   Hyperchiller  310-360

1 Safety

1.1  Importance of the manual

•  Keep it for the entire life of the machine.
•  Read it before any operation.
•  It is subject to changes: for updated information see the 
version on the machine.

1.2 Warning signals

!

Instruction for avoiding danger to persons.

Y

Instruction for avoiding damage to the equipment.

Z

The presence of a skilled or authorized technician is 
required.

,

There are symbols whose meaning is given in the 
para. 7.

1.3 Safety instructions

Every unit is equipped with an electric disconnecting 

switch for operating in safe conditions. Always use this device 
in order to eliminate risks maintenance.

!

 The manual is intended for the end-user, only for op-

erations performable with closed panels: operations like 
installation/commissioning/maintenance or that requir-
ing opening with tools must be carried out by skilled and 
qualifi ed personnel.

Do not exceed the design limits given on the dataplate.

! Y

 It is the user’s responsibility to avoid loads different 

from the internal static pressure. The unit must be appropriately 
protected whenever risks of seismic phenomena exist.
Only use the unit for professional work and for its intended 
purpose.

The user is responsible for analysing the application 

aspects for product installation, and following all the applicable 
industrial and safety standards and regulations contained in the 
product instruction manual or other documentation supplied 
with the unit.
Tampering or replacement of any parts by unauthorised per-
sonnel and/or improper machine use exonerate the manufac-
turer from all responsibility and invalidate the warranty. 
The manufacturer declines and present or future liability for 
damage to persons, things and the machine, due to negligence 
of the operators, non-compliance with all the instructions given 
in this manual, and non-application of current regulations re-
garding safety of the system.

The manufacturer declines any liability for damage due to 
alterations and/or changes to the packing.
It is the responsibility of the user to ensure that the specifi ca-
tions provided for the selection of the unit or components and/
or options are fully comprehensive for the correct or foresee-
able use of the machine itself or its components.

Y

 

IMPORTANT: The manufacturer reserves the right to 

modify this manual at any time. 
For the most comprehensive and updated information, the 
user is advised to consult the manual supplied with the 
unit.

1.4 Residual risks

The installation, start up, stopping and maintenance of the 
machine must be performed in accordance with the information 
and instructions given in the technical documentation supplied 
and always in such a way to avoid the creation of a hazardous 
situation. 
The risks that it has not been possible to eliminate in the design 
stage are listed in the following table.

part

affected

residual

risk

manner of

exposure

precautions

heat ex-
changer coil

small cuts

contact

avoid contact, wear 
protective gloves

fan grille 
and fan

lesions

insertion of 
pointed objects 
through the grille 
while the fan is in 
operation

ndo not poke 
objects of any type 
through the fan grille 
or place any objects 
on the grille

inside the 
unit:
compres-
sor and 
discharge 
pipe

burns

contact

avoid contact, wear 
protective gloves

inside the 
unit:
metal parts 
and electri-
cal wires

intoxi-
cation, 
electrical 
shock, 
serious 
burn

defects in the 
insulation of the 
power supply 
lines upstream 
of the electrical 
panel; live metal 
parts

adequate electrical 
protection of the 
power supply line; 
ensure metal parts 
are properly con-
nected to earth

outside the 
unit:
area sur-
rounding 
the unit

intoxica-
tion, seri-
ous burns

iire due to 
short circuit or 
overheating of 
the supply line 
upstream of the 
unit’s electrical 
panel

sensure conduc-
tor cross-sectional 
areas and the sup-
ply line protection 
system conform to 
applicable regula-
tions

Index

1 Safety 

1

1.1  Importance of the manual ................................................... 1
1.2 Warning signals ................................................................... 1
1.3 Safety instructions ............................................................... 1
1.4 Residual risks ...................................................................... 1

2 Introduction 

2

2.1 Transport 

.............................................................................. 2

2.2 Handling .............................................................................. 2
2.3 Inspection ............................................................................ 2
2.4 Storage ................................................................................ 2

3 Installation 

2

3.1 Operating space .................................................................. 2
3.2 Foundation 

........................................................................... 2

3.3 Versions ............................................................................... 2
3.4 Water circuit 

......................................................................... 2

3.5 Electrical circuit ................................................................... 3
3.6  Water-cooled version (W) .................................................... 3

4 Control 

4

4.1 Control panel ....................................................................... 4
4.2  Starting the chiller ................................................................ 4
4.3   Visualization probes ............................................................ 5
4.4  Visualization of digital outputs/analog inputs ...................... 5
4.5 Parameter settings .............................................................. 5
4.6  Direct parameter (DIrE) ........................................................ 5
4.7  Service parameters (USER) ................................................. 6
4.8 Chiller operation .................................................................. 7
4.9 Alarms management 

............................................................ 7

4.10 Automatic restart ............................................................... 7

5 Option 

8

5.1 Precision Control 
(Control pCOM) .......................................................................... 8
5.2  Precision C Low ambient temp.(-10C°) 
(Control pCOM) .......................................................................... 8
5.3  Low ambient temp. L2/L3 (-20/30 C°) 
(Control pCOM) .......................................................................... 8

6 Maintenance 

9

6.1 General instructions 

............................................................. 9

6.2 Preventive maintenance ...................................................... 9
6.3 Refrigerant ........................................................................... 9
6.4 Dismantling .......................................................................... 9

7 Troubleshooting 

10

8 Appendix

Содержание Hyperchill ICE310

Страница 1: ...Hyperchill pCO5 50Hz ICE310 ICE360 DATE 07 12 2022 Rev 00 CODE 398H271841 IT Manuale d uso EN User Manual ES Manual de uso DE Benutzer Handbuch FR Manuel d utilisation PT Manual do utilizador...

Страница 2: ......

Страница 3: ...ontenute nel presente manuale senza alcun preavviso Ai ni di una completa ed aggiornata infor mazione si raccomanda all utente di consultare il manuale a bordo unit 1 4 Rischi residui L installazione...

Страница 4: ...ltro a rete su ingresso acqua di condensazione Per particolari acque di raffreddamento deionizzata deminera lizzata distillata imateriali standard previsti per il condensatore potrebbero non essere ad...

Страница 5: ...ci delle tensioni ed angoli di fase fra fasi consecutive uguali fra loro Il massimo squilibrio ammesso fra le tensioni pari al 2 Collegamento 1 L alimentazione elettrica dei refrigeratori viene effett...

Страница 6: ...la scritta ON con la freccia lampeggiante premere il tasto P6 per avviare il chiller Water Outlet Temp b1 7 0 C Pump Comp 1 Comp 3 Comp 2 Comp 4 Simbolo Stato Descrizione fisso OFF fisso ON lampeggian...

Страница 7: ...UTPUT Pump Compressor 1 Compressor 2 Compressor 3 Compressor 4 DIGITAL OUTPUT A Freeze Unit Status Gen Alarm Fan 1 Fan 2 Fan 3 ANALOG INPUT b1 10 0 C b2 7 0 C b5 20 0 C P1 10 0 bar P2 10 0 bar 4 5 De...

Страница 8: ...ibrazione sonda CA2 U 0 0 4 7 4 Parametri sonda b5 Temperatura ambiente PARAMETRO CODICE TIPO DEFAULT Allarme alta temperatura HA5 U 60 0 Allarme bassa temperatura LA5 U 20 0 Calibrazione sonda CA5 U...

Страница 9: ...uasto per eliminare il guasto Eseguire la riparazione premere il tasto P1 Se apparir la scritta noAL noAL HP1 High pressure Alarm Circuit 1 premere il tasto P1 per resettare l allarme 4 9 1 Allarmi da...

Страница 10: ...t 1 OFF 15 bar ON 19bar Set 2 OFF 16 bar ON 20bar Set 3 OFF 17 bar ON 21 bar 5 2 Bassa temperatura ambiente L2 L3 20 30 C controllo pCOM PARAMETRO CODICE TIPO DEFAULT Set point termostatazione SEt D 7...

Страница 11: ...are apposito liquido detergente b Z ogni 3 anni installazione kit manutenzione ogni 3 anni Sono disponibili vedere paragrafo 7 4 a kit manutenzione ogni 3 anni b kit service 1 kit compressore 2 kit ve...

Страница 12: ...RE IL FILTRO ALETTE DEL CONDENSATORE SPORCHE PULIRE LE ALETTE DEL CONDENSATORE SUPERFICIE DEL CONDENSATORE OSTRUITA LIBERARE LA SUPERFICIE FRONTALE DEL CONDENSATORE PORTATA ACQUA INSUFFICIENTE AUMENTA...

Страница 13: ...ify this manual at any time For the most comprehensive and updated information the user is advised to consult the manual supplied with the unit 1 4 Residual risks The installation start up stopping an...

Страница 14: ...eralized deionized or distilled it is necessary to contact the manufacturer to verify which kind of condenser should be used since the standard material may not be suitable 3 4 Water circuit 3 4 1 Che...

Страница 15: ...tive phases must be equal The maximum permissible voltage imbalance is 2 Connection 1 The electrical power supply must be connected to the chiller using a 4 wire cable comprising 3 phase conductors an...

Страница 16: ...P6 to confirm ON the message ON appears with the arrow flashing Press the button P6 to start the chiller Water Outlet Temp b1 7 0 C Pump Comp 1 Comp 3 Comp 2 Comp 4 Symbol Status Description fixed OFF...

Страница 17: ...1 Compressor 2 Compressor 3 Compressor 4 DIGITAL OUTPUT A Freeze Unit Status Gen Alarm Fan 1 Fan 2 Fan 3 ANALOG INPUT b1 10 0 C b2 7 0 C b5 20 0 C P1 10 0 bar P2 10 0 bar 4 5 Parameter settings Gener...

Страница 18: ...on CA2 U 0 0 4 7 4 b5 probe parameters Ambient temperature PARAMETER CODE TYPE DEFAULT High temperature alarm HA5 U 60 0 Low temperature alarm LA5 U 20 0 Sensor calibration CA5 U 0 0 4 7 5 Compressor...

Страница 19: ...larm Carry out the repair press the button P1 If this message appear noAL noAL HP1 High pressure Alarm Circuit 1 press the button P1 to reset the alarm 4 9 1 Digital input alarms CODE DESCRIPTION RESE...

Страница 20: ...F 3 0 Set 1 OFF 15 bar ON 19bar Set 2 OFF 16 bar ON 20bar Set 3 OFF 17 bar ON 21 bar 5 2 Low ambient temp L2 L3 20 30 C Control pCOM 5 2 1 Direct parameter DIRECT PARAMETER CODE TYPE DEFAULT Temperat...

Страница 21: ...y carry out a Z every 4 months clean the condenser fins and make sure compressor electrical absorption is within the dataplate values b Z yearly W version in case of encrustations inside the condenser...

Страница 22: ...GE RANT FILTER CLOGGED RENEW THE FILTER CONDENSER FINS DIRTY CLEAN THE FINS OF THE CONDENSER CONDENSER SURFACES CLOGGED CLEAR THE FRONT SURFACE OF THE CONDENSER INSUFFICIENT WATER FLOW INCREASE THE FL...

Страница 23: ...ho de modi car sin previo aviso la informaci n de este manual Para que la informaci n resulte completa se recomienda al usuario consultar el manual a pie de m quina 1 4 Riesgos residuales Las operacio...

Страница 24: ...st ndar previstos para el con densador no sean adecuados para determinadas aguas de re frigeraci n desionizada desmineralizada destilada En estos casos se ruega ponerse en contacto con el fabricante 3...

Страница 25: ...s indicadas en el esquema el ctrico las cuales salvo indicaci n diversa son 10 para la tensi n y 1 para la frecuencia 2 La tensi n debe ser sim trica valores eficaces de las tensiones y ngulos de fase...

