INSTRUCTION MANUAL 

VeriSafe AVT 

 

B21075_00 

 

 

 

 

Page: 2 of 20 

 

 

 

 

 

04-2018

 

Safety Information 

 

This manual contains information and warnings which must be followed to ensure safe operation of the AVT. If the AVT is not used 
as described in this manual, the safety features of the AVT might be impaired. 

Failure to comply with the warnings and information 

in this manual could result in product failure, electrical shock, severe injury or death. 

   

Warning:       

      

 

• 

Always de-energize power before accessing an electrical enclosure.

 

• 

Always follow safety and lockout/tagout procedures when working on or near electrical systems and equipment.

 

• 

Use of the AVT does not replace lockout/tagout procedures. The AVT is intended to be used in conjunction with lockout/tagout processes 

and only addresses the absence of voltage verification step. 

 

• 

Use proper

 

personal protective equipment (PPE) when working around sources of hazardous electrical energy.

 

• 

Do not use this product outside of the specified performance and environmental limits.

 

• 

This product must be installed by a qualified electrical worker familiar with local and national electrical codes.

 

• 

The AVT will only test for absence of voltage at the point in the circuit where it is installed. If there are other sources of power in the 

equipment, dangerous voltage may be present. 

 

• 

Absence of voltage is indicated by illumination of the green Absence of Voltage Indicator. Absence of voltage is not guaranteed when 

the red Voltage Presence Indicators are not illuminated.

 

• 

The AVT must be installed correctly and grounded as described in this Instruction Manual to provide proper indication of absence of 

voltage. Sensor leads must not be mechanically connected with each other for the device to verify connection to the circuit. Correct 

function of the device must be verified after installation (see commissioning checklist).

 

• 

Sensor leads of the same color should be terminated on the same conductor.  Each conductor should have at least one sensor lead set, 

as shown on the schematic diagrams.  

• 

Excess length from Sensor Leads should be trimmed; Sensor Leads should not be extended with a splice. 

 

• 

Always comply with local installation codes and standards.  

 

• 

The AVT will not work with a standard alkaline 1.5Volt AA battery. Use only lithium, 3.6 Volt, Size AA approved batteries listed in table 

1 of the Maintenance section of this instruction manual.

 

• 

The product uses a lithium battery that is a fire, explosion and severe burn hazard. Do not crush, recharge, disassemble or heat 

above 85

°

 C, incinerate, or expose contents to water.  

• 

Use only the included AVT System Cable or approved replacement cables to connect the Isolation Module and Indicator Module. Do not 

use a standard Ethernet cable. 

• 

Battery, AVT System Cable and O-rings can be replaced. No other part of the product is serviceable. Do not attempt to open the Indicator 

Module or Isolation Module for repair or modification. When servicing this product, only use specified replacement parts.

 

• 

The section of the Indicator  Module  that is external to the electrical enclosure is approved for wash down  when  installed in an 

appropriate enclosure. Before a wash down operation, ensure the o-rings are in good condition, the faceplate is undamaged and fully 

secured to the unit and the cap is fully installed. 

• 

The AVT System Cable must be separated from the sensor leads and other circuits in the electrical enclosure by a minimum of 0.25 inches 

(6 mm). 

• 

To prevent damage to the AVT in high-vibration installations, surface mount the Isolation Module using screws and secure the Sensor 

Lead Wires and AVT System Cable to prevent strain on the connection points. 

• 

If a Sensor  Lead separates from the termination point to the power conductor and  contacts a low impedance path to ground, the 

connectivity test can be defeated resulting in a false absence of voltage indication.  Ensure that all sensor leads are terminated properly 

and secured to the power conductor or other nearby rigid feature to prevent movement if the termination fails to remain intact. 

• 

Devices must be installed in an enclosure where the internal compartment is only accessible by the use of a tool or other mechanical 

means. 

• 

EXPLOSION HAZARD - Do not replace the battery inside of the indicator module unless area is known to be non-hazardous. 

• 

EXPLOSION HAZARD – Do not disconnect equipment unless power has been removed or the area is known to be non-hazardous. 

 

Should a problem occur during installation, operation or maintenance of the VeriSafe AVT, contact Panduit using one of the technical 

support or customer service numbers listed on the cover of this manual.  Contact Panduit if you have any product problems related to the 

safety function of the product.  The product model number and serial number are printed on the Isolation Module and Indicator Module 

labels. 

