Connection cable
Power supply cord
Terminal Board
Control
Board
Recommended
length (mm)
Earth Wire
longer than
others
AC wires
for safety
reason
Holder
Holder
Indoor & outdoor
connection cable
Power supply
cord
Outdoor unit
Isolating Devices
Tape
Tape
•
How to pull the piping and drain hose out, in case of the
embedded piping.
•
In case of left piping how to insert the
connection cable and drain hose.
The mounting wall shall be strong and solid enough to prevent it from vibration.
The power supply cord, indoor and outdoor unit connection cable can be connected without removing the front grille.
1
Install the indoor unit on the installing holder that mounted on the wall.
2
Open the front panel and grille door by loosening the screw.
3
Cable connection to the power supply through Isolating Devices (Disconnecting means).
•
Connect the approved polychloroprene sheathed
power supply cord
3 x 1.5 mm
2
(3/4 ~ 1.75HP) or 3 x 2.5 mm
2
(2.0HP), type designation
60245 IEC 57 or heavier cord to the terminal board, and connect the other end of the cable to Isolating Devices (Disconnecting means).
•
Do not use joint power supply cord. Replace the wire if the existing wire (from concealed wiring, or otherwise) is too short.
•
In unavoidable case, joining of power supply cord between isolating devices and terminal board of air conditioner shall be done by using
approved socket and plug rated 15/16A (3/4 ~ 1.75HP) or 16A (2.0HP). Wiring work to both socket and plug must follow to national wiring
standard.
4
Bind all the power supply cord lead wire with tape and route the power supply cord via the left escapement.
5
Connection cable
between indoor unit and outdoor unit shall be approved polychloroprene sheathed 4 x 1.5 mm
2
(3/4 ~ 1.75HP) or 4 x
2.5 mm
2
(2.0HP) fl exible cord, type designation 60245 IEC 57 or heavier cord.
6
Bind all the indoor and outdoor connection cable with tape and route the connection cable via the right escapement.
7
Remove the tapes and connect the power supply cord and connection cable between indoor unit and outdoor unit according to the diagram below.
Terminals on the outdoor unit
S1
2
3
Colour of wires (connection cable)
Terminals on the indoor unit
L
1
N
S1
2
3
(Power supply cord)
Terminals on the isolating devices
(Disconnecting means)
(L) (N)
Note:
•
Isolating Devices (Disconnecting means) should have minimum 3.0 mm
contact gap.
•
Ensure the colour of wires of outdoor unit and the terminal Nos. are the
same to the indoor’s respectively.
•
Earth wire shall be Yellow/Green (Y/G) in colour and longer than other
AC wires as shown in the fi gure for the electrical safety in case of the
slipping out of the cord from the anchorage.
Cover for the
bottom piping
Cover for the
bottom piping
Tape it with piping in a
position as mentioned
in Fig. below.
Cover for
the right
piping
Piping
Drain
hose
Cover for
the left
piping
Install the indoor unit
Hook the indoor unit onto the
upper portion of installation
plate. (Engage the indoor unit
with the upper edge of the
installation plate). Ensure the
hooks are properly seated
on the installation plate by
moving it in left and right.
Secure the Indoor Unit
Press the lower left and right
side of the unit against the
installation plate until hooks
engages with their slot (sound
click).
Rear view for left piping installation
Drain cap
Drain hose
Adjust the piping slightly
downwards.
Drain hose
Connection cable
PVC tube
for drain
hose
Indoor unit
100 mm
Piping
Cable
Apply putty or
caulking material
to seal the wall
opening.
Connection cable
Piping
More than
470 mm
More than
950 mm
PVC tube (VP-65) for piping
and connection cable
PVC tube for drain hose (VP-30)
PVC tube for drain
hose (VP-20)
More than 700 mm
Drain hose
from main unit
HOW TO TAKE OUT FRONT GRILLE
Please follow the steps below to take out front grille if necessary
such as when servicing.
1.
Set the vertical airfl ow direction louvers to the horizontal
position.
2.
Remove the 2 caps on the front grille as shown in the
illustration at right, and then remove the 3 mounting screws.
3.
Pull the lower section of the front grille towards you to
remove the front grille.
When reinstalling the front grille, carry
out above step 2 - 3 in the reverse order.
AUTO SWITCH OPERATION
The below operations will be performed by pressing the “AUTO” switch.
1.
