MT-700 series installer guide 

 

 Page 9 

 

2)

 

The Subsystem cannot be changed on a Node after it has been dropped in Alliance.  To change 
subsystems, the node must be deleted and a new node dropped. 

3)

 

The sensor type cannot be changed on a Sensor after it has been dropped in Alliance.  To change 
sensors, the sensor must be deleted and a new sensor dropped. 

NOTE:

 If a Node or Sensor is deleted in Alliance, its history and logs will also be removed. 

Additional Features 

Alarms 

Alarm Set 2 

In addition to the standard alarm threshold, the controller provides a second set of alarm parameters 
that can be used to complement the primary alarm.  The second set is usually configured with narrower 
alarm limits, but a longer set time.  This can be used to identify poorly performing equipment and warn 
when product shelf life may be reduced.  For example, the primary alarm can be set to activate if the 
measured temperature is 15°F above optimal for one hour; but the second alarm can be set to activate 
if the measured temperature is 8°F above optimal for four hours.  This second condition may not 
warrant a high priority alarm; but it can be a good indicator that the system needs attention. 
By default, Alarm Set 2 is inactive and must be enabled on each sensor. 
To configure 

Set 2, open the ‘Alarm Settings’ tab in the sensor configuration win

dow.  In the lower right 

portion, click 

‘Set 2 Active’ and modify the alarm settings as desired.

  

Click the ‘OK’ button to save 

changes. 

NOTE

: When a sensor is configured for Dual Use, Set 2 is used as the primary alarm for the second 

temperature setting.  For details, see the Dual Use Sensors section. 

Cumulative Alarms 

One advanced feature built into Micro Thermo monitoring is Cumulative Alarming.  The Cumulative 
Alarm monitors an input over an extended period of time (usually 24 or 48 hours), and calculates the 
total time that the input exceeds the high/low limits.  This differs from the standard alarm sets, which 
require a continuous high/low measurement to activate.  Instead of resetting every time the 
measurement returns within limits, the Cumulative Alarm counts all current and previous exceptions 
that occur within the Cumulative Period. 
The Cumulative Alarm is an integral part of temperature monitoring, for maintaining food quality and 
shelf life.  The cumulative effect of temperature variations has a significant impact on refrigerated food. 
The variations can also be an indicator of current or developing issues in the system 

 the instability 

being caused either adjacent to the sensor or propagating from elsewhere in the system.  In either case, 
a Cumulative Alarm should be investigated to determine the cause. 
To configure the 

Cumulative Alarm, open the ‘Alarm Settings’ tab in the sensor configuration window.  

In the upper right section, select the alarm set to use for high/low limits and then specify the Set Time 
and Cumulative Period parameters. 

Disabling Alarms 

The U700 Monitoring Node allows alarms to be disabled for individual sensors.  Permanently disabling 
an alarm inhibits all alarms for that specific sensor.  This remains in effect until a technician manually re-
enables the alarm through Alliance.  While an alarm is disabled, the icon in Alliance will appear light blue 
for easy identification.  However, if a sensor never requires an alarm (e.g., an auxiliary input), it may be 
preferable to leave the alarm enabled with the alarm limits set to the 

sensor’s min/max range.  T

his will 

effectively disable the alarm, but will not affect the Alliance display. 

Содержание MT-700 Series

Страница 1: ...Supermarket Control Solutions Installation and Operation Manual PUID 70 MTA 1017 R4 0 11221...

Страница 2: ...ther materials provided from Parker or its subsidiaries or authorized distributors To the extent that Parker or its subsidiaries or authorized distributors provide component or system options based up...

Страница 3: ...ller module For DIN rail mounting mount the DIN rail in the desired location and attach the two controller modules to the rail separately First install the MT 722A controller at the left end of the DI...

Страница 4: ...Transformer 24VAC 250VA BAS Building Automated Station Data cable Passive or powered sensors Passive or powered sensors Passive or powered sensors Passive or powered sensors Passive or powered sensors...

