![Parker 8903/IM Скачать руководство пользователя страница 30](http://html1.mh-extra.com/html/parker/8903-im/8903-im_technical-manual_3789078030.webp)
26
8903/IM 8903/IP Ethernet Communications Interfaces
Module Faults: 16#0100 - 16#01ff
Code:
String:
Explanation and Possible Causes/Solutions:
16#0109 Connection Request
Error: Invalid
connection size
Note: Additional Error
Information for this
fault will be displayed
as the tag name
associated with the
connection instance
number that has the
fault.
The controller is attempting to set up a connection with the module and
cannot – the size of the connection is invalid.
The controller may be attempting to connect to a tag in a producing
controller whose size does not match the tag in this controller.
16#0110 Connection Request
Error: Module not
configured
The controller is attempting to set up a Listen Only connection with the
module and cannot – the module has not been configured and
connected to by an Owner (e.g., another Controller).
This controller is not an Owner of this module since it is attempting to
establish a Listen-Only connection, which requires no module
configuration. It cannot connect until an Owner configures and connects
to the module first.
16#0111 Requested Packet
Interval (RPI) out of
range.
The Requested Packet Interval (RPI) specified is invalid for this module or
for a module in the path to this module.§
For Listen-Only connections: the RPI set by the owner of this module is
slower than the one requested. Either increase the requested RPI or
decrease the RPI the owner controller is using. See the Connection tab
for valid RPI values.
16#0113 Connection Request
Error: Module
connection limit
exceeded.
This module (or a module in the path to this module) has exceeded its
connection capacity. Reduce the total number of connections used by this
module.
16#0114 Electronic Keying
Mismatch: Electronic
Keying product code
mismatch.
The Product Code of the actual module hardware does not match the
Product Code of the module created in the software.
Electronic Keying failed for this module. You may have a mismatch
between the module created in the software and the actual module
hardware.
16#0115 Electronic Keying
Mismatch: Electronic
Keying product type
mismatch.
The Product Type of the actual module hardware does not match the
Product Type of the module created in the software.
Electronic Keying failed for this module. You may have a mismatch
between the module created in the software and the actual module
hardware.
16#0116 Electronic Keying
Mismatch: Major
and/or Minor revision
invalid or incorrect
The Major and/or Minor revisions of the module do not match the Major
and/or Minor revisions of the module created in the software.
Ensure that you have specified the correct Major and Minor Revision if
you have chosen Compatible Module or Exact Match keying.
Electronic Keying failed for this module. You may have a mismatch
between the module created in the software and the actual module
hardware.