 

  VeriSafe is a product containing electronic circuit boards in both the Indicator and Isolation Modules. The Indicator Module 

contains a lithium battery. When decommissioning, remove the battery. Do not discard the battery in the trash; take it to an 
appropriate battery recycling facility. The Indicator and Isolation Modules can be disposed of at an electronics recycling facility.

 

 

Содержание VeriSafe AVT

Страница 1: ...version of this manual Email techsupport panduit com EU Website www panduit com emea EU Email emeatoolservicecenter panduit com www panduit com Technical Support Tel 1 866 405 6654 Panduit Europe EMEA...

Страница 2: ...ts 4 Output Contacts 4 Technical Specifications 5 Dimensions 7 Schematics 8 Installation Considerations 11 Installation Instructions 13 Commissioning Checklist 15 Operating Instructions 16 Troubleshoo...

Страница 3: ...mble or heat above 85 C incinerate or expose contents to water Use only the included AVT System Cable or approved replacement cables to connect the Isolation Module and Indicator Module Do not use a s...

Страница 4: ...recharger d monter ou chauffer au dessus de 85 C incin rer ou exposer le contenu l eau Utilisez uniquement le c ble syst me AVT inclus ou les c bles de remplacement approuv s pour connecter le module...

Страница 5: ...solation Module The outputs are normally open and close only when the green Absence of Voltage Indicator is illuminated By wiring to these contacts the AVT can be used as an input to a control system...

Страница 6: ...ements for safety related systems and for equipment intended to perform safety related functions functional safety General industrial applications including corrigendum 1 EN 55011 CISPR 11 Industrial...

Страница 7: ...tection specified is related to the Indicator Module only To meet the TYPE UL NEMA and CSA 1 12 4 4X 13 IP66 or IP67 requirements mount on a flat surface of an enclosure meeting the appropriate UL TYP...

Страница 8: ...4 2018 Dimensions Isolation Module Indicator Module Panel Knockout Units inches mm The Indicator Module is designed for use with a standard 30 mm knockout with notch The notch should be positioned on...

Страница 9: ...y or death Sensor leads of the same color should be terminated on the same conductor Each conductor should have at least one sensor lead set as shown on the schematic diagrams If a Sensor Lead separat...

Страница 10: ...MANUAL VeriSafe AVT B21075_00 Page 9 of 20 04 2018 Single Phase 2 Wire PE Single Phase 2 Wire PE Redundant Detection Lead Single Phase 3 Wire PE Corner Grounded DELTA 3 Wire PE High Leg DELTA 3 Wire...

Страница 11: ...Panduit Corp 2018 INSTRUCTION MANUAL VeriSafe AVT B21075_00 Page 10 of 20 04 2018 DC System 2 Wire PE Redundant Detection Lead...

Страница 12: ...AVT is suitable for use on circuits delivering up to 300 000 rms symmetrical A at 600 V Use of Overcurrent Protection Installation of an AVT with overcurrent protection is neither required nor recomm...

Страница 13: ...d pass This would be a multi fault scenario but is possible if terminations are not made properly and secured An AVT installed on a single phase system might only have one Detection Lead terminated to...

Страница 14: ...terminated properly and secured to the power conductor or other nearby rigid feature to prevent movement if the termination fails to remain intact Devices must be installed in an enclosure where the i...

Страница 15: ...r leads with a splice Use approved connection methods and follow local codes and standards when terminating the sensor leads Secure the sensor leads to the conductors to prevent the leads from contact...

Страница 16: ...label Verify that the label is placed near the isolation module and marked to indicate where the AVT is installed Record changes to panel documentation Close panel and secure doors covers Press the T...

Страница 17: ...of voltage push the Test Button A B Absence of Voltage Test Each time the Test Button is engaged the absence of voltage test sequence will be activated The test sequence includes running a self check...

Страница 18: ...test 2 Voltage detected above the threshold Warning This indicates that the enclosure is energized Follow safety procedures and use the appropriate PPE when investigating the source of voltage If pan...

Страница 19: ...the area is known to be non hazardous Battery Replacement Follow these steps to replace the battery Table 1 provides a list of batteries approved for use with the AVT Do not discard the battery in th...

Страница 20: ...alkaline cleaners Do not leave cleaners on the device for a long period rinse immediately Do not apply cleaners in direct sunlight or elevated temperatures The section of the VeriSafe Indicator Module...