18
19
English
English
Possible Cause
Symptom
What To Do
Press and release the On/Off/
Test button to start UPS
On/Off/Test button not
pushed
UPS will not turn on
Reset circuit breaker by
pressing the plunger back in.
If the AC circuit breaker trips
after UPS starts up, reduce
the load on the UPS
UPS operates in
battery mode only,
even though there is
normal AC present
Input AC circuit breaker is
tripped
UPS has detected an inter-
nal fault
Call for service
Fault LED is illumi-
nated
The On-Line LED
is illuminated, but
there is no output
Disconnect the computer
cable from the UPS and press
the On button. If UPS works
normally, the software has
control of the UPS
The UPS is being con-
trolled via its communica-
tions port
The batteries may be weak
or at the end of useful
service life
Charge the batteries for 8
hours and retest. -If the
runtime is still less than ex-
pected, the batteries may
need to be replaced, even
though the Weak/Bad Battery
LED is not illuminated
UPS does not pro-
vide the expected
runtime
Weak/Bad Battery
LED is illuminated
Overload LED is
illuminated and a
constant alarm
The On-Line LED is
illuminated and Load
Segment 1 has an
output, but there is
no output from Load
Segment 2
Loose connections at the
batteries, Weak batteries,
Bad batteries
The load has exceeded the
UPS's capacity
The output breaker for Load
Segment 2 is tripped,
Load Segment 2 was
turned off by the software
or the SNMP card
Check battery connections,
charge the batteries for 8-
hours and then retest, replace
the batteries
Check the specifications (see
section 8). Remove part of
the load
Reset the output breaker for
Load Segment 2, turn on Load
Segment 2 by the software or
the SNMP card
REPLACING THE BATTERY
WARNING!
This Uninterruptible Power Supply contains potentially hazardous
voltages. Do not attempt to disassemble the UPS beyond the
battery replacement procedure. This UPS contains no
user serviceable parts. Repairs and Battery replacement must
be performed by QUALIFIED SERVICE PERSONNEL ONLY.
Do not open or mutilate batteries. Released electrolyte is harmful
to the skin and eyes and may be toxic.
CAUTION:
(QUALIFIED SERVICE PERSONNEL ONLY)
CAUTION:
Do not dispose of batteries in a fire. The batteries may explode.
The batteries in this UPS are recyclable. Dispose of the batteries
properly. The batteries contain lead and pose a hazard to the
environment and human health if not disposed of properly. Refer
to local codes for proper disposal requirements or return the
battery to the supplier.
Although battery system voltages are only 24VDC, 48VDC and
72VDC the battery system can still present a risk of electrical
shock. These batteries produce sufficient current to burn wire or
tools very rapidly, producing molten metal. Observe these pre-
cautions when replacing the batteries:
1. Remove watches, rings, or other metal objects.
2. Use hand tools with insulated handles.
3. Wear protective eye gear (goggles), rubber gloves and boots.
4. Do not lay tools or other metal parts on top of batteries.
5. Disconnect the charging source prior to connecting or disco-
nnecting the battery terminals.
6. Determine if the battery is inadvertently grounded. If the batte-
ry is, remove the source of the grounding. Contact with any p-
art of a grounded battery can result in an electrical shock.
The likelihood of such shock will be reduced, if such grounds
are removed during installation and maintenance.
CAUTION:
The UPS has an easy to replace hot-swappable batteries. Please read all of
the WARNINGS and CAUTIONS before attempting to service the batteries.
NOTE: If there is a power interruption while replacing the hot-swappable
batteries, with the UPS on, the load will not be backed up.
Содержание ED1000RM2U
Страница 17: ...30 English Notes...