Fan Control Application Manual
13
AC30V series Variable Speed Drive
ID Trip Name
Disabled in Partial mode Disabled in Full mode Drive Protection
1 OVER VOLTAGE
2 UNDER VOLTAGE
(1)
Note 1
Note 1
3 OVER CURRENT
4 STACK FAULT
5 STACK OVER CURRENT
6 CURRENT LIMIT
7 MOTOR STALL
8 INVERSE TIME
9 MOTOR I2T
10 LOW SPEED I
11 HEATSINK OVERTEMP
12 AMBIENT OVERTEMP
13 MOTOR OVERTEMP
14 EXTERNAL TRIP
15 BRAKE SHORT CCT
16 BRAKE RESISTOR
17 BRAKE SWITCH
18 LOCAL CONTROL
19 COMMS BREAK
20 LINE CONTACTOR
21 PHASE FAIL
22 VDC RIPPLE
23 BASE MODBUS BREAK
24 24V OVERLOAD
25 PMAC SPEED ERROR
26 OVERSPEED
27 SAFE TORQUE OFF
Note 1. The Under Voltage trip is enabled when Fire Mode is active, but the trip level is reduced by 50%.
If a trip source becomes active when the associated trip is disabled the drive will continue to run. This is also the normal behavior of the drive,
(when Fire Mode is not active). If the associated trip is designed for drive protection, this will be recorded in non-volatile memory. The recorded
values are available to view in the Drives’ Trips History.
When Fire Mode is activated and a trip source becomes active and the associated trip is enabled, the Drive will trip, causing the motor to stop.
This is similar to the normal behavior of the Drive, (when Fire Mode is not active). However, when Fire Mode is active the firmware within the
Drive continues to monitor the trip source, once the trip source has become inactive the drive automatically resets the trip condition and restarts
the drive.