Risk Assessment
Under fault conditions, power loss or other operating conditions not intended, the
equipment may not operate as specified. In particular:
•
The motor speed may not be controlled
•
The direction of rotation of the motor may not be controlled
•
The motor may be energised
Accessibility
All live power terminals are IP20 rated only, since the equipment is intended to be
installed within a normally-closed cubicle or enclosure, which itself requires a tool to
open.
Protective Insulation
•
All control and signal terminals are SELV, i.e. protected by double insulation.
Ensure all wiring is rated for the highest system voltage.
NOTE
Thermal sensors contained within the motor must be single/basic insulated.
•
All exposed metalwork in the Drive is protected by basic insulation and bonding to
a safety earth.
RCDs
Not recommended for use with this product. Where their use is mandatory, use only
Type B RCDs (EN61009).
Caution
This is a product of the restricted sales distribution class according to IEC 61800-3. It
is designated as “professional equipment” as defined in EN61000-3-2. Permission of
the supply authority shall be obtained before connection to the low voltage supply.