ICEP002 (60Hz)
4.4.2 Temperature
control
PARAMETER
CODE
TYPE
DEFAULT
Temperature control set point
SEt
D
C°
--
F°
--
Temperature control set point
“
CPt
=
On
”
SEt
D
C°
20.0
F°
68.0
Temperature control differential
(NOT visible with code “
CPt
=
On
”)
dIFI
D
C°
4
F°
7.2
4.4.3
Energy saving temperature control
PARAMETER
CODE
TYPE
DEFAULT
energy saving enable
ESE
D
OFF
Set energy saving
SEt_ES
D
C°
20.0
F°
68.0
4.4.4 Compressor
parameters
PARAMETER
CODE
TYPE
DEFAULT
Minimum `On’ time.
dAS
F
2
Minimum time between two com-
pressor switch-ons.
dES
F
5
Compressor hour counter 1
AbCI
D
0
4.4.5
B1, B2 sensor parameters
PARAMETER
CODE
TYPE
DEFAULT
High temperature alarm (water)
HA1
D
C°
60
F°
140
Low temperature alarm (water)
LA1
U
C°
-20
F°
-4
High temperature alarm
(evaporator)
HA2
U
C°
60
F°
140
Low temperature alarm (evapo-
rator)
LA2
U
C°
3
F°
37.4
4.5 Change parameters
4.5.1 Parameter
(
SEt
/
dIFI
/
dEF
)
Fig.2
set
set
set
set
set
PAr
esc
set
Y
Y
set
Y
P_nA
tEr
CnP
r9E
Y
Y
PbI
Y
Y
Ar9
Y
HA1
Y
C1H
Y
Y
C1H2
SEt
Y
diFI
CF30
CF31
CF32
dEF
Y
Y
Y
Y
Y
4.5.2
Water temperature setting (see fi g.1/2)
1. Turn the main swicth (QS) to “ON” and wait for the “
OFF
” visualiza-
tion.
2. Press the buttons “
esc
” “
set
” together to enter on the parameter
type “
D”
.
3. Select the parameter “
PAr
”using “
”and “
” buttons and
press the button “
set
” to enter.
4. Select the parameter “
tEr
”using “
”and “
” buttons and
press the button “
set
” to enter.
5. Select the parameter “
SEt
”using “
”and “
” buttons and
press the button “
set
” to enter.
6. Change the value using “
”and “
” buttons and press the but-
ton “
set
” to confi rm and exit.
7. Press the button “
esc
” three times to exit.
4.5.3
Differential setting (see fi g.1/2)
1.Turn the main swicth (QS) to “ON” and wait for the “
OFF
” visualiza-
tion.
2.Press the buttons “
esc
” “
set
” together to enter on the parameter
type “
D”
3.Select the parameter “
PAr
”using “
”and “
” buttons and
press the button “
set
” to enter.
4. Select the parameter “
tEr
”using “
”and “
” buttons and
press the button “
set
” to enter.
5. Select the parameter “
dIFI
”using “
”and “
” buttons and
press the button “
set
” to enter.
6. Change the value using “
”and “
” buttons and press the but-
ton “
set
” to confi rm and exit.
7. Press the button “
esc
” three times to exit.
4.5.4
Restore default parameters (see fi g.1/2)
1.Turn the main swicth (QS) to “ON” and wait for the “
OFF
” visualiza-
tion.
2.Press the buttons “
esc
” “
set
” together to enter on the parameter
type “
D”
3.Select the parameter “
PAr
”using “
”and “
” buttons and
press the button “
set
” to enter.
4. Select the parameter “
P_nA
”using “
”and “
” buttons and
press the button “
set
” to enter.
5. Select the parameter “
dEF
”using “
”and “
” buttons and
press the button “
set
” to enter.
6. Change the value “
OFF
” to “
On
” using “
”and “
” buttons
and press the button “
set
” to confi rm and exit.
7. Press the button “
esc
” three times to exit.
Содержание ICEP002
Страница 2: ......
Страница 35: ...Ap ndice Appendix Appendice Hyperchill 60Hz Plus ICEP002 DATE 14 02 2022 Rev 7 CODE 398H271671...
Страница 36: ......
Страница 48: ...7 6 Circuit Diagram water 11 ICEP002...
Страница 50: ...7 7 Wiring diagram 13 ICEP002 Sheet 1 6...
Страница 51: ...7 7 Wiring diagram 14 ICEP002 Sheet 2 6 C KA...
Страница 52: ...7 7 Wiring diagram 15 ICEP002 Sheet 3 6...
Страница 53: ...7 7 Wiring diagram 16 ICEP002 Sheet 4 6...
Страница 54: ...7 7 Wiring diagram 17 ICEP002 Sheet 5 6...
Страница 55: ...7 7 Wiring diagram 18 ICEP002 Sheet 6 6 Max L 3Mt...