![Parker 690+ series Скачать руководство пользователя страница 141](http://html.mh-extra.com/html/parker/690-series/690-series_product-manual_755642141.webp)
Programming Your Application
1-133
690+ Series Frequency Inverter
Operation
Description
PROFILE SQRT
PROFILE X^1
PROFILE X^2
PROFILE X^3
PROFILE X^4
Profile
0
20
40
60
80
100
120
-5
45
95
Input A
Output
Sqrt
x
Input 2 (Min)
Input 3 (Max)
1
x
2
x
3
x
4
Example : Profile Min = 10, Max = 110
Profile
-60
-40
-20
0
20
40
60
0
50
100
150
Input A
Output
Sqrt
Input 2 (Min)
Input 3 (Max)
x
4
x
3
x
2
x
1
Example : Profile Min = 50, Max = -50
Profile functions convert an input (0-1) to an output with (min) +((max-min)
* fn(input)) where fn() is Sqrt (square root), Linear (X
1
), X
2
, X
3
or X
4
. The
output is clamped between Min and Max. The input is clamped 0-100.
The profiles are calculated from 100 point tables and linearly interpreted
between the points.
PROFILE SQRT
5
.
0
min)
(max
min
x
y
−
+
=
PROFILE X^1
x
y
min)
(max
min
−
+
=
PROFILE X^2
2
min)
(max
min
x
y
−
+
=
PROFILE X^3
3
min)
(max
min
x
y
−
+
=
PROFILE X^4
4
min)
(max
min
x
y
−
+
=
where INPUT A : Input x
INPUT B : Min
INPUT C : Max