- Advanced Analog Fire Alarm Control Panel

4. Controls Via Keypad

Keypad keys, are activated only when the key of the  Keyswitch is set in the Control 

Enable position.  

4.1 System SILENCE key

Pressing the 

SILENCE

 key will cause any existing audible signal to stop. If a 

new event occurs, the silenced condition will be canceled and the appropriate 

devices will resound.         

4.2 System TEST key

By pressing the 

System TEST

 key all the visual indicators of the keypad turn 

ON,  confirming  that  none  of  the  LEDs  are  damaged. The  condition  is  main

-

tained for as long as the 

System TEST 

key is kept pressed. The buzzer and the 

main sounders are also active during the test. 

4.3 System RESET key

The 

System RESET

 key is used for resetting the system’s zones in Standby 

mode after an alarm. 

4.4 Zones BYPASS keys

(also called zone disablements)

The 

Zones BYPASS

 keys are used to prevent the corresponding zone from causing 

an alarm. Note that zone disablements must not be a permanent working condition and 

they must be used only as a temporary action. For example zone bypassing can be used 

in case of building maintenance or other activities that can trigger false alarms on the 

detectors.

Bypassing a zone is achieved by positioning the keyswitch in the 

Control Enable

 posi-

tion and then pressing the corresponding 

Zones BYPASS

 key. At the same time 

the indicator is turned ON. It only returns to normal operation by pressing the 

same key again (toggle action). If one of the 

Zones BYPASS

 key indicators is 

turned ON (yellow color) the corresponding zone is isolated and does not cause 

alarms. If an error occurs to a bypassed zone,  the 

General FAULT

 indicator is 

activated but the system stays in silent mode. An alarm condition to a bypassed 

zone is recognized and indicated but do not activate the sounders. 
If any of the zones is in bypass state the buzzer sounds every 1 minute to re-

mind the user of the existing disablement.

Содержание Matrix2000

Страница 1: ...Matrix2000 User Guide CPD Advanced Analog Fire Alarm Control Panel 4 24 Zones Version 2 0 Revision 0 2 ...

Страница 2: ... be used in conjunction with products not man ufactured by PARADOX FIRE PARADOX FIRE cannot guarantee the performance of the fire alarm system and shall not be responsible in any way whatsoever for faulty installation or connection RoHS directive compliance The EC RoHS guideline has been released in order to reduce the heavy metal load in electrical and electronic products caused by e g lead and m...

Страница 3: ...ral Fault 5 2 3 1 SIGNALING DEVICE fault 6 2 3 2 EARTH fault 6 2 3 3 AUX POWER Fault 6 2 4 Zone Fault indications 6 2 5 System ALARM indication 7 2 6 Zones ALARM indications 7 3 Central Electric Keyswitch 8 4 Controls Via Keypad 9 4 1 System SILENCE key 9 4 2 System TEST key 9 4 3 System RESET key 9 4 4 Zones BYPASS keys 9 TABLE OF CONTENTS ...

Страница 4: ...ications and the simple controls of the Matrix2000 panel ensure the easy handling and controlling of the system by the operator 2 Keyboard Indications and Controls Operating monitoring and programming of the panel is performed in three different ac cess levels Access to level 2 is achieved by the keyswitch on the face of the panel Figure 1 Operations at access level 2 are performed with the silico...

Страница 5: ...e Battery wear increased internal resistance of batteries 2 2 System FAULT indication General Fault GENERAL FAULT indicates a problem in the system It turns ON in case of Zone wiring connection problems Signalling devices output wiring problems Relays outputs wiring problems auxiliary relays MER4 or MER8 Auxiliary power faults Earth fault condition The above mentioned problems could be open circui...

Страница 6: ...ll stop functioning If more than 1 Amp is required a compatible EN 54 4 approved fire alarm power supply must be used When such a power supply is used the 24 OUT connection of the panel must be connected to the negative terminal of the auxiliary power supply 2 4 Zone Fault indications The Zone Fault indications will blink in a different pattern Figure 2 page 6 depending on the type of the problem ...

Страница 7: ...ored Software Watchdog The Matrix2000 panel contains a watchdog circuit that will activate when the micropro cessor is either faulty or unable to execute the programmed firmware Upon detection the Fault relay the on board sounder and the fault indicator on the user interface are all activated 2 5 System ALARM indication When the system detects a condition of fire smoke high temperature etc the pan...

Страница 8: ...tral electric Keyswitch has three positions 1st position Access Level 1 Normal This is the Normal operation mode The panel waits for alarm events or any faults that may develop in the installation All buttons on the silicon rubber keypad are disabled 2nd position Access Level 2 Control Enable Alarm events and possible faults are detected all buttons on the silicon rubber keypad are active and the ...

Страница 9: ... are used to prevent the corresponding zone from causing an alarm Note that zone disablements must not be a permanent working condition and they must be used only as a temporary action For example zone bypassing can be used in case of building maintenance or other activities that can trigger false alarms on the detectors Bypassing a zone is achieved by positioning the keyswitch in the Control Enab...

Страница 10: ...t button 1 RESPONDING TO TROUBLE SIGNALS Turn the keyswitch of the keyboard to Con 1 trol Enable Silence the panel buzzer 2 Investigate the cause of the trouble and 3 notify the authorized service personnel im mediately TO SILENCE THE PANEL BUZZER Press Panel Silence 1 The buzzer turns OFF Any new events turn the buzzer back on Trouble conditions not cleared resound the buzzer after a predetermine...

Страница 11: ..._______________________________________________________ Zone 12 ______________________________________________________________________ Zone 13 ______________________________________________________________________ Zone 14 ______________________________________________________________________ Zone 15 ______________________________________________________________________ Zone 16 ____________________...

Страница 12: ...Document Part Number MATRIX UG01 CPD version 2 0 revision 0 2 November 2010 ...

Отзывы: