Troubleshooting
95
Description
Area/Module
Category
Event Log Message
Format: Date | Time |
Module | Module
Position | Description
Process Input
Status Bits
User Actions
SPI Communication - B40
<Warning>
Note: For this event, no information
is updated in any Data map for
PLC. It is notified only through
Device/Configuration Tool
Indicators and Message Logging.
MS/Co-Proc
Warning
MM-DD-YY | HRS:
MIN:SEC | MS/Co-proc |
--- | N/W Module - SPI
Communication Break
NA
# User can perform the
following options:
Option 1: Restart the
device
Option 2: Upgrade
Firmware of N/W through
FTP
Option 3: Replace the
Device
SPI Communication - B40 Normal
Event
MM-DD-YY | HRS:
MIN:SEC | MS/Co-proc |
--- | N/W Module - SPI
Communication Normal
NA
# No Action Required
RTC VBAT not available
Warning
MM-DD-YY | HRS:
MIN:SEC | MS/Co-proc |
--- | RTC VBAT not
available
NA
# User can perform the
following options:
Option 1: Power Cycle the
Device
Option 2: Insert/Replace
the RTC Battery
Option 3: Replace the
Device
Invalid Configuration from PLC
Note: For this event, no information
is updated in any Data map for
PLC. It is notified only through
Device/Configuration Tool
Indicators and Message Logging.
Warning
MM-DD-YY | HRS:
MIN:SEC | MS/Co-proc |
--- | Invalid Configuration
from PLC
NA
# User can perform the
following options:
Option 1: Set correct
configuration through PLC
Auxiliary Current - Current till
12 Amps
Auxiliary
Current
Event
MM-DD-YY | HRS:
MIN:SEC | Auxiliary
Current | --- | Normal
Auxiliary Current till
12Amps
NA
# No Action Required
Auxiliary Current - Current above
12 Amps
Note: - HW Cut-Off is at 12.7 Amps
Error
MM-DD-YY | HRS:
MIN:SEC | Auxiliary
Current | --- | High
Auxiliary Current above
12Amps
Aux Current bit = 1
Error bit = 1
# User can perform the
following options:
Option 1: Power Cycle the
Device
Option 2: Replace the
Device
Logic Current - Current till
7.5 Amps
Logic Current
Event
MM-DD-YY | HRS:
MIN:SEC | Logic Current |
--- | Normal Logic Current
till 7.5Amps - [<Actual
Current>Amps]
NA
# No Action Required
Logic Current - Current between
7.5 Amps to 8 Amps
Warning
MM-DD-YY | HRS:
MIN:SEC | Logic Current |
--- | High Logic Current
between 7.5Amps to
8Amps - [<Actual
Current>Amps]
Logic Current bit = 1
Warning bit = 1
# User can perform the
following options:
Option 1: Power Cycle the
Device
Logic Current - Current above
8 Amps
Error
MM-DD-YY | HRS:
MIN:SEC | Logic Current |
--- | High Logic Current
above 8Amps - [<Actual
Current>Amps]
Logic Current bit = 1
Error bit = 1
# User can perform the
following options:
Option 1: Power Cycle the
Device
Option 2: Replace the
Device
Содержание PCH1 T P Series
Страница 5: ...General 5 CHAPTER 1 General...
Страница 10: ...Overview 10 CHAPTER 2 Overview...
Страница 27: ...Overview 27 Solenoid addressing...
Страница 30: ...Technical Data 30 CHAPTER 3 Technical Data...
Страница 33: ...PCH Portal Function 33 CHAPTER 4 PCH Portal Function...
Страница 46: ...PCH Portal Function 46 Select Appropriate Box...
Страница 51: ...PCH Portal Function 51 Edit CANopen Startup Entry...
Страница 71: ...Configuration Tool Web Interface 71 CHAPTER 5 Configuration Tool Web Interface...
Страница 90: ...Troubleshooting 90 CHAPTER 6 Troubleshooting...
Страница 100: ...Abbreviation List 100 CHAPTER 7 Abbreviation List...
Страница 102: ...Appendix 102 CHAPTER 8 Appendix...
Страница 107: ...107 Parker Hannifin Corporation Pneumatic Division Americas USA Canada Mexico c parker parker com 1 800 272 7537...