Страница 26: ...par metro On Main menu 1 7 On OFF USER Pulse el bot n P6 para confirmar ON aparece el mensaje ON con la flecha intermitente Pulse el bot n P6 para encender el enfriador Water Outlet Temp b1 7 0 C Pum...

Страница 27: ...Compressor 2 Compressor 3 Compressor 4 DIGITAL OUTPUT A Freeze Unit Status Gen Alarm Fan 1 Fan 2 Fan 3 ANALOG INPUT b1 10 0 C b2 7 0 C b5 20 0 C P1 10 0 bar P2 10 0 bar 4 5 De nici n de los par metro...

Страница 28: ...ratura evaporador 1 PAR METRO C DIGO TIPO PREDET Configuraci n alta temperatura 1 cHA2 U 0 Alarma de alta temperatura 1 HA2 U 60 0 Alarma de baja temperatura 1 LA2 U 3 0 Calibraci n de la sonda CA2 U...

Страница 29: ...na alarma Pulse el bot n para ver el tipo de alarma HP1 High pressure Alarm Circuit 1 Nota elimine la causa de la falla para borrar la alarma Realice la reparaci n Pulse el bot n P1 Si aparece este me...

Страница 30: ...et 1 OFF 15 bar ON 19bar Set 2 OFF 16 bar ON 20bar Set 3 OFF 17 bar ON 21 bar 5 2 Baja temperatura ambiente L2 L3 20 30 C Control pCOM 5 2 1 Par metro directo DIRECT PAR METRO C DIGO TIPO PREDET Ajust...

Страница 31: ...rantizar la m xima eficacia y fiabilidad del refrigerador hay que Z ocada mes climpiar las aletas del condensador Versi n por biog s Z ocada 6 meses climpiar las aletas del condensador y controlar que...

Страница 32: ...ANTE ATASCADO SUSTITUIR EL FILTRO ALETAS DEL CONDENSADOR SUCIAS LIMPIAR LAS ALETAS DEL CONDENSADOR SUPERFICIE DEL CONDENSADOR OBSTRUIDA LIBERAR LA SUPERFICIE FRONTAL DEL CONDENSADOR CAUDAL DE AGUA INS...

Страница 33: ...f r die Anlagensicherheit zur ckzuf hren sind Der Hersteller bernimmt keine Haftung f r eventuell durch Austausch und oder nderung an der Verpackung entstandene Sch den Der Anwender hat sich zu vergew...

Страница 34: ...m Umweltschutz 3 1 Betriebsbereich Zur Gew hrleistung eines ungehinderten Luftstroms und zur Wartung der Einheit ist umfangsseitig ein ausreichender Mindestfreiraum ohne Behinderungen sicherzustellen...

Страница 35: ...obei Vtot Gesamtvolumen des Kreises in Liter Pt min max spezifisches Gewicht bei Mindest H chsttempe ratur die vom Wasser erreicht werden kann kg dm3 Bez glich der Werte des spezifischen Gewichts je n...

Страница 36: ...ngsstutzen auf der R ckseite der Einheit anschlie en 3 Flie t das Kondenswasser in einem offenen Kreislauf ist es ratsam den Kreis mit einem Filter im Kondensatoreinlass auszustatten um die Gefahr der...

Страница 37: ...nicht berschreitet d Den Chiller ausschalten und bei SET Temperatur den Hyd raulikkreislauf nachf llen e berpr fen dass die Temperatur des behandelten Was sers nicht unter 5 C und die Raumtemperatur...

Страница 38: ...e Betriebsstunden z hler Einheit tHU U 0 Alarmschwelle Betriebsstunden z hler Verdichter 1 tH1 U 0 Alarmschwelle Betriebsstunden z hler Verdichter 2 tH2 U 0 Alarmschwelle Betriebsstunden z hler Verdic...

Страница 39: ...4 8 Parameterverwaltung 4 8 1 Status Maschine Am digitalen Ausgang ist die status maschine sichtbar Status Beschreibung Unit Status Kaltwassersatz AUS Unit Status Kaltwassersatz AN 4 8 2 Pumpe Wenige...