Страница 5: ...perature Sensors Connect one lead to Signal Common connect the other lead to the desired Universal Input UI Temperature sensors are not polzarized Pressure Transducers Connect the Red lead to controll...

Страница 6: ...Node Next for the U700 controller to be paired with Alliance and the firmware installed on the controller 1 Click on the newly created node icon 2 In the configuration window that opens give the cont...

Страница 7: ...ify the upper lower threshold above below which an alarm will be generated Set Time specify the time delay during which the sensor must remain outside of the high low limit before an alarm is generate...

Страница 8: ...cumulative alarm time if applicable The graph s zoom level can be set to display between 1 Hour and 4 Days of data at a time and the statistical data displayed along the right hand side is continuousl...

Страница 9: ...d feature built into Micro Thermo monitoring is Cumulative Alarming The Cumulative Alarm monitors an input over an extended period of time usually 24 or 48 hours and calculates the total time that the...

Страница 10: ...different controllers At any point a sensor can be changed back to Single Usage and the Alarm Set 1 settings will be retained To configure a sensor for dual use first open the Details tab in the sens...

Страница 11: ...and select the Calculation tab Local and Remote resources must be configured before the calculation blocks can be set up For Remote sources click one of the Remote Source buttons and specify the Type...

Страница 12: ...1 LonWorks TP FTT 10 Network 78kbps Wire 18 AWG 7 26 stranded unshielded twisted pair Belden 8461 or equivalent Operating Temperature 13 F to 140 F 25 C to 60 C 0 90 RH non condensing Storage Temperat...

Страница 13: ...MT 700 series installer guide Page 13 U700 Field Wiring 4A Fuse...

Страница 14: ...ometric 15 Vdc output 100 mA max internally limited Communication LonWorks port TP FT 10 channels transceiver featuring polarity insensitive free topology star daisy chain bus loop or mixed topology w...

Страница 15: ...0K of SRAM 4K on battery back up for data Real Time Clock with battery back up Flash memory 2Mbytes with file system for application or data logging file storage on SPI microcontroller external Bus EE...

Страница 16: ...5V 15V outputs Inputs Universal input x16 0 10V thermistor RTD Outputs 5 0 Vdc output 200 mA max internally limited ratiometric 15 Vdc output 100 mA max internally limited Indicators Buttons Status Gr...

Страница 17: ...orm C Dry contact 5A 250V Max fuse protected 2AG 5A 250V 5 0 Vdc output 100 mA max internally limited ratiometric 15 Vdc output 100 mA max internally limited Indicators Buttons Status Green LED Status...

Страница 18: ...4 0 10V thermistor RTD Outputs MVC output x2 Modulating Valve Control for bipolar 4 wire stepper motor Current limited Motor coil resistance range 6 to 100 1 4 W to 6 W 5 0 Vdc output 65 mA max intern...

Страница 19: ...lay output x4 1 form C Dry contact 5A 250V Max fuse protected 2AG 5A 250V 5 0 Vdc output 100 mA max internally limited ratiometric 15 Vdc output 100 mA max internally limited Indicators Buttons Status...

Страница 20: ...per motor 2 banks of 4 outputs with only one output active per bank Current limited Inactive outputs are high impedance no holding current Motor coil resistance range 6 to 100 1 4 W to 6 W Indicators...

Страница 21: ...utton x8 To manually activate relays RO 1 to 8 Hardware features Microcontroller ARM Cortex M0 48MHz 64Kbytes of flash memory for program 8K of SRAM for data 20 FE 2018 20 FE 2018 Relay Outputs RO Use...

Страница 22: ...oftware selectable Input Precision coming Power supply outputs for sensors 5V ratiometric 15V see specific module specification for maximum load 26 MR 2014 Analog Outputs AO Used on Main controller 6U...

Отзывы: