16.4 Error Codes Table
Diagnosis display
Abnormality/Protection control
Abnormality judgement
Primary location to verify
H00
No abnormality detected
—
—
H12
Indoor/Outdoor capacity unmatched
90s after power supply
Indoor/outdoor connection wire
Indoor/outdoor PCB
Specification and combination table in
catalogue
H15
Outdoor compressor temperature sensor
abnormality
Continue for 5 sec.
Compressor temperature sensor
(defective or disconnected)
H23
Indoor refrigerant liquid temperature
sensor abnormality
Continue for 5 sec.
Refrigerant liquid temperature sensor
(defective or disconnected)
H42
Compressor low pressure abnormality
—
Outdoor pipe temperature sensor
Clogged expansion valve or strainer
Insufficient refrigerant
Outdoor PCB
Compressor
H62
Water flow switch abnormality
Continue for 1 min.
Water flow switch
H64
Refrigerant high pressure abnormality
Continue for 5 sec.
Outdoor high pressure sensor
(defective or disconnected)
H76
Indoor - control panel communication
abnormality
—
Indoor - control panel
(defective or disconnected)
H90
Indoor/outdoor abnormal communication
> 1 min after starting operation
Internal/external cable connections
Indoor/Outdoor PCB
H95 Indoor/Outdoor
wrong
connection
—
Indoor/Outdoor supply voltage
H98
Outdoor high pressure overload
protection
—
Outdoor high pressure sensor
Water pump or water leakage
Clogged expansion valve or strainer
Excess refrigerant
Outdoor PCB
H99
Indoor heat exchanger freeze prevention
—
Indoor heat exchanger
Refrigerant shortage
F12
Pressure switch activate
4 times occurrence within 20
minutes
Pressure switch
F14
Outdoor compressor abnormal revolution
4 times occurrence within 20
minutes
Outdoor compressor
F15
Outdoor fan motor lock abnormality
2 times occurrence within 30
minutes
Outdoor PCB
Outdoor fan motor
F16
Total running current protection
3 times occurrence within 20
minutes
Excess refrigerant
Outdoor PCB
F20
Outdoor compressor overheating
protection
4 times occurrence within 30
minutes
Compressor tank temperature sensor
Clogged expansion valve or strainer
Insufficient refrigerant
Outdoor PCB
Compressor
F22
IPM (power transistor) overheating
protection
4 times occurrence within 30
minutes
Improper heat exchange
IPM (Power transistor)
F23
Outdoor Direct Current (DC) peak
detection
7 times occurrence
continuously
Outdoor PCB
Compressor
F24
Refrigeration cycle abnormality
2 times occurrence within 20
minutes
Insufficient refrigerant
Outdoor PCB
Compressor low compression
F25 Cooling/Heating
cycle
changeover
abnormality
4 times occurrence within 30
minutes
4-way valve
V-coil
F27
Pressure switch abnormality
Continue for 1 min.
Pressure switch
F36
Outdoor air temperature sensor
abnormality
Continue for 5 sec.
Outdoor air temperature sensor
(defective or disconnected)
F37
Indoor water inlet temperature sensor
abnormality
Continue for 5 sec.
Water inlet temperature sensor
(defective or disconnected)
F40
Outdoor discharge pipe temperature
sensor abnormality
Continue for 5 sec.
Outdoor discharge pipe temperature
sensor (defective or disconnected)
F41
PFC control
4 times occurrence within 20
minutes
Voltage at PFC
F42
Outdoor heat exchanger temperature
sensor abnormality
Continue for 5 sec.
Outdoor heat exchanger temperature
sensor (defective or disconnected)
F43
Outdoor defrost sensor abnormality
Continue for 5 sec.
Outdoor defrost sensor (defective or
disconnected)
F45
Indoor water outlet temperature sensor
abnormality
Continue for 5 sec.
Water outlet temperature sensor
(defective or disconnected)
Содержание WH-SXH09D0E8
Страница 8: ...8 4 Location of Controls and Components 4 1 Indoor Unit 4 1 1 Location of Control ...
Страница 9: ...9 ...
Страница 10: ...10 ...
Страница 11: ...11 4 1 2 Weekly Timer Setting ...
Страница 12: ...12 4 1 3 Main Components 4 2 Outdoor Unit ...
Страница 13: ...13 5 Dimensions 5 1 Indoor Unit ...
Страница 14: ...14 5 2 Outdoor Unit ...
Страница 16: ...16 7 Block Diagram ...
Страница 17: ...17 8 Wiring Connection Diagram 8 1 Indoor Unit ...
Страница 18: ...18 8 2 Outdoor Unit ...
Страница 19: ...19 9 Electronic Circuit Diagram 9 1 Indoor Unit ...
Страница 20: ...20 9 2 Outdoor Unit ...
Страница 21: ...21 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board ...
Страница 22: ...22 10 2 Outdoor Unit 10 2 1 Main Printed Circuit Board ...
Страница 23: ...23 10 2 2 Noise Filter Printed Circuit Board ...
Страница 77: ...77 17 3 To Remove Pressure Gauge 17 4 To Remove Control Panel ...
Страница 78: ...78 17 5 To Remove RCCB 17 6 To Remove Transformer and Electronic Controller Board ...
Страница 80: ...80 When reinstall the water pipe use grease or water at the joining ...
Страница 86: ...86 19 2 Outdoor Unit ...
Страница 87: ...87 ...