4. Technical Characteristics
Power Supply
230VAC / 50Hz
Max. Power Consumption
Less than 5VA
Light Source
12 LED
Battery
3.6V 1.0Ah NiCd
Emergency Operation Time
From 150min to 240min depending on luminance setting
Luminance setting
5 steps (20, 40, 60, 80 & 100%)
Light source intensity (230V)
100lm
Switch over Voltage
Between 150 ~ 190V
IP rating
IP20
Isolation Category
Mains connection Doubly isolated
Environmental
Temperature: 5 to 45 °C
Humidity: 5 to 95% RH, non-condensating
Dimensions [WxHxD]
260x125x35.5 mm
Indication Area Dimensions [WxH]
228x75 mm
Guarantee
3 years (1 year for the battery)
5. Installation instructions
ATTENTION! The installation and maintenance of this unit must be performed by qualified
personnel only. Mains voltages are lethal. Electrical wiring must be compliant to all safety and
electrical regulations that apply.
Wall mounting installation:
The unit should be surface mounted. To wall mount the cabinet:
1. Remove the two screws on the left and right side of the device to be installed.
2. Open the case by pushing down on the two plastic tabs and pulling the face of the device forward.
3.
Remove the reflector assembly by gently holding it from it’s bottom side and pulling outward.
4. Use the back cover to mark the required drill points on the mounting surface (wall). Drill the required
holes.
5. Remove one of the three available knock outs, pass the mains cable through.
6.
Place the back cover on the wall and fix it in place with screws.
7. Connect the mains cable on the terminal block.
8.
Place the reflector assembly by sliding it in place.
9. Connect the battery (see battery replacement)
10. Place the front cover by hooking the two hinges at the bottom of the unit and gently pushing upward.
Push on the top side until the plastic tabs lock in place.
11. Place the screws in place paying attention to not overtight them.
Figure 2.
ELIX wall mounting base
Battery replacement:
ELIX contains a replaceable battery. The unit contains electronics required for the verification of the battery’s
good health. Change the battery when the indication
BAT
blinks. Change the battery according to the
following procedure:
1. Disconnect the 220VAC power from ELIX.
2. Remove the screws holding the battery cover in place, then remove the battery cover.
3. Remove the old battery from the battery holder.
4. Gently pull the battery cable until the battery connector is visible.
5. Disconnect the old battery from the exposed connector.
6. Connect the new battery observing the correct polarity.