Страница 40: ...4 10 Automatischer Neustart Bei einemAusfall der elektrischenVersorgung bleibt nach deren Wiederherstellung der Status des Kaltwassersatzes ON bzw OFF unver ndert 5 Option 5 1 Niedrige Umgebungstemper...

Страница 41: ...e Effizienz und Zuverl ssigkeit des Chiller werden empfohlen Z alle Monat Reinigung der Rippen des Kondensators Biogas Version Z alle 6 Monate Reinigung der Rippen des Kondensators und berpr fung der...

Страница 42: ...T FILTER ERSETZEN RIPPEN DES KONDENSATORS VERSCHMUTZT RIPPEN DES KONDENSATORS REINIGEN OBERFL CHE DES KONDENSATORS BEDECKT BEDECKUNG AN FRONTOBERFL CHE DES KONDENSATORS ENTFERNEN WASSER VOLU MENSTROM...

Страница 43: ...es pour une utilisation correcte de cette m me unit ou de ses composants Y ATTENTION Le fabricant se r serve le droit de modi er sans aucun pr avis les informations contenues dans ce manuel A n de dis...

Страница 44: ...ur l arriv e d eau de condensation Pour des eauxde refroidissement sp ciales d ionis e d min ralis e distill e les mat riaux standard pr vus pour le conden seur pourraient ne pas tre appropri s Dans c...

Страница 45: ...nce 2 La tension doit tre sym trique valeurs efficaces des tensions et des angles de phase entre phases cons cutives gales Le d s quilibre maximal admis entre les tensions est de 2 Raccordement 1 L al...

Страница 46: ...pal Appuyer sur le bouton P5 pour s lectionner On Main menu 1 7 On OFF USER Appuyer sur le bouton P6 pour confirmer ON le message ON appara t avec la fl che clignotante Appuyer sur le bouton P6 pour a...

Страница 47: ...mpressor 1 Compressor 2 Compressor 3 Compressor 4 DIGITAL OUTPUT A Freeze Unit Status Gen Alarm Fan 1 Fan 2 Fan 3 ANALOG INPUT b1 10 0 C b2 7 0 C b5 20 0 C P1 10 0 bar P2 10 0 bar 4 5 D nition des par...

Страница 48: ...Temp rature vaporateur 1 PARAM TRE CODE TYPO D FAUT Configuration haute temp rature 1 cHA2 U 0 Alarme haute temp rature 1 HA2 U 60 0 Alarme basse temp rature 1 LA2 U 3 0 Calibrage sonde CA2 U 0 0 4 7...

Страница 49: ...1 est rouge une alarme est pr sente Press the button to see the type of alarm HP1 High pressure Alarm Circuit 1 Remarque liminer la cause du d faut pour effacer l alarme Effectuez la r paration Appuye...

Страница 50: ...dIF F 3 0 Set 1 OFF 15 bar ON 19bar Set 2 OFF 16 bar ON 20bar Set 3 OFF 17 bar ON 21 bar 5 2 Basse temp rature ambiante L2 L3 20 30 C Contr le pCOM 5 2 1 Param tres Direct DIRECT PARAM TRE CODE TYPO D...

Страница 51: ...la garantie 6 2 Entretien pr ventif ou pr dictif Pour garantir dans le temps l efficience maximum et la fiabilit de l appareil proc der comme suit Z tous les mois nettoyage des ailettes du condenseur...

Страница 52: ...AILETTES DU CONDENSATEUR SALES NETTOYER LES AILETTES DU CONDENSATEUR SURFACE DU CONDENSEUR BOUCH E LIB RER LA SURFACE FRONTALE DU CONDENSATEUR D BIT D EAU INSUFFISANT AUMENTARE LA PORTATA DEL FLUI DO...

Страница 53: ...reito de modi car as in forma es contidas no presente manual sem incorrer na obriga o de avis las previamente Para obter informa es completas e actualizadas recomenda se ao utilizador de consultar o m...

