16.5.22
Compressor Overheating (F20)
Malfunction Decision Conditions:
During operation of cooling and heating, when temperature above 112°C is detected by the compressor tank
temperature sensor.
Malfunction Caused:
1 Faulty compressor tank temperature sensor.
2 2/3 way valve closed.
3 Refrigerant shortage (refrigerant leakage).
4 Clogged expansion valve or strainer.
5 Faulty outdoor unit PCB (main).
6 Faulty
compressor.
Abnormality Judgment:
Continue 4 times in 30 minutes.