Electrical Installation
07-02-12-02-EN-V1215.doc / Type:
638
63
5.4
Fuses , Contactors
●
638A
Servo - Driver
638A01..
638A02..
638A04..
638A06..
Fuse, Contactor
FI – Switch
Not recommended
Maximal Input Supply
Current, 1 phase
[A]
2,8
5,5
8 2)
9,3 1)2)
Maximal Input Supply
Current, 3 phase
[A]
1,7
3,4
5,9
6,7 1)
Fusible cut-out VDE
Type 6..16A gG 6..16A gG 10..16A gG 16A gG
Automatic circuit breaker
VDE
Type B6A..16A
or
C6A..16A
B6A..16A
or
C6A..16A
B10A..16A
or
C10A..16A
B16A
or
C16A
Fusible cut-out UL
3) Type
6A
6A
10A
15A
Line contactor
4) Type
DILM7
DILM7
DILM7
DILM7
DC-Link connection
Fusible cut-out VDE
DC-link resp. AC-supply
5) Type 10A..16A
gRL
10A..16A
gRL
10A..16A
gRL
10A..16A
gRL
●
638B
Servo - Driver
638B03..
638B05..
638B08..
638B10.. 638B15..
Fuse, Contactor
FI – Switch
Not recommended.
Nominal Input Supply
Current, 3 phase
[A]
3,2
5,6
9,0
10,9 6)
11,4 6)
Fusible cut-out VDE
Type 6..16A gG 6..16A gG 10..16A gG 16A gG
16A gG
Automatic circuit breaker
VDE
Type B6A..16A
or
C6A..16A
B6A..16A
or
C6A..16A
B10A..16A
or
C10A..16A
B16A
or
C16A
B16A
or
C16A
Fusible cut-out UL
7) Type
10A
15A
25A
30A
30A
Line contactor
4) Type
DILM7
DILM7
DILM12
DILM15
DILM15
DC-Link connection
Fusible cut-out VDE
DC-link resp. AC-supply
5) Type 10A..30A
gRL
10A..30A
gRL
10A..30A
gRL
16..30A
gRL
16A..30A
gRL
1)
The continues output power is on the 6A device limited to 70%. see
Output_Power_638A
2)
With S1 full load operation > 1,1KW a linechoke with uk >= 4% is recommended.
e.g. E12-0018KL.
3)
Recommended: UL listed (JDDZ) Fusible cut-out Class K5, Class H, Class J, Class CC or
rather UL listed (JDRX) Class H.
4)
Recommended e.g. EATONr
5)
Class gRL fuses combine protection for cable and semiconductors.
e.g. Fa. SIBA Sicherungs-Bau GmbH
Serie 60 034.34.16; Fuseholder 5106304.x (up to 30A)
Serie 50124.34.xx, Fuseholder 5105804.3 (up to 40A)
If these fuses are used, the mains voltage may only be switched on, when the Softstart -
function is active. (Device in Undervoltage operating state).
6)
With S1 full load operation > 5,5KW a linechoke with uk >= 4% is recommended.
e.g.Parker E31-0018KL and for UL-Recommendation Block LR3 40-4/16.
7)
UL listed (JDDZ) Fusible cut-out Class J or Class CC.
For DC-Link Applications Class CC Types are recommended.
If Class CC Types are used, the mains voltage may only be switched on, when the Softstart -
function is active. (Device in Undervoltage operating state)