Safety & EMC Requirements
Where there is a conflict between safety and EMC requirements, personnel safety shall always take
precedence.
WARNING!
Ignoring the following may result in injury or
damage to equipment:
- Never perform high voltage resistance checks on the wiring
without first disconnecting the inverter from the circuit being
tested.
- Whilst ensuring ventilation is sufficient, provide guarding and /or
additional safety systems to prevent injury or damage to
equipment.
- When replacing an inverter in an application and before returning
to use, it is essential that all user defined parameters for the
product’s operation are correctly installed.
- When replacing an inverter in an application and before returning
to use, it is essential that all user defined parameters for the
product’s operation are correctly installed.
- All control and signal terminals are SELV, i.e. protected by double
insulation. Ensure all external wiring is rated for the highest
system voltage.
- Thermal sensors contained within the motor must have at least
basic insulation.
- All exposed metalwork in the Inverter is protected by basic
insulation and bonded to a safety earth.
- RCDs are not recommended for use with this product but, where
their use is mandatory, only Type B RCDs should be used.
WARNING!
Ignoring the following may result in injury or
damage to equipment:
- In a domestic environment this product may cause radio
interference in which case supplementary mitigation measures
may be required.
- This equipment contains electrostatic discharge (ESD) sensitive
parts. Observe static control precautions when handling,
installing and servicing this product.
- This is a product of the restricted sales distribution class
according to IEC 61800-3. It is designated as “professional
equipment” as defined in EN61000-3-2 for. Permission of the
supply authority shall be obtained before connection to the public
low voltage supply.