023-064X Technical Manual

  

 
 

8

 

3.2  User settings list 

To view the current settings on the model 023-064X, press right 

 several times. 

To modify the current setting press up 

 or down 

To save, press 

left 

and 

up

 arrows 

 and 

 at the same time.  The appearance of **OK** will confirm successful 

save. 

 

Setting Code       

Definition                    

 

 

Display Maximum value       default 

============================================================================= 

Sensor A 

(first module, plugged into the top slot)  

 

 

Firmware rev 2B29.9 

 

      

Sensor B

 (second module, plugged into the bottom slot) 

00 

18 

Alarm 1 and relay limit  

 

 

AL1     

sensor scale     

400ppm 

01 

19 

Alarm 1 set time (seconds) 

 

 

A1Del 

999 

 

5s 

02 

20 

Alarm 1 reset time (seconds)   

 

A1Off 

999 

 

300s 

03 

21 

Alarm 2 limit          

 

 

AL2 

sensor scale    

400ppm 

04 

22 

Alarm 2 set time 

 

 

 

A2Del 

999 

 

5s 

05 

23 

Alarm 2 reset time   

 

 

A2Off 

999 

 

300s 

06 

24 

Alarm 3 limit          

 

 

AL3 

sensor scale     

400ppm   

07 

25 

Alarm 3 set time    

 

 

A3Del 

999           

5s 

08 

26 

Alarm 3 reset time   

 

 

A3Off 

999           

5s 

 
40 

 

sensor A analog output zero (factory set) 

AnZA 

255         

41 

 

sensor A analog output span (factory set) 

AnSA 

255 

42 

 

sensor B analog output zero (factory set) 

AnZB 

255         

43 

 

sensor B analog output span (factory set) 

AnSB 

255 

44 

 

°C 

temperature display 0=off 1=on 

 

Temp 

0/1 

 

45 

 

audio alarm 3 off/on 

 

    

 

Aud 

0/1 

 

49 

 

Keyboard security lock, 0=off, 1=on 

 

KBL 

0/1 

 

50 

 

Temperature modify/correct   

 

TMod 

-9/+9

°C

 

51 

 

High temperature alarm limit (alarm 1)   

ATHi 

0-99

°C

    

60 

52 

 

Warm up delay, disables alarms on power up 

W/U 

0-99 mins 

60 

55 

 

Low temperature alarm limit (alarm 3)   

ATLo 

0-99

°C 

 

56 

 

Network Display on/off (non BACnet version) 

Net 

0/1 

 

57 

 

sensor A refrigerant ppm scale 

 

Ref-A 

Refrig list 

Rx 

58 

 

sensor B refrigerant ppm scale 

 

Ref-B 

Refrig list 

Rx 

Where default Rx is R507 for 023-0642 and R22 for 023-0643 

 
 

3.3  Test 

 

Analog output 

To test the output signal, power the sensor and wait for the warm-up period to expire 
Press right

 

 

several times until you see 40 AnZA

Press up

 

 

or down

 

 

to fine tune the output. 

Use 40

 

AnZA to force sensor A output to 2V (4mA) (min range 0 ppm) 

Use 41

 

AnSA to force sensor A output to 10V (20mA) (max range) 

Use 42

 

AnZB to force sensor B output to 2V (4mA) (min range 0 ppm) 

Use 43

 

AnSB to force sensor B output to 10V (20mA) (max range) 

 

Relay output 

To force the relay output 1 for 5 minutes, press 

up 

 

for more than 5 sec. Add 5 minutes each time you 

press 

up 

“MAN” or “M” at the left of the display will tell that the relay is overridden. 
To cancel the relay override, press 

down 

 

 

Содержание 023-064 Series

Страница 1: ...or by any means electronic mechanical photocopying recording or otherwise without the prior written permission of Parker Hannifin Canada Micro Thermo Technologies is a trademark of Parker Hannifin Ca...

Страница 2: ...ettings list 8 3 3 Test 8 4 Operation 9 5 Calibration 9 6 MT Alliance installation 10 7 To add a missing Sensor model in the list 12 Safety Information This manual describes information required to in...

Страница 3: ...master slave operation or central control via a controller Pre calibrated plug and play sensor modules avoid the need to recalibrate when upgrading expired sensors Impact resistant water resistant enc...

Страница 4: ...C 88 F decreasing linearity to 50 rh at 40 C 104 F 1 5 User Interface Back lit LCD display shows gas concentration user settings and alarm status Red LED alarm indicators gas level 1 and 2 High inten...

Страница 5: ...to 5 feet 1 to 2 meters from the floor when the ceiling is 7 to 10 feet high If the ceiling height is higher than 10 feet for example for heavy equipment the carbon monoxide detectors are installed at...

Страница 6: ...ual pull station panel 24Vac 5VA Transformer Sensor GND Sensor U Input To sensor node Binary Input from limit switch AL1 AL2 AL3 PWR BI S L H S R141b 123 10 Active Sensor Alarm PPM reading Jumper Up P...

Страница 7: ...ermine the threshold of Sensor A at which the relay should operate default is 400ppm Setting 1 A1Del is the set time default is 30 sec 2 A1Off is the reset time default is 20 sec The relay reset by it...

Страница 8: ...55 44 C temperature display 0 off 1 on Temp 0 1 0 45 audio alarm 3 off on Aud 0 1 1 49 Keyboard security lock 0 off 1 on KBL 0 1 0 50 Temperature modify correct TMod 9 9 C 51 High temperature alarm li...

Страница 9: ...concentration drops below the threshold AL1 is for relay settings AL2 is for alarm 2 settings and AL3 is for alarm 3 and buzzer settings See section 3 2 User settings list to change any setting The bu...

Страница 10: ...tration Type Local Source Micro Thermo Manufacturer and the Sensor Model and gas type you are going to monitor pre defined sensor model will be available in version MTA 8 5 For previous version create...

Страница 11: ...alarm You can use predefined values by clicking on Pick Alarm Settings button Select the Hardware tab to review the sensor manufacturer and model and where you can select the node and input where this...

Страница 12: ...nge accordingly to the table at section 1 3 Ordering information Electrical point values are constant and should always be 9 45V and 2V respectively Please pay special attention to put 1 of full range...

Отзывы: