28
AC30 Profibus DP-V1 Option
0050 Comms Module Serial
Range
Type
DWORD
0x00000000
…
0xFFFFFFFF
Communications option parameter.
Serial number of the option
communications module.
0051 Comms Diagnostic
Range
Type
USINT
(enumerated)
(0) NONE
(1) HARDWARE MISMATCH – required
communications option does not match that
fitted, or no option fitted but one is required.
(2) INVALID CONFIGURATION – the
configuration of the option is not valid.
(3) MAPPING FAILED – the process data
mapping is not permitted, e.g. adding read-
only parameters to the read process data
mapping.
(4) EXCEPTION – configuration error
(5) UNSUPPORTED OPTION – the fitted
option is not currently supported
Communications option parameter.
Indicates the state of the
communications option fitted.
0052 Comms Diagnostic Code
Range
Type
DWORD
0x00000000
…
0xFFFFFFFF
Communications option parameter.
Diagnostic code associated with the
Diagnostic parameter.
www.comoso.com