AUTO OPERATION MODE
The Auto operation will be activated immediately once the Auto Switch is pressed and release before 5 sec..
2.
TEST RUN OPERATION (FOR PUMP DOWN/SERVICING PURPOSE)
The Test Run operation will be activated if the Auto Switch is pressed continuously for more than 5 sec. to
below 8 sec..
A “pep” sound will occur at the fi fth sec., in order to identify the starting of Test Run operation.
3.
HEATING TRIAL OPERATION
Press the “AUTO” switch continuously for more than 8 sec. to below 11 sec. and release when a “pep pep”
sound is occured at eight sec. (However, a “pep” sound is occurred at fi fth sec..) Then press Remote controller
“A/C Reset” button once.
Remote controller signal will activate operation to force heating mode.
4.
REMOTE CONTROLLER RECEIVING SOUND ON/OFF
The ON/OFF of Remote controller receiving sound can be change over by the following steps:
a) Press “AUTO” switch continuously for more than 16 sec. to below 21 sec..
A “pep”, “pep”, “pep”, “pep” sound will occur at the sixteenth sec..
b) Press the “A/C Reset” button once. Remote controller signal will activate the Remote controller sound setting
mode.
c) Press the “AUTO” switch once to select Remote controller receiving sound ON/OFF. A “peep” sound indicates
receiving sound ON, and a “pep” sound indicates receiving sound OFF.
5.
HEATING ONLY OPERATION
Press the “AUTO” switch continuously for more than 8 sec. to below 11 sec. And release when a “pep pep” sound
is occurred at eighth sec. (However, a “pep” sound is occurred at fi fth sec.) Then press Remote controller “Check”
button once. Remote controller signal will activate heating only operation mode.
DISPOSAL OF OUTDOOR UNIT DRAIN WATER
•
If a drain elbow is used, the unit should be placed on a stand which is taller than 3 cm.
•
If the unit is used in an area where temperature falls below 0°C for 2 or 3 days in
succession, it is recommended not to use a drain elbow, for the drain water freezes
and the fan will not rotate.
ECO SENSOR
•
Do not hit or violently press the sensor.
This can lead to damage and malfunction.
•
Do not place large objects near the sensor and keep heating units or humidifi ers away
from the sensors detection area.
This may lead to sensor malfunction.
WARNING
This equipment must be
properly earthed.
Recommended
length (mm)
a
b
c
d
e
f
g
55 35 35 50 40 35 60
1. FOR THE RIGHT REAR PIPING
Step-1
Pull out the Indoor piping
Step-2
Install the Indoor Unit
Step-3
Secure the Indoor Unit
Step-4
Insert the power supply cord and
connection cable
•
Insert the cables from bottom of the
unit through the control board hole until
terminal board area.
2. FOR THE RIGHT AND RIGHT
BOTTOM PIPING
Step-1
Pull out the Indoor piping
Step-2
Install the Indoor Unit
Step-3
Insert the power supply cord and
connection cable
•
Insert the cables from bottom of the
unit through the control board hole until
terminal board area.
Step-4
Secure the Indoor Unit
3. FOR THE EMBEDDED PIPING
Step-1
Replace the drain hose
Step-2
Bend the embedded piping
•
Use a spring bender or equivalent to bend
the piping so that the piping is not crushed.
Step-3
Pull the connection cable into Indoor
Unit
•
The power supply cord and indoor unit
and outdoor unit connection cable can be
connected without removing the front grille.
Step-4
Cut and fl are the embedded piping
•
When determining the dimensions of the
piping, slide the unit all the way to the left
on the installation plate.
•
Refer to the section “Cutting and fl aring
the piping”.
Step-5
Install the Indoor Unit
Step-6
Connect the piping
•
Please refer to “Connecting the piping”
column in outdoor unit section. (Below
steps are done after connecting
the outdoor piping and gas-leakage
confi rmation.)
Step-7
Insulate and fi nish the piping
•
Please refer to “Insulation of piping
connection” column as mentioned in
indoor/outdoor unit installation.
Step-8
Secure the Indoor Unit
Right Rear piping
Cover for
the bottom
piping
Tape it with piping in a
position as mentioned
in Fig. below.
Cover for
the right
piping
Piping
Drain hose
Cover for
the left
piping
Right and Right Bottom piping
(This can be used for left rear piping and bottom piping also.)