Страница 54: ...previstos para o condensador po dem n o ser adequados Nesse caso queira contactar o fabricante 3 4 Circuito hidr ulico 3 4 1 Controlos e liga o Y ACerti que se de que as tubagens est o devidamente li...

Страница 55: ...es e ngulos de fase entre fases consecutivas iguais entre si O dese quil brio m ximo admitido entre as tens es de 2 Liga o 1 A alimenta o el ctrica dos refrigeradores efectuada mediante um cabo de 4...

Страница 56: ...ra con rmar ON a mensagem ON aparece com a seta piscando Prima o bot o P6 para iniciar Water Outlet Temp b1 7 0 C Pump Comp 1 Comp 3 Comp 2 Comp 4 S mbolo Status Descri o xo OFF xo ON piscando Esperan...

Страница 57: ...digitais e as entradas anal gicas dispon veis DIGITAL OUTPUT Pump Compressor 1 Compressor 2 Compressor 3 Compressor 4 DIGITAL OUTPUT A Freeze Unit Status Gen Alarm Fan 1 Fan 2 Fan 3 ANALOG INPUT b1 1...

Страница 58: ...nda b2 Temperatura evaporador 1 PAR METRO C DIGO TIPO DEFAULT Con gura o de temperatura elevada 1 cHA2 U 0 Alarme de temperatura elevada 1 HA2 U 60 0 Alarme de baixa temperatura 1 LA2 U 3 0 Calibragem...

Страница 59: ...ho una alarma est presente Prima o bot o para ver o tipo de alarme es HP1 High pressure Alarm Circuit 1 Nota elimine a causa da falha para limpar o alarme Fa a o reparo Prima o bot o P1 Se esta mensag...

Страница 60: ...EF3 F 21 0 Diferencial dIF F 3 0 Set 1 OFF 15 bar ON 19bar Set 2 OFF 16 bar ON 20bar Set 3 OFF 17 bar ON 21 bar 5 2 Baixa temperatura ambiente L2 L3 20 30 C Controle pCOM 5 2 1 Par metros direto DIREC...

Страница 61: ...preventiva Para garantir a m xima e ci ncia e abilidade do refrigerador ao longo do tempo veri que Z de m s limpeza do condensador vers o biog s Z de 6 em 6 meses limpeza do condensador e veri ca o d...

Страница 62: ...ERA O ENTUPIDO SUBSTITUA O FILTRO ALHETAS DO CONDENSADOR SUJAS LIMPE AS ALHETAS DO CONDENSADOR SUPERF CIE DO CONDENSADOR OBSTRU DA DESOBSTRUA A SUPERF CIE FRONTAL DO CONDENSADOR D BITO DE GUA INSUFICI...

Страница 63: ...Appendice Anhang Ap ndice Appendix Appendice Anexo...

Страница 64: ...CONTENTS 7 1 Legend 1 7 2 Handling 7 3 Operating space 10 7 4 Installation diagram 11 7 5 Technical data standard 12 7 6 Dimensions 13 7 7 Spare parts 14 7 9 Wiring diagram 17...

Страница 65: ...namiento During transport and stockage Pendant le transport et l entreposage Durante o transporte e armazenamento Dopo l installazione Nach der Installation Tras la colocaci n After installation Apr s...

Страница 66: ...pressure Pression maximum d utilisation c t air Press o m xima de funcionamento do lado do ar Valori di taratura Einstellwerte Valores de calibraci n Calibration values Valeurs de r glage Valores de c...

Страница 67: ...rico Electrical supply inlet Entr e alimentation lectrique Entrada da alimenta o el ctrica Posizione di fissaggio Position Befestigungsbohrungen Posici n orificios de fijaci n Base fixing holes positi...

Страница 68: ...de flujo Sight glass T moin de d bit Luz de fluxo 7 Filtro refrigerante K ltemittelfilter Filtro refrigerante Refrigerant filter Filtre r frig rant Filtro refrigerante 8 Valvola espansione Expansions...

