34
12.5 Indoor Unit Safety
12.5.1 Indoor Unit Safety Control
1 When water pump is ON, the system will start checking flow switch status (ON/OFF).
2 If the flow switch ON for 10 seconds, the system will check on the water inlet temperature for 10 seconds.
If the water inlet temperature not exceeds 80°C, the water pump shall be continuously running with normal
mode. If the water inlet temperature exceeds 80°C for continuously 10 seconds, the water pump will be
OFF immediately.
3 After water pump OFF for more than 10 minutes, it will be ON back and the indoor unit safety control
checking is restarted.
12.6 Auto
Restart
Control
When the power supply is cut off during the operation of Air-to-Water Heatpump, the compressor will re-operate after
power supply resumes.
Содержание WH-SXH09D0E8
Страница 8: ...8 4 Location of Controls and Components 4 1 Indoor Unit 4 1 1 Location of Control ...
Страница 9: ...9 ...
Страница 10: ...10 ...
Страница 11: ...11 4 1 2 Weekly Timer Setting ...
Страница 12: ...12 4 1 3 Main Components 4 2 Outdoor Unit ...
Страница 13: ...13 5 Dimensions 5 1 Indoor Unit ...
Страница 14: ...14 5 2 Outdoor Unit ...
Страница 16: ...16 7 Block Diagram ...
Страница 17: ...17 8 Wiring Connection Diagram 8 1 Indoor Unit ...
Страница 18: ...18 8 2 Outdoor Unit ...
Страница 19: ...19 9 Electronic Circuit Diagram 9 1 Indoor Unit ...
Страница 20: ...20 9 2 Outdoor Unit ...
Страница 21: ...21 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board ...
Страница 22: ...22 10 2 Outdoor Unit 10 2 1 Main Printed Circuit Board ...
Страница 23: ...23 10 2 2 Noise Filter Printed Circuit Board ...
Страница 77: ...77 17 3 To Remove Pressure Gauge 17 4 To Remove Control Panel ...
Страница 78: ...78 17 5 To Remove RCCB 17 6 To Remove Transformer and Electronic Controller Board ...
Страница 80: ...80 When reinstall the water pipe use grease or water at the joining ...
Страница 86: ...86 19 2 Outdoor Unit ...
Страница 87: ...87 ...