VAC-SIF-05

Training & Maintenance Manual

CVX0260B

Parker Hannifin Corporation

Pneumatic Division

Richland, Michigan

www.parker.com/pneumatic

Operation Mode

MODES

VACUUM ON

VACUUM OFF

BlOw-OFF

EOS*

Normal Conditions

Air Economizing between 

18-15.5 inHg

Idle

Blow-off On 

Blow-off Idle

EOS Off

Emergency 
or Power Failure 
Loss of DeviceNet™ 
Communications or Power

Vacuum On 

↓ 
↓ 

Vacuum On

Idle

Blow-off 

On    Idle 

   

Idle    Idle

EOS On

Restore Power

Vacuum On 

Air Economizing 

Function Resumes

Idle

Idle

EOS Off

* EOS = Emergency Operating System

  OUT 1 AIR ECONOMIZING 

OUT 2 PART PRESENCE

 N.C. Below n_1, N.O. Above n_1  N.O. Below P_3, N.C. Above P_3
  n_1, Switch Point -18 inHg 

P_3, Switch Point -10 inHg

  n_2, Hysteresis -15.5 inHg 

P_4, Hysteresis -9.0 inHg 

 

Hysteresis Mode 

Hysteresis Mode

 

Units of Measure; inHg

Basic Modes of Operation

The Arrows show what happens during each mode if there is 
an Emergency Stop Condition or Power Failure.

Normal Conditions:

Input Power and Output power are available. Vacuum 
can be ON in Air Economizing mode or be idle. 
Blow-off can be On or Idle.

Emergency Operating System is OFF:

The Emergency Operating System is off because the 
emergency stop valve is energized because Output 
Power is present.

Emergency Stop or Power Failure:

If Vacuum is being created, the unit will continue to 
create vacuum because the emergency operating 
system turns ON. Air Economizing mode, will be 
overridden, and maximum vacuum that the system 
can obtain will be created by the vacuum generator. 
If the Vacuum is IDLE, it will remain in the IDLE State. 
Blow-off will be turned to the IDLE state.

Restore Power: 

When the output power is restored with input and 
output power, the unit will return to the output status 
of the PLC/PC program.

Factory Sensor Settings 

All factory settings can be changed in the field. Instructions 
on Sensor Functions and Programming can be found in the 
CVX installation manual or the MPS-23 Sensor Instruction 
Sheet.
With 24VDC applied to the sensor power, GREEN LED 1 on 
the sensor should be illuminated indicating a N.C. Sensor 
and RED LED 2 should not be illuminated indicating a N.O. 
Sensor.

Operation

AIR ECONOMIZING SwITCH POINT IS FACTORY SET AT 
18 inHg. All SYSTEM DESIGN PARAMETERS MUST BE 
ANAlYZED BEFORE CHANGING “n_1”. 

Air Economizing 

function will be turned off by setting “n_1” above the 
maximum vacuum pressure that the system can create.
It may be necessary to adjust the part presence switch point 
“P_3” to avoid false signals when vacuum is falsely created 
by tubing or fitting flow restrictions in an open system. 
Press the mode key one (1) time and “n_1” and “-18.0” will 
alternate on the display. Bypass “n_1” by pressing the mode 
key. By pass "n_2" by pressing the mode key.  “P_3” and “10” 
will alternate on the display. Press the arrow up key to adjust 
the switch point above the vacuum level measured with the 
system open. To enter and store this change, press the mode 
key 2 times. 
Output 2 part presence signal is in a non-passing state 
above P_3.

kPa

MODE

Switch (OUT 1)

(Green LED)

Switch (OUT 2)

Setting Button
Change setting mode and
pre-set final desired value

3-1/2 digit LED display
Display the measured
pressure value, each set
content and error code.

(Red LED)

(

) Button

Use the 

 button to

change setting mode

and pre-set desired value. 

(

) Button

Use the 

 button to

change setting mode

and pre-set desired value. 

(Revised 07-23-13)

Содержание CVX0260B

Страница 1: ...Pneumatic Division Richland Michigan 49083 Training Maintenance Manual for CVX0260B Vacuum Generators VAC SIF 05 Training Maintenance Manual CVX0260B ISSUED July 2013 Supersedes November 2012...

Страница 2: ...pilot valve blow off needle control valve pressure sensor vacuum check valve vacuum filter and exhaust filter Each Vacuum Generator is mounted to a 2 Station bar manifold with an optional electrical...

Страница 3: ...level within the system The vacuum operated pilot valve is turned back on at a vacuum level n_2 The hysteresis feature of the vacuum sensor can maintain the vacuum level of the system indefinitely wh...

Страница 4: ...tput 1 to Activate Vacuum VAC ON Vacuum Begins Vacuum Mode Continues Part Presence Command VAC ON Sensor Output 1 N C Preset n_1 18 inHg Sensor Output 2 N O Preset P_3 10 inHg n_1 n_2 P_3 P_4 Robot Co...

