Parker 44 Series Скачать руководство пользователя страница 5

Bulletin MSG30-3245-INST/UK 

Installation Manual

5

Parker Hannifin

Pump & Motor Division Europe

Chemnitz, Germany

Axial Piston Pump

Series PV, series 44 and higher

Flushing port

The PV pumps of design series 44+ are equipped 

with three drain ports*. In addition pumps with seal 

option W and P, all pumps PV140 - PV360 and pumps 

with X-modification X5830 (bearing flushing port) 

are equipped with a flushing port for front bearing 

and shaft seal. The flushing flow can - depending on 

the actual working conditions - be used to keep the 

pump case filled, to warm up the pump (during cold 

temperature operation) or for better heat dissipation 

e. g. for operation with HFC fluids (water glycole) to 

keep the case fluid temperature in the allowed range. 

Permanent dead head operation ( >15 min) either for 

pumps of frame size 3 and larger (PV063 and higher) 

or at high input speeds above 1,800 rpm requires 

flushing of the pump case.

Flushing should be taken from the filter/cooling 

circuit (e. g. pre-loaded return line). Recommended 

flushing flows see following table.
PV016 - PV028 

4 - 6 l/min

PV032 - PV046, PV076 

5 - 8 l/min

PV063 - PV092 

7 - 10 l/min

PV140 - PV180 

9 - 12 l/min

PV270 - PV360 

13 - 17 l/min

(flushing flow for front bearing: 10 - 15% of the total 

flushing flow)

Drive input

For direct drive use elastic coupling free of axial 

and radial reaction forces. Please follow strictly the 

instructions of the coupling supplier regarding axial 

clearance, axial displacement and angular toler-

ances. Couplings never shall be mounted using a 

hammer. Threads in the shaft end allow smooth 

mounting of the coupling.

The drive shaft should only carry true torque. 

Contact Parker for allowable side loads or axial forces.
PV pumps are normally for one direction of rotation 

only. Therefore check rotation of drive motor prior to 

installation.

Electrical interface

Check voltage, current, phase and connection prop-

erties. Verify direction of motor rotation.

Fluid reservoir

The reservoir needs to meet all system requirements 

concerning design, size, location and porting. Beside 

beeing reservoir for the hydraulic fluid, the tank also 

supports heat dissipation, air removal, water removal 

and contamination sedimentation. Often the reservoir 

also is the fundament for the motor pump unit. In this 

case the separation of pump and remaining struc-

ture by elastic means is mandatory to avoid noise 

and vibration being induced into the frame work. 

The reservoir needs to be carefully sealed against 

ingression of contamination and water. A level indica-

tor and thermometer should be placed in an easily 

accessible location. 

Fluid content (general rule): stationary systems 3 

to 4 times pump nominal flow, 1 times or even smaller 

in mobile systems.

Filling of the system

Use only high quality mineral oil based fluids, like 

HLP oils according to DIN 51524 part 2. For other 

fluids (HFC, HFD, bio degradable or synthetic fluids) 

please contact Parker and review the Hydraulic Fluids 

Information in Catalogue  2500/UK.
Operation viscosity should be 16 to 100 mm²/s, op-

timum viscosity range is in the 20 to 40 mm²/s, max. 

viscosity  for short time up to 320 mm²/s.
Because of the possibly uncompatible ingredients 

fluids should not be mixed (separation of fluid, reduc-

tion or loss of fluid properties).

Pay highest attention on cleanliness!

Fill system only via a filtration device. Use filtration 

unit, when basic contamination of the refill fluid ex-

ceeds class 10 according NAS 1638 (contamination 

level 21/19/16 according to ISO 4406). Hydraulic 

fluid supplied in barrels typically exceeds these con-

tamination levels.

Filtration

Filtration is the most important factor to the opera-

tional life of the hydraulic system. Statistical analy-

ses indicate, that contamination is by far the most 

important reason for system or component failure. 

Use return line, pressure and/or bypass filtration. 

Bypass filtration usually is most efficient. For general 

purpose hydraulic systems with limited requirements 

for operational life contamination level 19/15 accord-

ing to ISO 4406 should be desired; corresponding fil-

ter rating: x = 25 

µ

m ( b

25

75 ) according to ISO 4572.

Cleanliness level for systems with higher re-quire-

ments for operational life and functional safety should 

be 18/16/13 according to ISO 4406; corresponding 

filter rating x = 10 

µ

m ( b

10

75 ) according to ISO 4572. 

Use filter with indicator or electrical signal when 

capacity limit is approached.

Suction filter should be avoided. Suction condi-

tions will be affected. Filter can be blocked and cause 

cavitation and severe pump damage. When used, a 

vacuum sensor with shut off function is mandatory.

Properly dimensioned breather rating 

10 

µ

should be used. Observe min. and max. fluid level; 

consider exchange volume with cylinders in the 

system.

Filling of pump case

Pump case  must be filled via the drain port, to ensure 

lubrication, sealing and smooth start up.

Содержание 44 Series

Страница 1: ...additional support parker com pmde Effective December 20 2018 Supersedes July 1 2010 Bulletin MSG30 3245 INST UK Installation and start up information PV series Design series 44 PVplus Variable displacement axial piston pump ...

