11.4. Sanitary water control
11.4.1.
Flow adjustment valve control
• There are 3 setting temperature for sanitary water which are 45
q
C, 50
q
C and 55
q
C.
• The valve will open according to the temperature different between sanitary water setting temperature and Pump1 return water
temperature sensor. If the temperature different is less than 1
q
C, the valve will be closed.
11.4.2.
Delay control at hot water supply start time
• At the time of a hot water supply start, delay in starting the control of the flow adjust valve for the time is shown below:
11.4.3.
Tap water flow sensor control
• When flow sensor detects flow rate is more than 3.5L/min, the tap water supply is consider normal.
• When flow sensor detects flow rate is below 3.0 L /min, the tap water supply is consider low or close.
Содержание WH-TX30B9E8
Страница 7: ...7 4 Location of Controls and Components 4 1 Tank Unit 4 1 1 Location of Control ...
Страница 8: ...8 4 1 2 Main Components ...
Страница 9: ...9 5 Dimensions ...
Страница 10: ...10 6 Water Cycle Diagram ...
Страница 11: ...11 7 Wiring Connection Diagram ...
Страница 12: ...12 8 Electronic Circuit Diagram 8 1 Indoor Unit ...
Страница 13: ...13 9 Printed Circuit Board 9 1 Tank Unit 9 1 1 Main Printed Circuit Board ...
Страница 14: ...14 9 1 2 Surge Printed Circuit Board ...
Страница 47: ...47 15 2 Heater Removal Procedures ...
Страница 48: ...48 15 3 Main Printed Board Removal Procedures ...
Страница 49: ...49 15 4 Control Board Removal Procedure ...
Страница 50: ...50 15 5 Pressure Relief Valve Procedures ...
Страница 51: ...51 15 6 Flow Switch Removal Procedures 15 7 Water Pump Removal Procedures ...
Страница 52: ...52 16 Technical Data 16 1 Pump Characteristic 16 2 Water Tank Sensor Characteristic ...
Страница 53: ...53 ...
Страница 54: ...54 ...