Страница 69: ...er outlet temperature sensor Sonde temp rature eau en sortie Sonda da temperatura da gua de sa da 19 B2 Sonda temperatura evaporatore Temperatursensor Verdampfer Sonda de temperatura del evaporador Ev...

Страница 70: ...e 1 transducer Transducteur haute pression 1 Transdutor de alta press o 1 34 P2 Trasduttore di alta pressione 2 Hochdrucksender 2 Transductor de alta presi n 2 High pressure 2 transducer Transducteur...

Страница 71: ...nterrupteur automatique compresseur ventilateur pompe Interruptor autom tico do compressor ven tilador bomba TC1 Trasformatore ausiliari Transformator Steuervorrichtungen Transformador auxiliares Auxi...

Страница 72: ...Verbinder Karte Conector de la tarjeta Card connector Connecteur carte Conector da placa X1 7 Morsettiera Klemmenleisten Borneras Terminal blocks Bo tes bornes R guas de terminais UD Uscite digitali...

Страница 73: ...a de sinal on H101 Lampada segnalazione allarme Leuchtanzeige f r Alarmsignalisierung L mpara indicadora de alarmas Alarm signal lamp Lampe signalisation alarme L mpada de sinal de alarme S100 Interru...

Страница 74: ...7 2 Handling 7 3 Operating space 10 ICE310 360 7 2 Handling A B C 1600 mm 4000 mm 7000 mm A B C D E D E 970 mm 1000 mm 7 3 Operating space 1500 mm m m 0 0 5 1 m m 0 0 5 1 1500 mm...

Страница 75: ...egabile 7 4 Pressure reducer riduttore di pressione 8 Tank Serbatoio 9 Expansion Tank Vaso espansione 10 Safety valve Valvola disicurezza 11 Flexible union Giunto flessibile 12 Pressure switch Pressos...

Страница 76: ...1 2 LP1 2 P1 2 Min Max T ICE310 2x40 141 92 28 21 bar 1 5 3 5 bar STD ON 21 bar OFF 15 bar 0 C 30 C 2 15 C 30 6 barg 400 ICE360 2x60 212 88 MODEL F L A Full Load Ampere A 400V 10 3ph 50Hz Total instal...

Страница 77: ...4 1025 40 35 40 1 57 4200 165 35 100 3 94 3100 122 05 300 11 81 300 11 81 300 11 81 100 3 94 142 5 59 1990 78 45 1 77 2132 83 93 47 5 1 87 N 8 HOLES 20 1405 55 32 47 5 1 87 95 3 74 1310 51 57 95 3 74...

Страница 78: ...glass 6 398H348022 refrigerant filter body 7 398H206228 Filter cartridge 398H206053 tank evaporator 10 27 398H510988 398H510990 pump P15 1 5 barg 12 on request on request P30 3 barg on request on req...

Страница 79: ...fety valve 41 398H378341 differential water pressure switch 43 398H354136 local display A2 on request main diconnector switch QS 398H256289 compressor automatic switch QF1 4 398H256269 fans automatic...

Страница 80: ...7 8 Circuit diagram ICE310 360 16 ICE310 360...

Страница 81: ...C1 NC QF1 QF3 QF9 NC FU10 2A aM FU11 2A aM QF2 QF4 FU11 FU10 NC NC KM1 KM3 NC NC FU2 FU1 KM7 KM2 KM4 KM5 KM6 KM8 KM1 KM3 OPTIONAL NC NC NC NC FU3 5A T FU4 5A T FU5 5A T FU6 5A T KM7 X1 X3 X5 X4 X2 X6...

Страница 82: ...M 3 MOTORE COMPRESSORE 1 COMPRESSOR MOTOR 1 PE W U M1 MC1 V M1 M2 M 3 MOTORE COMPRESSORE 3 COMPRESSOR MOTOR 3 PE W U M3 MC3 V M1 M2 M 3 MOTORE COMPRESSORE 2 COMPRESSOR MOTOR 2 PE W U M2 MC2 V M1 M2 M...

