plant mains input or separately at the
mains input to each axis combination.
Use of the devices in the industrial area (limit value class C3 in accordance with EN
61800-3)
The following mains filters are available for self-sufficient utilization:
Device:
Limit value class
Reference: Axis system
with motor cable
Mains filter
Order No.:
PSD1-M_P010
C3
< 6 x 10 m
ECP-0003-01
PSD1-M_P010
C3
< 6 x 50 m
ECP-0003-02
PSD1-M_P020
C3
< 6 x 50 m
ECP-0003-03
3.1.3.
Connection length in-between mains filters & device
In general, the connection mains filter - device shall be as short as possible.
unshielded:
< 0.5 m
shielded:
< 5 m (screen must be connected to ground - e.g. ground - control
cabinet)