Страница 5: ...e IDLE state Restore Power When the output power is restored with input and output power the unit will return to the output status of the PLC PC program Factory Sensor Settings All factory settings ca...

Страница 6: ...Individual Vacuum Channels 3 8 G Ports or 3 8 NPT OperatingTemperature 32 to 122 F 0 to 50 C Operating Pressure 70 PSI Vacuum Filtration 130 m Noise Level 72dB Air Consumption 10 41 SCFM Maximum Vacuu...

Страница 7: ...Not Shown 14 PSCVXDNB DeviceNet PSCVXD3B M12 Discrete PSCVXN3B 18 Pin Discrete 15 MPS V23C NC NPN Sensor PSCVXDNB PSCVXD3B PSCVXN3B Contents The CVX0260B is supplied with four 4 M5 x 1 Socket Head Cap...

Страница 8: ...ach CVX0260B incorporates a small filter housed on the body to protect the internal components of the generator Additional maintenance of this filter will also vary with each environment and applicati...

Страница 9: ...PC Program Sensor Output 1 ou1 to N O Manually changing sensor OU1 from N C to N O LED should change state See Sensor Verify Sensor Output 1 settings Programming for changing Output status Verify tha...

Страница 10: ...cuum confirmation High Signal to the PLC PC at set point P_3 prior to part on Log Part On and Part Off Vacuum Check Exhaust and Vacuum Filters for Pressure P_3 must be between Part Off obstructions to...

Страница 11: ...ify H 1 is illuminated at 0 inhg ou1 N C N O no signal will be passed through the Air Economizing Setting Sensor Output 1 must be set to sensor to activate the vacuum pilot from the Normally Closed Pa...

Страница 12: ...p Vacuum CVX0260BE0SDN Dimensions 2 56 65 0 3 51 89 2 4 31 109 5 1 76 44 6 2 24 57 0 1 97 50 0 Blow Off Valve Mounting Holes 4 5 5mm Blow Off Needle Adjustment Vacuum Valve Vacuum Filter Housing 67 17...

Страница 13: ...try and the two sensors The auxiliary power bus pro vides power for the vacuum solenoids and blow off solenoids No external PLC programming is required for Air Economizing Functions because this funct...

Страница 14: ...Bit Strobed and Polled messaging General Description The Convum Vacuum Generator operates as a Group II Only slave on the DeviceNet network The unit supports the following types of messaging Explicit...

Страница 15: ...as the Poll response Sensor 1 Dip Switches VAC1 BL01 BL02 VAC1 Sensor 2 1 2 3 4 5 6 7 8 Sensor 1 VAC2 BL02 BL01 VAC1 Sensor 2 O N 1 2 3 4 5 6 7 8 O N Network Status Module Status Factory DIP Switch Se...

Страница 16: ...XN3B M18 24VDC Optional Mounting Plate 13 00 330 2 3 50 101 6 12 18 309 4 2 00 50 8 50 12 7 1 00 25 4 28 7 13 Dia Thru Typ 4 Places 27 6 85 Typ 4 Places 438 11 13 Dia Typ 4 Places 2 56 65 0 3 51 89 2...

Страница 17: ...put Power R Not Used S Not Used T Not Used U Not Used 24VDC J K M N B H S R D E G F L A T U P C Face View Male 18 Pin Connector Notes Pin B F are jumpered inside unit Either pin can connect power to b...

Страница 18: ...red by paint etc If masking is not possible contact your local representative for replacement labels WARNING FAILURE OR IMPROPER SELECTION OR IMPROPER USE OF THE PRODUCTS AND OR SYSTEMS DESCRIBED HERE...

Страница 19: ...tore Final Key returns sensor to current pressure reading 2 1 Troubleshooting Verify ou1 is set NC LED 1 will be ON if NC Check DIN LED for electrical connection Use Manual Overrides to confirm manual...

Страница 20: ...change to store Press Up or to change to store Final Key returns sensor to current pressure reading 2 1 Troubleshooting Verify ou1 is set NC LED 1 will be ON if NC Check DIN LED for electrical connect...

Страница 21: ...x 1x 1x Press button for more than 3 seconds NO Mode 2 5ms Lock Mode Measure mode Key lock mode can prevent operation mistakes Press button for less than 5 seconds Key lock unlock mode Use the or butt...

Страница 22: ...and then restart If error condition remains please return to factory for inspection Er6 Internal system error Er7 Internal data error Output type Manual setting mode Auto setting mode Do not use on C...

Страница 23: ...y any customer Buyer shall be governed by all of the following Terms and Conditions Buyer s order for any item described in its document when communicated to Seller verbally or in writing shall consti...

Страница 24: ...21 4PDN Option 2 E mail pdnapps parker com Customer Support Phone 877 321 4PDN Option 1 E mail pdncustsvc parker com Web site www parker com pneumatics Parker Hannifin Corporation Pneumatic Division 8...

Отзывы: