Duplex Fuel Filter & Separator
7(23)
DUAL FBO
73309 031912
Operation and Maintenance Instructions
©
Parker Hannifin
Racor Division
Risk of fire. Smoking, naked flames, or sparks near of the system cause a
risk of fire.
Always have a fire extinguisher at hand and keep it properly serviced.
In case of fire:
•
Put out the fire with a fire extinguisher.
•
Prevent the fire from spreading.
•
Call for help.
Always aim to protect the environment. Observe the local environment
laws when disposing of filters, hoses, fuel, oils, or other waste material.
All detected leaks shall be remedied without delay.
4. TECHNICAL SPECIFICATIONS
Operating pressure:
Max 7 bar (102 psi)
By-pass valve’s opening pressure
No by-pass
Operating temperature (min-max):
0 – 60
°
C (32-140°F)
Material:
EN-GJS-400-15 / S355J0 / CR03 for all pressurized
components
Weight:
40 kg (90#)
Volume:
20 liters (5.3 gal)
Dimensions (WxHxD):
550 mm, 690 mm, 225 mm (22”, 27”, 9.0”)
Filtering element:
5-10-25
μ
m filter / separator