250
3
English
5 Control
5.1 Control
panel
3
4
2
1
y
x
é
z
[
&
Display
Reference
Name
Description
1
MAIN SWITCH
I ON = dryer powered;
O OFF = dryer not powered
2
POWER LED
Yellow = dryer powered
Green = dryer operating
3
WARNING LED
Off = no signal
Flashing = Alarm or warning
4
DRAIN LED
Lit = Drain open
Keyboard mode
STANDARD
MENU*
x
ON/OFF BUTTON
Switching no/off Confi rm
z
RESET BUTTON
Reset alarm/warnigng
Up
é
HISTORY BUTTON
Alarm/warning log
Down
y
DRAIN BUTTON
Condensate drain
Out
*returns to STANDARD mode aft er 5 minutes.
5.2 Operation
Operation status
With the MAIN SWITCH
&
turned to “I ON” (dryer powered) three
working conditions are possible:
DRYER
STATUS
DISPLAY
[
POWER LED (2)
1
OFF
OFF
Yellow
2
ON Dew
point
Green
3
REMOTE OFF
r.OF
Yellow
To switch from OFF to ON turned to “I ON” (and vice versa) press
x
.
!
In OFF status the unit remains powered until the MAIN SWITCH
&
turned to “I OFF”.
Y
To manage REMOTE OFF mode, remove the bridge be-
tween terminals X4.0 and X4.10 (see par. 8.8.) and connect
the remote start/stop switch(to be provided by the customer).
In ON status, use the button with the following logic:
X4.0 X4.10
X4.0 X4.10
DRYER STATUS
ON
REMOTE OFF
!
Do not activate ON status (refrigeration compressor operating)
more than 10 times in one hour.
Scheduled maintenance
Y
When the DISPLAY
[
alternatively shows the Sr warning
code and dew point, contact authorized assistance personnel for carry-
ing out scheduled maintenance indicated in par. 6.3 and for resetting the
warning code (see par. 5.4 in List of alarm/warnings).
Press
z
to cancel the warning for 24 hours.
Condensate drain
Th
ere are two operation modes:
• TIMED - check that the automatic condensate drainage system is
working properly.
Use manual drainage to check that condensate is not retained as this
is symptomatic of poor drainage.
Th
is check of the timed drain opening (parameter d1).
Settings depends upon the operating conditions of the dryer and var-
ies the amount of condensate to be removed.
For standard dryer operating conditions, see the following table of
recommended settings:
Model
Parameter d1
250
5
• EXTERNAL - if there is an external drain (24VAC).
To change operation mode, use the parameter d3 (see par. 5.3 in List
of parameters).
Y
Only set the EXTERNAL mode in absence of the solenoid valve.
Otherwise the relative coil could become damaged.
Alarm log
Contains the descriptions of the last alarms (max. 8).
Press
é
for 5 seconds: the keypad now operates in
Alarm
MENU
mode and the events can be scrolled with
z
and
é
.
Every event is displayed with “ALx” (x=1-8).
AL1 = most recent event.
If there are no events “---“ appears.
Содержание 250
Страница 2: ......
Страница 27: ...250 25 8 5 Exploded drawing 250 2 3 4 B1 9 6 12 15 B3 1 8 QS1 A B C D E ...
Страница 28: ...250 26 8 6 Dimensional 250 i n c h e s mm c e n t e r o f g r a v i t y p o s i t i o n ...
Страница 29: ...250 27 8 7 Refrigerant circuit 250 A1 ...
Страница 30: ...250 28 8 8 Wiring diagram 230V 1Ph 60Hz ...
Страница 31: ...250 29 8 8 Wiring diagram 230V 1Ph 60Hz ...
Страница 32: ...250 30 8 8 Wiring diagram 230V 1Ph 60Hz ...
Страница 33: ...250 31 8 8 Wiring diagram 230V 1Ph 60Hz ...
Страница 34: ...250 32 8 8 Wiring diagram 230V 1Ph 60Hz 5x20 24V 1A T ...
Страница 35: ...250 33 8 8 Wiring diagram 230V 3Ph 60Hz ...
Страница 36: ...250 34 8 8 Wiring diagram 230V 3Ph 60Hz ...
Страница 37: ...250 35 8 8 Wiring diagram 230V 3Ph 60Hz ...
Страница 38: ...250 36 8 8 Wiring diagram 230V 3Ph 60Hz ...
Страница 39: ...250 37 8 8 Wiring diagram 230V 3Ph 60Hz ...
Страница 40: ...250 38 8 8 Wiring diagram 230V 3Ph 60Hz ...
Страница 41: ...250 39 8 8 Wiring diagram 460V 3Ph 60Hz ...
Страница 42: ...250 40 8 8 Wiring diagram 460V 3Ph 60Hz ...