Страница 2: ...making the final selection of the products and systems and assuring that all performance and safety requirements of the application are met The products are subject to change by Parker Hannifin GmbH at any time without notice Contents Page 1 Installation and start up 3 2 Displacement adjustment 6 3 Standard pressure compensator code MMC 6 4 Standard pressure compensator with D03 interface code MM1...

Страница 3: ...low pressure pipe avoid sharp el bows and any restriction of cross section The suction pipe must have access to clean cooled and filtered fluid free of air bubbles No tur bulences or high flow velocities should occur at the tube inlet Therefore position inlet as far as possible away from return line and drain line Make sure that the fluid circulation in the reservoir does keep return flow from suc...

Страница 4: ...hing port covered below pump alternative drain port L3 case drain line from drain port main flushing line to alter native drain port 1 2 bearing flushing line to bearing flushing port PV016 092 PV270 PV360 DS45 Port L1 on top L2 L3 at the side L4 at bottom standard PV270 360 Interface for compensator Alternative drain port Drain port Pressure port outlet Suction port inlet Gage port Flushing port ...

Страница 5: ...mandatory to avoid noise and vibration being induced into the frame work The reservoir needs to be carefully sealed against ingression of contamination and water A level indica tor and thermometer should be placed in an easily accessible location Fluid content general rule stationary systems 3 to 4 times pump nominal flow 1 times or even smaller in mobile systems Filling of the system Use only hig...

Страница 6: ...ing the adjustment screw clockwise will reduce the pumps displacement For the sizes PV016 PV092 the thread pitch is 1mm for sizes PV140 PV360 the thread pitch is 1 5 mm The table shows the displacement change per mm resp per turn and the minimum adjustable displacement Note All pumps are adjusted and tested after as sembly in our factory Only the compensator pressure needs to be adjusted That is d...

Страница 7: ...NG6 DIN 24 340 compensator differential adjustment lock nut pressure adjustment lock nut 5 Standard pressure compensator for accessory mounting code MMZ interface NG6 DIN 24 340 Version MMZ is designed especially for compen sator accessory mounting ordering code PVAC see chapter 12 Because the accessory packages come with their own pilot valves this version has no integrated pilot catridge to avoi...

Страница 8: ...g or flow compensator primarily controls the pump output flow To achieve this the load pressure after a main stream throttle valve load sensing valve not included in the shipment of the pump is connected to the load sensing port of the compensator The compensator control strategy is to keep the pressure drop constant across this main stream throttle valve The integrated pilot valve maintains a pre...

Страница 9: ... two spool compensator code MT has two separate compensator valves for flow load sensing and pressure compensation That results in a steeper pressure compensation curve which can be beneficial in certain applications The flow control stage has no integrated pilot valve because this would eliminate the effect of the two spool control The pressure stage has no integrated pilot valve because during f...

Страница 10: ...e power compensator with load sensing code C a modified load sensing compensator is used Constant horse power curve with adjustment 9 Horse power compensator codes L C Adjustment A tolerance compensation for optimized performance done at pilot cartridge Adjustment B maximum pressure setting done at integrated pressure pilot valve At the adjustment screw of the horse power pilot valve a basic adjus...

Страница 11: ...ing and stand by pressure In neutral position both cartridges are con nected to the compensator valve The lower pressure defines the compensating pressure of the pump When the A solenoid B side of the DCV is energized only the A side cartridge is connected the higher pressure adjusted there defines the compensating pressure When solenoid B is energized the valve spool con nects all four ports Then...

Страница 12: ...blocked E g by plugs cleaning tissues plastic plugs Ball valve in the suction line closed Suction filter blocked Solution Check suction line for free flow Open valves in suction line Valves should be equipped with electrical indicator Check suction filter Reason Suction line not gas tight pump gets air into suction port Solution Seal suction line against air ingression Reason Pressure line system ...

Страница 13: ...r side of load sensing valve Reason No or too low pressure at pump outlet port Solution Pump outlet pressure must be at least 15 bar because otherwise the bias spring in the pump cannot be compressed Pump does not upstroke sticks at zero displacement Reason Compensator is blocked due to contamination Solution Clean hydraulic fluid clean compensator valve Reason Cable to LVDT or proportional soleno...

Страница 14: ...Bulletin MSG30 3245 INST UK Installation Manual 14 Parker Hannifin Pump Motor Division Europe Chemnitz Germany Axial Piston Pump Series PV series 44 and higher Notes ...

Страница 15: ...PRODUCTS DESCRIBED HEREIN OR RELATED ITEMS CAN CAUSE DEATH PERSONAL INJURY AND PROPERTY DAMAGE This document and other information from Parker Hannifin Corporation its subsidiaries and author ized distributors provide product or system options for further investigation by users having technical expertise The user through its own analysis and testing is solely responsible for making the final selec...

Страница 16: ...rope Chemnitz Germany Axial Piston Pump Series PV series 44 and higher Parker Hannifin MSG30 3245 INST UK Manufacturing Germany GmbH Co KG Pump Motor Division Europe Neefestr 96 D 09116 Chemnitz Tel 49 0 371 3937 0 Fax 49 0 371 3937 488 Copyright 2018 www parker com pmde All rights reserved ...

Отзывы: