Programming Information

P31P / P32P Series

Electronic Proportional Regulators

Set Proportional Band

Proportional band is used for setting the reaction sensitivity of the regulator.  The displayed value is X 10 mbar and has a range between 50 
(0.5 bar) and 250 (2.5 bar).

Fine Settings

or

or

Parameter Number 12 – Set Proportional Band (P20 Must be Set to 0) 

Step

1

2

3

4

5

Press

3-6 seconds

Until Display 

Reads 

Flashing Decimal

Flashing Decimal 

(value between 

50 and 250)

Flashing

Description

Accesses 

changeable 

parameters.

Accesses 

parameter no. 12.

Displays current 

parameter value.

Incremental 

value is:

x 10 mbar      

Edits parameter.

Accepts and 

saves new 

parameter 

setting.

Sequences to 

next parameter.

Behavior Control

The regulation speed of the pressure regulator can be modified by means of one parameter. (P 20)
The value in this parameter has a range from 0-5.  A higher value indicates slower regulation speed, but will be more stable.

*  When the value 0 is entered, you are able to create your own custom settings true parameters 12, 13 and 21.

or

or

Parameter Number 20 – Set Behavior Control 

Step

1

2

3

4

5

Press

3-6 seconds

Until Display 

Reads 

Flashing Decimal

Flashing Decimal 

(value between 

0 and 5)

Flashing

Description

Accesses 

changeable 

parameters.

Accesses 

parameter no. 20.

Displays current 

parameter value.      

Edits parameter 

0 = custom set* 

1 = fastest (narrow

proportional band)

2 = fast 

3 = normal

4 = slow

5 = slowest 

(proportional

band is broad)

Accepts and 

saves new 

parameter 

setting.

Sequences to 

next parameter.

www.comoso.com

www.comoso.com

Содержание P31P Series

Страница 1: ...Proportional Regulator 0 to 10 volt 4 to 20 mA Proportional Regulator Applications F4 F5 Features Benefits F6 Ordering Information F7 Technical Information F8 F9 Programming Information F10 F15 Dimens...

Страница 2: ...dard 4 20mA Control Signal Software Selectable Modular Mounting 10 bar 2 bar Version Special Applications Clean Line Design Suitable for Washdown IP65 Forced Exhaust Option Available 4 Output Signal V...

Страница 3: ...ts of this industry Automotive Packaging and Food The new Proportional Regulator is designed to quickly and accurately adjust and maintain a set output pressure The unit will operate regardless of flo...

Страница 4: ...ently no way of checking that the set value and the actual value are the same Also no account is taken of external influences such as air consumption by the system which can drastically alter the actu...

Страница 5: ...pin 1 Output Signal Digital PNP D PNP or 0 10V P NPN or 0 10V N 4 20mA fixed M Note These brackets fit both Proportional Regulators and Combined Soft Start Dump Valves Body size Global Mini 1 4 1 Glob...

Страница 6: ...with a digital display indicating the output pressure either in PSI or bar The factory setting is as indicated on the label can be changed through the software at all times parameter 14 Schematic P31P...

Страница 7: ...Dead Band The dead band is preset at 1 3 of Full Scale adjustable via parameter 13 Accuracy Linearity 0 3 of Full Scale Proportional Band The proportional band is preset at 10 of Full Scale Fail Safe...

Страница 8: ...artup connecting to the 24V power supply manual mode is activated This means that the user is able to in decrease the output pressure of the regulator by pressing the UP or DOWN key During this action...

Страница 9: ...0 10V 2 analog 4 20 mA Accepts and saves new parameter setting Sequences to next parameter Adjust Span Analog Output Signal Set value is a of Full Analog range As an example for a 0 10V output signal...

Страница 10: ...ses parameter no 9 Displays current digital display Use up or down arrows and accept to adjust the display value if using an external pressure sensor Accepts and saves new parameter setting Sequences...

Страница 11: ...ress 3 6 seconds Until Display Reads Flashing Decimal Flashing Decimal value between 0 and 100 Flashing Description Accesses changeable parameters Accesses parameter no 19 Displays current parameter v...

Страница 12: ...10 mbar Edits parameter Accepts and saves new parameter setting Sequences to next parameter Behavior Control The regulation speed of the pressure regulator can be modified by means of one parameter P...

Страница 13: ...ashing Description Accesses changeable parameters Accesses parameter no 21 Displays current parameter value Edits parameter 5 fastest regulation 100 slowest regulation Accepts and saves new parameter...

Страница 14: ...M12 Connector 20 0 79 126 25 4 99 57 2 25 28 5 1 12 37 25 1 47 89 3 51 40 1 58 14 3 0 56 4 pin M12 Connector 28 6 1 13 28 6 1 13 175 7 6 94 75 2 96 37 5 1 48 64 4 2 54 105 3 4 16 57 2 2 26 7 0 28 7 0...

Страница 15: ...certain pressure Lower your setpoint value preferably to 0 Volts Reset parameter 18 to 0 Display shows unrealistic value Display maybe configured in the wrong value bar instead of psi Check through p...

Страница 16: ...ee of excursion beyond the dead band This band must exceed the dead band of the unit Proportional Effect The speed at which the unit approaches P2 secondary pressure Sensitivity The smallest change in...

Отзывы: