4. Parameters - overview
Parameter
Description
How to set
P2
Maximum Speed in Hz
Default is 50 or 60 depending on region. Set at
for 50Hz motor.
50
P3
Minimum Speed as % of P2
Default is 0. Set to
for most applications.
0
P6
Motor Current in Amps
Set to match motor nameplate - eg. 4.7
P7
Base Frequency in Hz
Default is 50. Change to 60 for 60Hz motor only - otherwise set at
.
50
P13
Fixed Boost (%)
See section 6 for details of how to correctly set this value.
The Inverter contains a number of settings
which can be changed to tailor it for use in a
wide range of applications. These settings are
known as parameters.
Parameters are typically referred to by code or
number (eg. P6 = Motor Full Load Current)
with a description available in the manual.
The parameters contain critical information
essential to the correct operation of the
Inverter. Therefore, they should at least be
checked by the user before it is operated for
the first time.
The parameters listed in section 5 are intended
to provide a starting point to allow for basic
operation of the 650 Inverter.
5. Parameters to set before use
See section 7 to learn how to set a parameter value.
Set the following parameters to allow the 650
to run in standard mode with Run, Stop and
Speed Control from the keypad.
If any of the parameters have been changed
previously, follow the procedure in section 13
to reset the Inverter to Factory Defaults.
5.1 Parameters to check and values to set