4
Fan Control Application Manual
AC30V series Variable Speed Drive
Inputs
Terminal
Function
Comment
ANIN 01 (X11/01)
SPEED SETPOINT
Speed Reference used when MANUAL RUN
ANIN 02 (X11/02)
Not used
DIGIN 01 (X13/02)
MANUAL RUN*
Run command for using the Analog Input as Setpoint
DIGIN 02 (X13/03)
AUTO RUN*
Run command for using the selected Preset Speed as Setpoint
DIGIN 03 (X13/04)
PRESET SELECT 1
These 3 digital input select the active Preset Speed if the Time Of Day Timer
feature is not being used
DIGIN 04 (X12/01)
PRESET SELECT 2
DIGIN 05 (X12/02)
PRESET SELECT 3
DIGIN 06 (X12/03)
NOT COAST STOP
When FALSE the Drive does not control Fan. The Fan will freewheel.
DIGIN 07 (X12/04)
NOT FIRE MODE
When FALSE activates Fire Mode
* If both Run inputs are TRUE, than MANUAL RUN has the highest priority.