SMARTZONE G6 IRUPS USER MANUAL
52
Section 5
– Replacing Battery Cartridges
Internal Battery Cartridges in the 1-3kVA UPS Units (UVC024,
UVC036, UVC048, UVC072)
Replace battery cartridges with only the same SKU. It is recommended to replace all
battery cartridges in a system at the same time with new battery cartridges of the same
SKU for that unit (UPS and EBP).
1. Change to Bypass Mode, this will not allow the UPS to transition to Battery Mode will
the battery cartridges are being replaced.
2. Remove the faceplate:
142.
Press both sides of UPS faceplate until the latches release (see Figure 61).
Figure 61: Press the Latches to Remove Faceplate
143.
Remove the faceplate (see Figure 62).
Figure 62: Remove the Faceplate