AC30 Profibus DP-V1 Option
Cable Specification
PROFIBUS DP-V1 cable uses a specific colour code (red/green). You
should maintain this colour code throughout your network. The cable
has a single twisted pair with overall shielding.
The bus line is specified in IEC 61158 and it can be used in
accordance with the table below.
Cable Parameters
PROFIBUS line
Surge impedance in
Ω
135 … 165
Capacitance per unit length (pF/m)
< 30
Loop resistance (
Ω
/km)
110
Core diameter (mm)
0.64
Core cross-section (mm
2
)
> 0.34
Note:
Belden B3079E cable meets the above specification.
PROFIBUS DP-V1 Connectors
You should use connectors recommended by Profibus. These
connectors will have a shield clamp providing shield continuity and will
help to ensure good noise immunity of your network.
We recommend the use of the horizontal Erbic range of PROFIBUS-
DP connectors from ERNI:
♦
ERNI Part number 103648, grey - used on all
nodes in the middle of the network
♦
ERNI Part number 103649, yellow - termination
connector
♦
ERNI Part number 134728, grey - includes
switchable termination
For further information, visit
www.erni.com
www.comoso.com