28
DC current measurement
Note:
Always measure current on one conductor only.
Covering more than one conductor results in measuring differential
current (like identifying leakage current). To avoid measuring errors
related to other hot conductors, please observe maximum
phase-to-phase clearance.
Due to various factors (e.g.: Earth magnetic field), the device can display a
random value. Changes in the position of the instrument change this
value. Press SEL to set the display to zero. The symbol "Z" appears in the
display. (Zero)
1.
Switch the unit on with the main switch (1).
2.
Press the lever to open the induction jaw.
3.
Place the wire in the center of the pliers opening as far as possible and
close the measuring pliers again.
4.
Once the reading stabilizes, read the value. If the polarity is reversed a
"Minus sign" is displayed.
AC Current measurement
1.
Switch the unit on with the main switch (1).
2.
Press the lever to open the induction jaw.
3.
Place the wire in the center of the pliers opening as far as possible and
close the measuring pliers again.
4.
Once the reading stabilizes, read the value.
5.
If the current level is > 0,2 A, the current is displayed.
Voltage measurement
1.
Switch the unit on with the main switch (1).
2.
Attach the pin-plug of the black test lead to the COM-jack and the
pin-plug of the red test lead to the multi-function jack.
3.
Touch the measuring points with the probe tips.
Содержание PAN 100AD+