WALLMOUNT CONFIGURATION

The wallmount configuration

 

allows the user to mount the UPS on the wall.  There is

a wallmount bracket kit available for the UPS.  The kit includes two wall mounting
brackets, ten retaining screws, and the wallmount template.  

WARNING: 

Use two or

more people when installing the UPS.   Use 

CAUTION,

 the UPS is extremely heavy.

The UPS's side panels have mounting bracket screw holes for attaching the wall
mounting brackets.
1.  Once the location and position of the UPS has been determined, lay the UPS do-
      wn flat.

WARNING:  

The UPS must be installed in the proper up-right position.  If the UPS is

not installed in the proper up-right position the Batteries will be damaged.  Once the
UPS is placed on the wall, looking at the front panel the YELLOW Battery discon-
nected label on the top cover of the UPS MUST be on your left hand side.
2.  Align the mounting brackets with the mounting bracket screw holes and attach w-
    ith the six retaining screws.
3.  Use the template to mark the screw hole position on the wall.  

CAUTION, 

you sh-

     ould always were protective gear for your hands and eyes when operating power
     tools.
4.  Attach the four retaining screws to the wall and make sure that all of the retaining
    screws are screwed into structural material.  Then clean the area of any loose m-
     aterial.  Do not tighten the retaining screws all the way, leave approximately 3/8" of
     the retaining screws sticking out.
5.  Position the UPS, so that the mounting bracket keyed holes line up with the four
     retaining screws.  Slide the UPS down until its resting securely on the four retai-
     ning screws.
6.  Tighten the four retaining screws to secure the UPS to the wall.
7.  The LCD panel can be rotated to read in the up-right position.  Remove the front
      panel from the UPS.  On the backside of the front panel, push the LCD panel out-
     wards, the panel will pop out.  Position the LCD panel so that it reads in the up-
     right position.  Re-install the front panel on the UPS.
8.  The Wallmount Configuration is complete.  See Connecting your Equipment.

TOWER CONFIGURATION

The tower configuration allows the user to install the UPS in the up-right position
next to a tower computer.  The tower brackets are provided with the UPS.  

WARNING:

Use two or more people when installing the UPS.  Use 

CAUTION,

 the UPS is ex-

tremely heavy.
1.  Once the location of the UPS has been determined, place the tower brackets in
     the desired location.

WARNING:  

The UPS must be installed in the proper up-right position.  If the UPS is

not installed in the proper up-right position the Batteries will be damaged.  Once the
UPS is placed in the tower brackets, looking at the front panel the YELLOW Battery
disconnected label on the top cover of the UPS MUST be on your left hand side.
2.  Slide the UPS into the tower brackets.  Make sure that the UPS is stable.
3.  The LCD panel can be rotated to read in the up-right position.  Remove the front
      panel from the UPS.  On the backside of the front panel, push the LCD panel out-
     wards, the panel will pop out.  Position the LCD panel so that it reads in the up-
     right position.  Re-install the front panel on the UPS.
4.  The Tower Configuration is complete.  See Connecting your Equipment.

DESKTOP CONFIGURATION

The desktop configuration allows the user to install the monitor, the computer and
the UPS in one single stack.  

WARNING: 

Use two or more people when installing the

UPS.  Use 

CAUTION,

 the UPS is extremely heavy.

1.  Once the location of the UPS has been determined, lay the UPS down flat on the
     desk.
2.  Stack the computer and then the monitor on top of  the UPS.  

NOTE:

 Do not stack

     the UPS on top of the computer.  The UPS is heavy and may damage the other
     equipment.
3.  The Desktop Configuration is complete.  See Connecting your Equipment.

Содержание E750RTXL2U

Страница 1: ...r s Manual Enterprise Plus LCD RTXL UPS Series Para Systems Inc 1455 Lemay Dr Carrollton TX 75007 Phone 1 972 446 7363 Fax 1 972 446 9011 Internet minutemanups com UPS Sizing sizemyups com PN 34000431...

Страница 2: ...s and Indicators 6 3 Installation 9 4 Operation 15 5 Troubleshooting 19 6 Replacing the Battery 20 7 Obtaining Service 23 8 Specifications 24 9 Configurable Parameters Settings 26 10 Limited Product W...

Страница 3: ...ouble free service Please read this manual before installing your Enterprise Plus Series UPS models E750RTXL2U E1000RTXL2U E1500RTXL2U E1500RTXLT2U E2000RTXL2U E3000RTXL2U E3000RTXLT2U as it provides...

Страница 4: ...esidential installation This equip ment generates and uses radio frequency and if not installed and used properly that is in strict accordance with the manufacturer s instructions this equip ment may...

Страница 5: ...l be illuminated and the UPS will sound a constant alarm to indicate that there is an Overload condi tion The Battery Capacity Bar Graph operates as follows LED 1 When the battery capacity is 20 the L...

Страница 6: ...ction Labeled Load 1 Load 2 The locking and Always On receptacles Labeled Load 3 do not support the Load Shed ding Function NOTE The locking recptacle is not on all models 7 The input circuit breaker...

Страница 7: ...tteries is complete See Connecting your Equipment NOTE If you are using an External Battery Pack with this UPS series the UPS must be configured so that the UPS will report the correct estimated runti...

Страница 8: ...e UPS On the backside of the front panel push the LCD panel out wards the panel will pop out Position the LCD panel so that it reads in the up right position Re install the front panel on the UPS 8 Th...

Страница 9: ...e T network single line phone Fax or Modem line to the RJ11 45 modular connectors on the rear panel of the UPS This connection will require another length of telephone or network cable The cable comin...

Страница 10: ...ad 1 Load 2 The user can control the two segments individually or both at the same time The Load Shedding Function is controllable by the Power Monitoring Software or the SNMP card NOTE The output seg...

Страница 11: ...ps after UPS restarts reduce the load on the UPS UPS operates in battery mode only even though there isAC present The AC normal icon is illumi nated but there is no output Disconnect the computer cabl...

Страница 12: ...e impact on battery life NOTE If there is a power interruption while replacing the hot swappable batteries with the UPS on the load will not be backed up BATTERY REPLACEMENT PROCEDURE PLEASE READ THE...

Страница 13: ...and address B Where and when the unit was purchased C All of the model information about your UPS D Any information on the failure including LEDs that may be illuminated E Adescription of the protect...

Страница 14: ...arge cycles and ambient temp BM0029 BM0030 8 hours to 90 after full load discharge BM0031 Battery Type Sealed Non Spillable Maintenance Free Value Regulated LeadAcid System Voltage Runtime Full Load m...

Страница 15: ...ems products that are depot repaired or replaced pursuant to this warranty shall only be warranted for the unex pired portion of the warranty applying to the original product This warranty applies onl...

Страница 16: ...UPS Model No E750RTXL2U Y E1000RTXL2U Y E1500RTXL2U Y E2000RTXL2U Y E3000RTXL2U Y E1500RTXLT2U Y E3000RTXLT2U Y I hereby declare that the equipment specified above conforms to the above Directive s P...

Отзывы: