Panduit VeriSafe AVT Скачать руководство пользователя страница 17

© Panduit Corp. 2018 

INSTRUCTION MANUAL 

VeriSafe AVT 

 

B21075_00 

 

 

 

 

Page: 16 of 20   

 

 

 

 

04-2018

 

Operating Instructions 

 

Warning:

 

• 

To avoid electric shock, always de-energize power before entering an electrical enclosure.

 

• 

Always follow safety and lockout/tagout procedures when working on or near electrical systems and equipment.

 

• 

Use proper

 

personal protective equipment (PPE) when working around sources of hazardous electrical energy.

 

• 

Absence of voltage is indicated by illumination of the green Absence of Voltage Indicator. Absence of voltage is not 

guaranteed when the red Voltage Presence Indicators are not illuminated. 

 

The AVT should only be operated by individuals who have been trained on the operation of the tester and can demonstrate 

knowledge of the following criteria: 

 

Familiar with requirements and information in the Instruction Manual and understand the function of the AVT, 

meaning of the indicators and markings, and limitations of the Voltage Presence Indicators 

 

Aware of where the AVT is installed in the electrical system and any additional electrical hazards that may be 

present in the system that are not detectable by the AVT 

 

Able to recognize electrical hazards and familiar with lockout/tagout procedures 

 

 

Voltage Presence Indicators 

A.

 

When voltage is detected in one or more phases, the appropriate 

Voltage Presence Indicators will illuminate.

 

B.

 

Absence of voltage is not guaranteed when the Voltage 

Presence Indicators are not illuminated

. To test for absence of 

voltage, push the Test Button.

 

A. 

 

B. 

 

Absence of Voltage Test 

Each time the Test Button is engaged, the absence of voltage test sequence will be activated. The test 

sequence includes running a self-check, using a known voltage source to test the tester to verify that 

the AVT is functioning, testing for AC and DC voltage phase-to-phase and phase-to-ground, and 

verifying the sensor leads are in contact with the circuit conductors. 

 

1.

 

De-energize the circuit according to company safety procedures. 

2.

 

Verify that lockout/tagout devices have been applied to all applicable energy sources and the 

Voltage Presence indicators are not illuminated. 

3.

 

Press the Test Button to initiate the absence of voltage test.  

4.

 

The Caution Indicator will begin to flash. This indicates that the test is in progress. 

5.

 

When the absence of voltage is verified, the Absence of Voltage Indicator will illuminate.  

6.

 

If the absence of voltage is not verified, the Caution  Indicator will illuminate for about five 

seconds followed by a series of flashes. The number of flashes will help diagnose why the test 

failed. Refer to the Troubleshooting section for additional information. 

  3. 

 

  5. 

 

6. 

 

Test Button:

 Initiates test 

Absence of Voltage Indicator

: Illuminates 

green

 

when the Absence of 

Voltage is verified 

Caution Indicator

: Flashes 

yellow

 

rapidly to indicate test in process, 

illuminates solid to indicate the test has failed and flashes after a solid 

illumination to indicate the reason for failure 

Voltage Presence

 

Indicators

: Three 

red

 

indicators illuminate when the 

presence of hazardous AC voltage is detected. 

Absence of voltage is not 

guaranteed when the Voltage Presence Indicators are not illuminated.  

Содержание VeriSafe AVT

Страница 1: ...version of this manual Email techsupport panduit com EU Website www panduit com emea EU Email emeatoolservicecenter panduit com www panduit com Technical Support Tel 1 866 405 6654 Panduit Europe EMEA...

Страница 2: ...ts 4 Output Contacts 4 Technical Specifications 5 Dimensions 7 Schematics 8 Installation Considerations 11 Installation Instructions 13 Commissioning Checklist 15 Operating Instructions 16 Troubleshoo...

Страница 3: ...mble or heat above 85 C incinerate or expose contents to water Use only the included AVT System Cable or approved replacement cables to connect the Isolation Module and Indicator Module Do not use a s...

Страница 4: ...recharger d monter ou chauffer au dessus de 85 C incin rer ou exposer le contenu l eau Utilisez uniquement le c ble syst me AVT inclus ou les c bles de remplacement approuv s pour connecter le module...

Страница 5: ...solation Module The outputs are normally open and close only when the green Absence of Voltage Indicator is illuminated By wiring to these contacts the AVT can be used as an input to a control system...

Страница 6: ...ements for safety related systems and for equipment intended to perform safety related functions functional safety General industrial applications including corrigendum 1 EN 55011 CISPR 11 Industrial...

Страница 7: ...tection specified is related to the Indicator Module only To meet the TYPE UL NEMA and CSA 1 12 4 4X 13 IP66 or IP67 requirements mount on a flat surface of an enclosure meeting the appropriate UL TYP...

Страница 8: ...4 2018 Dimensions Isolation Module Indicator Module Panel Knockout Units inches mm The Indicator Module is designed for use with a standard 30 mm knockout with notch The notch should be positioned on...

Страница 9: ...y or death Sensor leads of the same color should be terminated on the same conductor Each conductor should have at least one sensor lead set as shown on the schematic diagrams If a Sensor Lead separat...

Страница 10: ...MANUAL VeriSafe AVT B21075_00 Page 9 of 20 04 2018 Single Phase 2 Wire PE Single Phase 2 Wire PE Redundant Detection Lead Single Phase 3 Wire PE Corner Grounded DELTA 3 Wire PE High Leg DELTA 3 Wire...

Страница 11: ...Panduit Corp 2018 INSTRUCTION MANUAL VeriSafe AVT B21075_00 Page 10 of 20 04 2018 DC System 2 Wire PE Redundant Detection Lead...

Страница 12: ...AVT is suitable for use on circuits delivering up to 300 000 rms symmetrical A at 600 V Use of Overcurrent Protection Installation of an AVT with overcurrent protection is neither required nor recomm...

Страница 13: ...d pass This would be a multi fault scenario but is possible if terminations are not made properly and secured An AVT installed on a single phase system might only have one Detection Lead terminated to...

Страница 14: ...terminated properly and secured to the power conductor or other nearby rigid feature to prevent movement if the termination fails to remain intact Devices must be installed in an enclosure where the i...

Страница 15: ...r leads with a splice Use approved connection methods and follow local codes and standards when terminating the sensor leads Secure the sensor leads to the conductors to prevent the leads from contact...

Страница 16: ...label Verify that the label is placed near the isolation module and marked to indicate where the AVT is installed Record changes to panel documentation Close panel and secure doors covers Press the T...

Страница 17: ...of voltage push the Test Button A B Absence of Voltage Test Each time the Test Button is engaged the absence of voltage test sequence will be activated The test sequence includes running a self check...

Страница 18: ...test 2 Voltage detected above the threshold Warning This indicates that the enclosure is energized Follow safety procedures and use the appropriate PPE when investigating the source of voltage If pan...

Страница 19: ...the area is known to be non hazardous Battery Replacement Follow these steps to replace the battery Table 1 provides a list of batteries approved for use with the AVT Do not discard the battery in th...

Страница 20: ...alkaline cleaners Do not leave cleaners on the device for a long period rinse immediately Do not apply cleaners in direct sunlight or elevated temperatures The section of the VeriSafe Indicator Module...

Страница 21: ...t to Buyer whichever is longer 4 No Warranty for Third Party Products Panduit makes no representations and disclaims all warranties of any kind express or implied relative to any third party product o...