CHECK ITEMS
Drain hose
Sleeve for piping hole
Indoor unit
Hooks at installation
plate
Piping
marking
Installation
plate
Unit’s hook
Cable
45°
Drain
hose
Piping
Sleeve for piping hole
Drain hose
Piping
Connection cable
More than 950 mm
•
Do not turn over the unit without it’s shock absorber during pull out the piping.
It may cause intake grille damage.
•
Use shock absorber during pull out the piping to protect the intake grille from damage.
Piping
Intake grille
Shock absorber
Piping
pull ou
t th
e p
ipin
g
pull o
ut t
he
p
ip
in
g
•
After selecting the best location, start installation to Indoor/Outdoor Unit Installation Diagram.
1.
Fix the unit on concrete or rigid frame fi rmly and horizontally by bolt nut (ø10 mm).
2.
When installing at roof, please consider strong wind and earthquake.
Please fasten the installation stand fi rmly with bolt, screws or nails.
INDOOR UNIT
OUTDOOR UNIT
HOW TO FIX INSTALLATION PLATE
2
SELECT THE BEST LOCATION
(Refer to “Select the best location” section)
1
TO DRILL A HOLE IN THE WALL AND INSTALL A SLEEVE OF PIPING
3
The center of installation plate should be at more than
1
at right and left of the wall.
The distance from installation plate edge to ceiling should more than
2
.
From installation plate center to unit’s left side is
3
.
From installation plate center to unit’s right side is
4
.
b
: For left side piping, piping connection for liquid should be about
5
from this line.
: For left side piping, piping connection for gas should be about
6
from this line.
1.
Mount the installation plate on the wall with 5 screws or more (at least 5 screws).
(If mounting the unit on the concrete wall, consider using anchor bolts.)
•
Always mount the installation plate horizontally by aligning the marking-off line with the thread and using a level gauge.
2.
Drill the piping plate hole with ø70 mm hole-core drill.
•
Line according to the left and right side of the installation plate.
The meeting point of the extended line is the center of the hole.
Another method is by putting measuring tape at position as shown in the diagram above.
The hole center is obtained by measuring the distance namely 128 mm for left and right hole respectively.
•
Drill the piping hole at either the right or the left and the hole should be slightly slanting to the outdoor side.
1.
Insert the piping sleeve to the hole.
2.
Fix the bushing to the sleeve.
3.
Cut the sleeve until it extrudes about 15 mm from the wall.
CAUTION
When the wall is hollow, please be sure to use
the sleeve for tube assembly to prevent dangers
caused by mice biting the connection cable.
4.
Finish by sealing the sleeve with putty or caulking
compound at the fi nal stage.
15 mm
Putty or caulking compound
ø70 mm through hole
Indoor
Outdoor
Sleeve for tube
assembly
Approx. 5 - 7 mm
Bushing for tube
assembly
Wall
CONNECT THE CABLE TO THE INDOOR UNIT
5
Cover for piping
How to keep the cover
In case of the cover is cut, keep
the cover at the rear of chassis as
shown in the illustration for future
reinstallation.
(Left, right and 2 bottom covers for
piping.)
To take out the unit, push
the
marking at the
bottom unit, and pull it
slightly towards you to
disengage the hooks
from the unit.
(For the right piping, follow the same procedure)
Is there any gas leakage at fl are nut connections?
Has the heat insulation been carried out at fl are nut
connection?
Is the connection cable being fi xed to terminal board
fi rmly?
Is the connection cable being clamped fi rmly?
Is the drainage ok?
(Refer to “Check the drainage” section)
Is the earth wire connection properly done?
Is the indoor unit properly hooked to the installation
plate?
Is the power supply voltage complied with rated value?
Is there any abnormal sound?
Is the cooling/heating operation normal?
Is the thermostat operation normal?
Is the remote control’s LCD operation normal?
SELECT THE BEST LOCATION
(Refer to “Select the best location” section)
1
INSTALL THE OUTDOOR UNIT
EVACUATION OF THE EQUIPMENT
PIPING INSULATION
2
4
6
CONNECT THE CABLE TO THE OUTDOOR UNIT
5
INDOOR UNIT INSTALLATION
4
Model
Dimension
1
2
3
4
5
6
Z7***, XZ7***, Z9***, XZ9***
Z12***, XZ12***, Z15***
Z18***, XZ18***
515 mm
82 mm
460 mm
460 mm
43 mm
95 mm
1.
Please cut using pipe cutter and then remove the burrs.
