background image

Refrigerating Specialties Division

3

OPTIONS

Ranges
Available in Ranges A, V and D. Honeywell motor has 160

o

 cam

rotation which is equivalent to a change in set-point of 60 psi
(4.1 bar) for Ranges A or V, or 106 psi (7.3 bar) for Range D;
Penn motor has 240

cam rotation which changes set-point 90

psi (6.2 bar) for Ranges A or V, or 159 psi (10.9 bar) for Range
D.

Motors
Model:  M9181A-1012 Honeywell Inc.
Features:  Reversing, proportional motors used to operate
valves or dampers in electric modulating circuits. Oil immersed
motor and gear train for reliable performance and long life.
Wiring box provides NEMA 3 weather protection. Actuator
motor and circuitry operate from 24 volts AC.  Fixed stroke,
160

o . 

No auxiliary switches. The controller type is a 135 ohm

Honeywell Series 90 proportional controller (See Fig. 10).

Model:  M7284A-1020 Honeywell Inc.
Features: Electronic Modutrol motors used to control dampers
and valves. This motor accepts a current signal from an
electronic controller to position a damper of valve at any point
between open and closed. Oil immersed motor and gear train
for reliable performance and long life.  Wiring box provides
NEMA 3 weather protection. Actuator  motor and circuitry
operate from 24 volts AC.  Fixed stroke, 160

o

 . No auxiliary

switches. This motor is used with controllers that provide a
stable, noise-free proportional output of 4-20mA nominal,
25mA maximum (See Fig. 13).

Model:  M6281A-1009 Honeywell Inc.
Features:  Floating control motor with an internal electrically
isolated feedback potentiometer. This motor is used with
controllers that provide SPDT or floating output to operate
dampers or  valves. The feedback potentiometer provides an
indication of the motors shaft position and can be used for
slaving Series 90 motors or rebalancing an external control
circuit. Wiring box provides NEMA 3 weather protection. Actua-
tor  motor and circuitry operate from 24 volts AC. Fixed stroke,
160

o

. No auxiliary switches (See Fig. 12).

Model: M6191B-1006 Honeywell Inc.
Features: Non-spring return, 3-wire floating control motor. This
motor is used with controllers that provide a switched or floating
SPDT output to operate dampers or valves. Actuator  motor
and circuitry operate from 24 volts AC. Fixed stroke, 160

o

 . One

(1), auxiliary switches (See Fig. 14).

Model:  M150-JGA-1 Penn Johnson
Features:  The M100J motor actuators are used to position
valves and dampers in heating ventilating, air conditioning,
refrigeration and industrial applications. The motor accepts a
Johnson Controls 0 to -2 VDC electronic controller input, or a
0 to +24 VDC input, or a 3-wire 135 to 1000 ohm potentiometer
input (See Fig. 11).

Fig 2. A4AOM

Содержание A2BM-DN

Страница 1: ...psi 0 14 bar pressure drop to fully open These valves are generally ordered with a close coupled upstream strainer to prevent the entrance of foreign material into the valve and the rest of the system...

Страница 2: ...s reached Turning the adjusting screw in will lower the pressure turning it out will raise the pressure If after several hours of operation the tempera ture is not as desired readjust the pressure adj...

Страница 3: ...24 volts AC Fixed stroke 160o No auxiliary switches This motor is used with controllers that provide a stable noise free proportional output of 4 20mA nominal 25mA maximum See Fig 13 Model M6281A 100...

Страница 4: ...is controlling at the lower of two set points This would be the electrically compensated low pres sure pilot doing the controlling When the pilot solenoid is de energized the regulator is controlling...

Страница 5: ...losing 35 Dirt Wiper Retainer 36 Dirt Wiper 37 Seal Bottom Cap 38 Bottom Cap 39 Screw Bottom Cap 40 Packing Washer 41 Packing Ring 42 Stuffing Box Nut 43 Gasket Seal Cap 44 Seal Cap 45 Gasket Flange 4...

Страница 6: ...ntal line in a vertical position with the manual opening stem on bottom Where other positions are desired the factory should be consulted please give applica tion and piping details To function proper...

Страница 7: ...1 Screw Body 32 Body 33 Throttling Plug Asm 34 Spring Closing 35 Dirt Wiper Retainer 36 Dirt Wiper 37 Seal Bottom Cap 38 Bottom Cap 39 Screw Bottom Cap 40 Packing Washer 41 Packing Ring 42 Stuffing Bo...

Страница 8: ...iaphragm Follow er 16 Gasket Bonnet 17 Diaphragm 18 Seat Pilot 19 Gasket Adapter 20 Valve Body 21 Plug 76 Motor 77 Cam Lock Screw 78 Motor Cam 79 Motor Mounting Screw 80 Cam Follow er Asm 81 Lock Nut...

Страница 9: ...nship and materials for a period of one 1 year from date of shipment from originating factory This warranty is in force only when products are properly installed field assembled maintained and operate...

Страница 10: ...14 1 1 5 8 239 9 4 N ODS TUBE 7 8 19 0 8 1 3 8 25 1 0 1 5 8 28 1 1 2 5 8 38 1 5 3 1 8 43 1 7 4 1 8 55 2 2 ENGAGE 1 1 8 23 0 9 1 5 8 28 1 1 2 1 8 33 1 3 3 1 8 43 1 7 3 5 8 48 1 9 MENT 1 3 8 25 1 0 2 1...

Страница 11: ...Refrigerating Specialties Division 11 Fig 12 M6281A 1009 Fig 11 Penn M150 JGA Fig 13 M7284A 1020 Fig 10 M9181A 1012...

Страница 12: ...40 3 COVER BOTTOM A4A S4A 1 5 8 to 2 1 2 DUCTILE IRON GGG 40 3 BONNET A4W DUCTILE IRON GGG 40 3 COMPONENT DESCRIPTION MATERIAL Kv VOLUME BODY 2 A4A DN DUCTILE IRON GGG 40 3 42 4 1 61 L ADAPTER 2 A4A D...

Отзывы: