![Parker AC650V Series Скачать руководство пользователя страница 65](http://html1.mh-extra.com/html/parker/ac650v-series/ac650v-series_product-manual_3771557065.webp)
9-6
Technical Specifications
650V AC Drive
Digital Inputs
Operating Range
DIN1, DIN2, DIN3, DIN4, DIN5:
0-5V dc = OFF, 15-24V dc = ON
(absolute maximum input voltage ±30V dc)
IEC1131
DIN6, DIN7:
0-1.5V dc = OFF, 4-24V dc = ON
(absolute maximum input voltage ±30V dc)
IEC1131
undefined state
15V
5V
0V
24V
ON
OFF
undefined state
4V
1.5V
0V
24V
ON
OFF
Input Current
7.5mA @ 24V
Sample Interval
10ms
Digital Outputs
DOUT1 and DOUT2
Nominal Open
Circuit Output
Voltage
23V (minimum 19V)
Nominal Output
Impedance
47
Rated Output Current 50mA
(either individually or as the sum of outs from terminals 6, 10 & 11)
Cabling Requirements for EMC Compliance
Power Supply Cable
Motor Cable
Brake Resistor Cable Signal/Control Cable
Cable Type
(for EMC Compliance)
Unscreened
Screened/armoured
Screened/armoured
Screened
Segregation
From all other wiring
(clean)
From all other wiring (noisy)
From all other wiring
(sensitive)
Length Limitations
With Internal AC Supply
EMC Filter
Unlimited
*25 metres
25 metres
25 metres
Length Limitations
Without Internal AC
Supply EMC Filter
Unlimited
25 metres
25 metres
25 metres
Screen to Earth
Connection
Both ends
Both ends
Drive end only
Output Choke
300 metres
maximum
* Maximum motor cable length under any circumstances
Содержание AC650V Series
Страница 9: ...Contents Contents Page Cont 8...