Страница 83: ...NTIFREEZE HEATHER 1 RA1 OPTIONAL OPZIONE OPTIONAL OPZIONE R11 S11 R12 S12 4 1D GND M 3 MOTORE VENTILATORE 3 FAN MOTOR 3 PE W U M7 EV3 V TK1 TK2 1 5mm2 14 02 06 6 3C 01 01 6 3C 02 6 4C 05 05 6 4C 06 W5...

Страница 84: ...3 4 7D KM2 X1 0 X1 03 14 13 4 4D KM1 2 1 YV1 REFRIGERANT SOLENOID VALVE 1 ELETTROVALVOLA REFRIGERANTE 1 4 18 17 03 04 0 Vs1 24V 150VA Vs2 230V 50VA Vs3 0 24V 50VA P 250VA 3 2 5 mm2 R S 5 1D 0 5 1D 4 4...

Страница 85: ...7B RT3 A2 A1 RELE TERMICA COMPRESSORE 2 COMPRESSOR 2 OVERLOAD RELAY KA20 A2 A1 RELE TERMICA COMPRESSORE 2 COMPRESSOR 2 OVERLOAD RELAY KA30 X1 4 X1 4 X1 31 X1 29 A2 A1 PHASE MONITOR RELAY RELE MONITOR...

Страница 86: ...V 4 7 1D 0 A2 A1 HIGH PRESSURE 2 RELAY RELE ALLARME ALTA PRESSIONE 2 KA10 J1 J12 J13 pCO5 8 1D 20 8 1D 19 12 11 7 1B 14 7 1B 12 11 8 1B 14 8 1B X3 10 Not Used Non Utilizzato Not Used Non Utilizzato No...

Страница 87: ...4 Not Used Non Utilizzato Not Used Non Utilizzato OPTIONAL OPZIONE OPTIONAL OPZIONE 1 2 4 4B 3 4 4 4B 5 6 4 4B A2 A1 PUMP CONTACTOR CONTATTORE POMPA KM9 GENERAL ALARM ALLARME GENERALE UNIT STATUS RELA...

Страница 88: ...ITOR RELAY RELE MONITORE DI FASE KA4 22 24 21 5 7D PHASE MONITOR RELAY RELE MONITORE DI FASE KA4 WATER LEVEL SENSOR SENSORE DI LIVELLO ACQUA L1 X3 20 X3 24 X2 21 X2 20 X2 22 X2 20 D REMOTE ON OFF ON O...

Страница 89: ...ELAY RELE ALLARME ALTA PRESSIONE 2 KA10 32 34 31 5 7D PHASE MONITOR RELAY RELE MONITORE DI FASE KA4 X4 20 8 8D G 20 20 8 8D G0 19 19 IDC9 J7 A1 DIGITAL INPUTS ID13H J8 A1 ID14 J8 A1 ID14H J8 A1 J8 A1...

Страница 90: ...ato TRASMETTITORE ALTA PRESSIONE 2 HIGH PRESSURE 2 TRANSMITTER TRASMETTITORE ALTA PRESSIONE 1 HIGH PRESSURE 1 TRANSMITTER U1 J2 A1 U2 J2 A1 U3 J2 A1 GND J2 A1 VDC J2 A1 A1 U4 J3 A1 U5 J3 A1 GND J3 A1...

Страница 91: ...7 9 Wiring diagram ICE310 360 27 ICE310 360 Sheet 11 of 12...

Страница 92: ...4 04 YV2 10 10 10 HP1 0 0 0 0 0 0 0 0 0 A FREEZE OPT 0 0 0 4 4 4 HP2 13 13 13 M5 EV1 TK1 40 40 40 HP2 14 14 14 M5 EV1 TK2 051 051 051 A FREEZE OPT 28 28 28 RT1 M1 20 20 20 LP2 4 4 4 RT1 M2 19 19 19 20...

Страница 93: ......