Page 16 - 30
24.
Use P clip to retain cables from the power modules to the control module.
Plug in the cable from the CS module into
the control module connector marked
CS.
Plug in the cable from the top CD module
into the control module connector marked
W.
Plug in the cable from the middle CD
module into the control module connector
marked
V.
Plug in the cable from the bottom CD
module into the control module connector
marked
U.
Plug in the small earth wire into the control module faston. Secure cables together with small
tyrap.
25.
Fit small blanking plate LA501357U001 (item 298) with bolts FB376R25 fitted with M8
washers FC12301R (torque setting 4.5Nm) (item 652).
If CP module is not fitted, fit medium size blanking plate BA501301U002 with bolts FB376R25
quantity 2 (item 651) fitted with M8 washer per bolt FC12301R (torque setting 4.5Nm) (item
652).
BA501301U002
LA501357U001