3. Installing the CPX-1000
1000-A2-GN22-00
3-18
February 2003
Step 3
Set the rear circuit breaker to the
Off/
0
position (if it is not
already off).
Step 4
Remove the cover from the plant battery terminal strip.
Step 5
Connect the
−
48 VDC A and
−
48 VDC B terminals of the CPX to the
−
48 VDC A and B outputs of the power source using two 14 AWG
(or larger), stranded or solid wires terminated in #10 size
compression ring lugs (Caltronics #RT-117, or equivalents).
Step 6
Connect the Return A and Return B terminals of the CPX to the A
(+) and B (+) terminals of the power source as in step 5.
Step 7
Run the
−
48V power and battery return wires across the back of
each CPX shelf and along the side of the equipment rack, or use the
optional Cable Management Assembly.
Note
Be sure that all grounding connection surfaces are free
and clear of contaminants.
Caution
Make proper polarity connections. Damage may occur to
the circuitry when powered up if polarity is reversed.
Note
If you use 14 AWG wire, be sure that the plant battery
power distribution point
is no more than 40
feet
from
the CPX. Use a larger gauge wire if the power source is
further away.
Note
The RTN A and RTN B terminals are also connected
together inside the CPX enclosure.
Содержание Jetstream CPX-1000
Страница 14: ...Preface 1000 A2 GN22 00 x February 2003...
Страница 24: ...1 Voice over Broadband Networking 1000 A2 GN22 00 1 10 February 2003...
Страница 64: ...2 CPX 1000 Voice Services Platform Description 1000 A2 GN22 00 2 40 February 2003...
Страница 100: ...3 Installing the CPX 1000 1000 A2 GN22 00 3 36 February 2003...
Страница 128: ...5 Repair Procedures 1000 A2 GN22 00 5 14 February 2003...
Страница 156: ...D Specifications 1000 A2 GN22 00 D 8 February 2003...