4.4 

Isolation valve locking option

The user can easily choose between the two-position (valve open or valve closed) or 
single-position (valve closed) locking system.

• 

Unscrew the screw/washer assembly of the shut-off handle (1+2).

• 

Remove the shut-off handle (3).

• 

Position the upper locking plate (4) in the desired position (refer to the marking 
on the plate):

• 

No visible marking: Locking only possible in closed valve position

• 

Visible “S” marking: Locking possible in both positions

• 

Reassemble the parts in the opposite direction, making sure that the screw/
washer assembly holding the isolation handle is tight.

This operation can be carried out after the block has been installed in the circuit, 
preferably when there is no pressure in the circuit.

5 Maintenance

Maintenance must only be carried out by qualified technicians, with consideration given 
to the explosion risk. Preventive maintenance periodicities for a safe use depend on the 
installation and operating conditions (contact Parker or an approved Parker agent).
It is recommended to check at regular intervals:

• 

The general condition of the safety block

• 

Cleanliness

• 

Any leaks in the connections or in the  
various components

Also refer to local regulations.

5.1 

Other operations

You are advised to carry out regularly the following checks:

• 

Check the safety devices and connections

• 

Check the safety block mountings

• 

Visually inspect the safety block for any sign of wear and tear such as deforma-
tion or corrosion 

• 

If you are using an abrasive or corrosive fluid, check the inside of the safety 
block. 

• 

Check earthing (continuity)

• 

Visually inspect the rubber sealing parts

Preventive maintenance periodicities for a safe use depend on the installation and 
operating conditions.
Contact Parker or an approved Parker agent
To maintain a safety block when it is in service (regular re-qualification operations, etc.), 
refer to the current site regulations. 
For disassembly, cleaning and reassembly operations contact Parker or an approved 
Parker agent. 
Use only original spare parts. 

5.2 

Regulations and Directives

Pressure Equipment Directive PED 2014/68/EU
The SB blocks meet the essential safety requirements concerning the risk of overpres-
sure in gas loaded accumulators.
REACH Regulation 1907/2006 EU 
Important: this information is subject to change in line with the half-yearly publication 
of the list of candidate substances of very high concern for authorisation on the ECHA 
(European Chemical Agency) website.
All the articles in the SB range comply with REACH regulations. These articles do not 
contain any substance of very high concern (SVHC) in their composition at a concen-
tration higher than 0.1% by weight.
ROHS Directive 2011/65/EU
The optional electrical components of the SB range (electric coils) comply with the 
ROHS Directive.
ATEX Directive2014/34/UE
Manually operated SB blocks do not fall within the scope of the ATEX Directive 
2014/34/EU as they do not have their own ignition sources.
The product is considered a “simple” mechanical product as defined in paragraph §38 
of the ATEX Guidelines 2014/34/EU.

IMPORTANT

 

Electrically operated versions must never be used in an explosive atmosphere. 
Where potentially flammable atmospheres exist, it is imperative that the user 
take into account the risk of electrostatic ignition.
6 Recycling

Before destroying or recycling a safety block, relieve it of any residual pressure. Decon-
taminate it if necessary and separate the metal parts from the electrical parts if they are 
present (electric coils).
 For each type of component (mechanical or electrical), refer to the applicable rules for 
each country.

1

Sechskantschraube

2

Unterlegscheibe

3

Griff

4

Äußere Absperrplatte*

5

Unterlegscheibe*

6

Innere Absperrplatte*

7

Nutstift

8

Antriebsspindel

General Information

This equipment is designed, manufactured and tested in accordance with the ap-
plicable European Regulations and Directives and complies with the relevant safety 
provisions of EN ISO 4413. 
It is imperative to strictly follow the instructions in this manual and in the specific 
manuals when they exist and are relevant. The supplier accepts no liability for direct or 
indirect material or human damage resulting from failure to comply with the following 
instructions, nor for the consequences such as, for example, operating losses, etc. Be-
fore commissioning and during operation, the operator must take into account and is 
fully responsible for compliance with the regulations in force at the place of installation 
concerning gas loaded accumulators and must carefully keep the documents supplied 
with the device throughout its operating life. They may be required during inspections.

Handling and Storing

 

The original packaging is suitable for handling and storage, unless otherwise specified. 
The device must not be subjected to even slight shocks. 
Store in a cool, dry place. Do not expose to flame or heat. 
The storage period should not exceed 5 years. 
All openings must remain sealed during storage to protect the unit from pollution and 
internal corrosion.

Block Labelling and Marking

The information and markings may not be changed without the prior written consent 
of Parker.
The following information is shown on the block:

• 

Parker logo.

• 

Company name and manufacturing site.

• 

Product reference.

• 

Date of manufacture (week/year).

• 

Permissible temperature range TS in [°C].

• 

Maximum allowable pressure PS in [bar].

• 

Serial number.

• 

Hydraulic diagram.

4 Commissioning

Before installing and operating the safety and isolation unit, the instructions and safety 
information in this manual must be read carefully. 

Commissioning should only be carried out by qualified technicians (contact 
Parker or its authorised network). Before installation, visually inspect the unit 
for damage.  
Before working on the hydraulic systems, make sure that there is no pressure. 
Improper installation can lead to serious accidents, pressure fluid leakage 
and/or bursting.

It is strictly forbidden to:

• 

weld, sol, drill or any other operation on the block that may alter its mechanical 
properties 

• 

The accumulator must be connected to port A of the block with the appropriate 
fitting.

• 

The hydraulic pressure source must be connected to port P of the block.

• 

The connection between the block and the tank is made through port T.

• 

Check that the voltage of the electrical control signal matches the coil on the 
bleed valve (optional).

4.1 

Preparing for commissioning

Checking the operating limits:
The pressure in the hydraulic system must not exceed the PS of the block.

• 

The operating temperature range of the system and the environment must not 
exceed the TS of the block.

• 

The set pressure of the pressure relief valve must be less than or equal to the 
PS of the accumulator.

• 

The block is designed for use with mineral oil type fluid, for use with other fluid 
consult PARKER.

• 

The block is not designed for use with a group 1 fluid as defined in the Pressure 
Equipment Directive PED 2014/68/EU.

• 

It is the responsibility of the circuit designer to provide the necessary elements 
to avoid overpressure, overflow in the tank (valve on the return line, sufficient 
vent on the tank, etc.), particularly in the event of accidental rupture of the ac-
cumulator separator (bladder, diaphragm, piston).

4.2 

Documentary inspection

The following documents are provided with each safety block:

• 

Operating instructions

• 

Pressure relief valve calibration certificate

• 

Pressure relief valve operating instructions

Any other certificates must be specially requested before ordering.

4.3 Installation

• 

Before connecting the safety and isolation unit, it is essential to check that the 
connections are suitable for the circuit and the accumulator.

• 

The accumulator must be connected to port A of the block with the appropriate 
fitting.

• 

The hydraulic pressure source must be connected to port P of the block.

• 

The connection between the block and the tank is made through port T.

• 

Check that the voltage of the electrical control signal matches the coil on the 
bleed valve (optional).

5

Parker Hannifin

Cylinder and Accumulator Division Europe

user manual / manuel d’utilisation / Benutzerhandbuch

SB Safety Block / Bloc Série SB / Sicherheitsblock  SB Serie

Содержание A04B2PY CE Series

Страница 1: ...SB Safety Block Bloc de d compression et d isolement S rie SB Sicherheitsblock f r Druckspeicher SB Serie USER MANUAL MANUEL D UTILISATION BENUTZERHANDBUCH...

Страница 2: ...e maintenance de s curit et d avertissement de l application sont satisfaites L utilisateur doit analyser tous les aspects de l application respecter les normes industrielles applicables et suivre les...

Страница 3: ...d compression manuelle 6 Une fois l accumulateur isol la vanne de vidange permet de d charger l accumulateur connect orifice A vers l orifice T Man uvrer le volant 6 dans le sens anti horaire pour pur...

Страница 4: ...re Absperrplatte 5 Unterlegscheibe 6 Innere Absperrplatte 7 Nutstift 8 Antriebsspindel 1 Vis 2 Rondelle 3 Poign e 4 Plaque de verrouillage superieure 5 Rondelle 6 Plaque de verrouillage inferieure 7 G...

Страница 5: ...cific manuals when they exist and are relevant The supplier accepts no liability for direct or indirect material or human damage resulting from failure to comply with the following instructions nor fo...

Страница 6: ...trique correspond celle de la bobine de la vanne de d compression en option La connexion entre le bloc et le r servoir se fait par l orifice T 4 4 Option de verrouillage de la vanne d isolement L util...

Страница 7: ...ck angeschlossen werden Die hydraulische Druckquelle muss an den Anschluss P des Blocks angeschlos sen werden Die Verbindung zwischen dem Block und dem Tank wird ber den Anschluss T hergestellt berpr...

Страница 8: ...STGRENZE 100KG T port must not be blocked and must have contained discharge to tank L orifice T ne doit pas tre bloqu et doit avoir une d charge contenue dans le r servoir Der T Anschluss darf nicht b...

Страница 9: ...valve replaceable one piece encapsulated coils with minimal amperage draw sperical poppet for low leakage nylon inserted jam nut provides secure holding in high vibration applications all external par...

Страница 10: ...me la norme DIN 43650 AC ou DC fourni sans connecteur DIN Universeller 50 60 Hz Betrieb Wasserdichte Spule hermetisch versiegelt erfordert keine O Ringe oder wasserdichte Kits Externes Flussmittelband...

Страница 11: ...ere Informationen finden Sie im SB Katalog LINK to valve PED and ATEX document VIEW SB RANGE ON PARKER COM link to catalogues on parker com 11 Parker Hannifin Cylinder and Accumulator Division Europe...

Страница 12: ...0 1 466 6370 IL Israel Tel 39 02 45 19 21 IT Italy Corsico MI Tel 39 02 45 19 21 KZ Kazakhstan Almaty Tel 7 7273 561 000 NO Norway Asker Tel 47 66 75 34 00 PL Poland Warsaw Tel 48 0 22 573 24 00 PT P...

Отзывы: