![Paradox Hellas S.A. Elix Скачать руководство пользователя страница 2](http://html.mh-extra.com/html/paradox-hellas-s-a/elix/elix_user-manual_753657002.webp)
The system will automatically exit the programming mode if no user interaction takes place for more than 60
seconds.
The programming procedure consists of two (2) steps. The user advances to the next step by pressing the
PRG/TEST
button for more than 3 seconds. The steps are described below:
STEP 1: Brightness level with main power present (
PWR
and
FLT
LEDs blinking)
In this step the user sets the brightness level produced by ELIX while the mains supply power is present. By
instantaneously pressing the
PRG/TEST
button the brightness cycles through the six (6) available levels
(including the off state). When the desired brightness is active, the user presses the
PRG/TEST
button for
more than three (3) seconds; the brightness level is saved and the programming continuous to STEP 2.
If EMERGENCY ONLY operation is required the user must select Zero Brightness (Lighting
element OFF).
STEP 2: Brightness level during mains power loss (
PWR
and
BAT
LEDs blinking)
In this step the user sets the brightness level produced by ELIX while the mains supply power is lost. By
instantaneously pressing the
PRG/TEST
button the brightness cycles through the five (5) available levels
(minimum to maximum brightness). When the desired brightness is active, the user presses the
PRG/TEST
button for more than three (3) seconds; the brightness level is saved and the programming is completed.
After the completion of the programming steps ELIX returns to normal operation.
During the programming operation, ELIX does not check the mains power or execute any
diagnostic tests.
3. Indications Functionality
PWR Indication (green LED)
• OFF:
Mains voltage is low or lost.
• ON:
Mains voltage is present.
FLT Indication (yellow LED)
• OFF:
Light Elements in normal mode.
• Blinking:
Light Elements Fault.
BAT Indication (red LED)
• OFF:
Battery is working properly.
• ON:
Battery Fault.
• Blinking:
Battery has lost capacity and will need to be replaced soon.
SYSTEM IN NORMAL OPERATION MODE
LED INDICATOR
STATE
Description
PWR
(green)
ON
Mains power present
OFF
Mains power is lost
FLT
(yellow)
BLINK
Light element Fault
BAT
(red)
ON
Battery Fault
BLINK
Battery reduced capacity, needs to be replaced soon
SYSTEM IN PROGRAMMING MODE
LED INDICATOR
STATE
Description
PWR
BLINK
System enters programming mode
FLT
BLINK
System is in STEP 1
BAT
BLINK
System is in STEP 2