2.
Remove the burrs by using reamer. If burrs is not removed, gas leakage may be caused.
Turn the piping end down to avoid the metal powder entering the pipe.
3.
Please make fl are after inserting the fl are nut onto the copper pipes.
When properly fl ared, the internal surface of the
fl are will evenly shine and be of even thickness.
Since the fl are part comes into contact with the
connections, carefully check the fl are fi nish.
Improper fl aring
Inclined Surface
damaged
Cracked Uneven
thickness
CUTTING AND FLARING THE PIPING
1. To cut
2. To remove burrs
3. To fl are
Bar
Red arrow mark
Handle
Core
Yoke
Clamp handle
Bar
0 – 0.5 mm
Copper pipe
Reamer
Point down
Pipe
Guide
surface
Connection cable
About
70 – 80 mm
Connection cable
Gas side piping
Liquid side piping
Drain hose
Insert the connection cable
1.
Please carry out insulation at pipe connection portion as mentioned in Indoor/Outdoor Unit Installation Diagram. Please wrap the
insulated piping end to prevent water from going inside the piping.
2.
If drain hose or connecting piping is in the room (where dew may form), please increase the insulation by using POLY-E FOAM with
thickness 6 mm or above.
WHEN INSTALLING AN AIR CONDITIONER, BE SURE TO EVACUATE THE AIR INSIDE THE INDOOR UNIT AND PIPES in the
following procedure.
Do not purge the air with refrigerants but use a vacuum pump to vacuum the installation.
There is no extra refrigerant in the outdoor unit for air purging.
1.
Connect a charging hose with a push pin to the Low side
of a charging set and the service port of the 3-way valve.
•
Be sure to connect the end of the charging hose with
the push pin to the service port.
2.
Connect the center hose of the charging set to a
vacuum pump.
3.
Turn on the power switch of the vacuum pump and
make sure that the needle in the gauge moves from
0 cmHg (0 MPa) to –76 cmHg (–0.1 MPa). Then
evacuate the air approximately ten minutes.
4.
Close the Low side valve of the charging set and turn
off the vacuum pump. Make sure that the needle in the
gauge does not move after approximately fi ve minutes.
Note : BE SURE TO TAKE THIS PROCEDURE IN
ORDER TO AVOID REFRIGERANT GAS
LEAKAGE.
5.
Disconnect the charging hose from the vacuum pump
and from the service port of the 3-way valve.
6.
Tighten the service port caps of the 3-way valve at a torque of 18 N•m with a torque wrench.
7.
Remove the valve caps of both of the 2-way valve and 3-way valve. Position both of the valves to “OPEN” using a hexagonal
wrench (4 mm).
8.
Mount valve caps onto the 2-way valve and the 3-way valve.
•
Be sure to check whole system for gas leakage.
•
If gauge needle does not move from 0 cmHg (0 MPa) to –76 cmHg (–0.1 MPa), in step
3
above take the following measure:
- If the leak stops when the piping connections are tightened further, continue working from step
3
.
- If the leak does not stop when the connections are retightened, repair location of leak.
- Do not release refrigerant during piping work for installation and reinstallation.
- Take care of the liquid refrigerant, it may cause frostbite.
OPEN
CLOSE
Gas side
Liquid side
Outdoor unit
Two-way valve
Three-way valve
Indoor unit
Vacuum
pump
Close
Close
2/2
WARNING
This equipment must be properly earthed.
•
Earth wire shall be Yellow/Green (Y/G) in
colour and longer than other AC wires for
safety reason.
ENGLISH
ACXF60-01930-AB
PRINTED IN MALAYSIA
Model
A
B
C
D
Z7***, XZ7***
570 mm
105 mm
18.5 mm
320 mm
Z9***, XZ9***
Z12***, XZ12***
540 mm
160 mm
18.5 mm
330 mm
Z15***
Z18***, XZ18***
613 mm
131 mm
16 mm
360.5 mm
A
B
C
D
1.
Remove the control board cover from the unit by loosening the screw.
2.
Connection cable
between indoor unit and outdoor unit shall be
approved polychloroprene sheathed 4 x 1.5 mm
2
(3/4 ~ 1.75HP) or 4 x
2.5 mm
2
(2.0HP) fl exible cord, type designation 60245 IEC 57 or heavier
cord. Do not use joint connection cable. Replace the wire if the existing
wire (from concealed wiring, or otherwise) is too short.
Terminals on the outdoor unit
S1
2
3
Colour of wires (connection cable)
Terminals on the indoor unit
L
1
N
S1
2
3
3.
Secure the cable onto the control board with the holder (clamper).
4.
Attach the control board cover back to the original position with screw.
5.
For wire stripping and connection requirement, refer to instruction
5
of
indoor unit.
AIR PURGING METHOD IS PROHIBITED FOR R32 SYSTEM
WARNING
RISK OF FIRE
JOINING OF
WIRES MAY
CAUSE
OVERHEATING
AND FIRE.
Do not joint wires
OR
OR
Use complete wire without joining.
Use approved socket and plug with earth pin.
Wire connection in this area must follow to national
wiring rules.
WIRE STRIPPING, CONNECTING
REQUIREMENT
Wire stripping
No loose strand
when inserted
10 ± 1 mm
5 mm or more
Indoor/outdoor
connection
terminal board
(gap between wires)
Conductor
fully inserted
Conductor over
inserted
Conductor not
fully inserted
ACCEPT
PROHIBITED
PROHIBITED
3
4
B
A
C
Wall
Wall
Wall
Installation plate
1
2
screw
More than
1
More than
1
Measuring
Tape
Indoor unit
266 mm
128 mm
266 mm
128 mm
More than
2
For best strength of
INDOOR unit installation,
it is highly recommended
to locate “ ” at 5 position
as shown.
PIPE
HOLE
CENTER
PIPE
HOLE
CENTER
128mm TO
PIPE HOLE
CENTER
128mm TO
PIPE HOLE
CENTER
Hose
Install the hose at an angle so that the
water smoothly fl ows out.
Drain elbow
7
CHECK THE DRAINAGE
•
Open front panel and remove air fi lters.
(Drainage checking can be carried out without removing the front grille.)
•
Pour a glass of water into the drain tray-styrofoam.
•
Ensure that water fl ows out from drain hose of the indoor unit.
Drain tray-styrofoam
EVALUATION OF THE PERFORMANCE
•
Operate the unit at cooling/heating operation mode for fi fteen minutes or more.
•
Measure the temperature of the intake and discharge air.
•
Ensure the difference between the intake temperature and the discharge is more
than 8°C during Cooling operation or more than 14°C during Heating operation.
Discharge air
8
Secure the power supply cord and connection cable onto
the control board with the holder.
9
Close grille door by tighten with screw and close the
front panel.
Holder
Indoor unit
Indoor & outdoor
connection cable
Earth wire
longer than
others
AC wires
for safety
reason
Terminal Board
Exchange the drain hose and
the cap
CONNECT THE PIPING
3
Connecting The Piping to Indoor
For connection joint location at outside building
Please make flare after inserting flare nut (locate at joint
portion of tube assembly) onto the copper pipe. (In case of
using long piping)
Connect the piping
•
Align the center of piping and suffi ciently tighten the fl are
nut with fi ngers.
•
Further tighten the fl are nut with torque wrench in specifi ed
torque as stated in the table.
Torque
wrench
Spanner or
Wrench
For connection joint location at inside building
•
Decide the length.
•
Cut and remove the tube connectors at indoor copper pipings
(both gas and liquid piping) by using pipe cutter. Remove burrs
from cut edge.
•
Use pipe expander to expand the end of long piping.
•
Align the center of piping and braze the piping joints.
Indoor
copper pipe
Tube connector
(40~50mm)
Brazing point
1. Cut and
Remove
2. Expand long
pipe
3. Braze both
pipe
Connecting The Piping to Outdoor
Decide piping length and then cut by using pipe cutter.
Remove burrs from cut edge.
Make fl are after inserting the fl are nut (locate at valve)
onto the copper pipe. Align center of piping to valve and
then tighten with torque wrench to the specifi ed torque as
stated in the table.
ECO SENSOR
Do not overtighten, overtightening may cause gas leakage.
Piping size
Torque
6.35 mm (1/4")
[18 N•m (1.8 kgf•m)]
9.52 mm (3/8")
[42 N•m (4.3 kgf•m)]
12.7 mm (1/2")
[55 N•m (5.6 kgf•m)]
15.88 mm (5/8")
[65 N•m (6.6 kgf•m)]
19.05 mm (3/4")
[100 N•m (10.2 kgf•m)]
Vane
(Move the vane
to downward)
Screw
Front
grille
Cap