13.1.10. Crank case heater control
• Purpose:
- For compressor protection during low outdoor ambient operation (during heating low temperature operation).
• Control content:
a. Trigger heater START conditon
• when the outdoor air temperature is 13 C or below, and discharge temperature is 13.2 C or below.
b. Resetting heater STOP condition
1. when the outdoor air temperature exceeds entry condition (15 C)
2. when the discharge temperature exceeds entry condition (20.2 C)
13.2. Protection Control For Heating Operation
13.2.1. Outdoor Air Temperature Control
The maximum current value is regulated when the outdoor air temperature rises above 14 C in order to avoid compressor
overloading.
13.2.2. Deice Operation
When outdoor pipe temperature and outdoor air temperature is low, deice operation start where outdoor fan motor stop.
13.3. Protection Control For Cooling Operation
13.3.1. Outdoor Air Temperature Control
• The Compressor operating frequency is regulated in accordance to The outdoor air temperature as shown in The diagram below.
• This control will begin 1 minute after the compressor starts.
• Compressor frequency will adjust base on outdoor air Temperature.
13.3.2. Freeze Prevention Control 1
1. When indoor heat exchanger temperature is lower than 0°C continuously for 10 seconds, compressor will stop operating.
2. Compressor will resume its operation three minutes after the indoor heat exchanger is higher than 1°C.
3. Indoor heat exchanger freeze prevention (H99) will memory in error history.
Содержание WH-SXC09D3E5
Страница 10: ...10 4 Location of Controls and Components 4 1 Indoor Unit 4 1 1 Location of Control ...
Страница 11: ...11 ...
Страница 12: ...12 ...
Страница 13: ...13 4 1 2 Weekly Timer Setting ...
Страница 14: ...14 4 1 3 Setting Up The Special Functions ...
Страница 15: ...15 4 1 4 Main Components 4 2 Outdoor Unit ...
Страница 16: ...16 5 Dimensions 5 1 Indoor Unit ...
Страница 17: ...17 5 2 Outdoor Unit ...
Страница 19: ...19 ...
Страница 20: ...20 7 Block Diagram 7 1 WH UX09DE5 ...
Страница 21: ...21 7 2 WH UX12DE5 ...
Страница 22: ...22 8 Wiring Connection Diagram 8 1 Indoor Unit 8 1 1 WH SXC09D3E5 ...
Страница 23: ...23 8 1 2 WH SXC12D6E5 ...
Страница 24: ...24 8 2 Outdoor Unit ...
Страница 25: ...25 9 Electronic Circuit Diagram 9 1 Indoor Unit 9 1 1 WH SXC09D3E5 ...
Страница 26: ...26 9 1 2 WH SXC12D6E5 ...
Страница 27: ...27 9 2 Outdoor Unit ...
Страница 28: ...28 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board ...
Страница 29: ...29 10 1 2 Solar Printed Circuit Board Optional ...
Страница 30: ...30 10 2 Outdoor Unit 10 2 1 Main Printed Circuit Board ...
Страница 31: ...31 10 2 2 Capacitor Printed Circuit Board 10 2 3 Noise Filter Printed Circuit Board ...
Страница 45: ...45 Solar Priority is Set Solar Priority is Not Set ...
Страница 51: ...51 Heat Tank Mode Heating priority not set Under Solar Priority Not Set Condition ...
Страница 60: ...60 Solar Priority Not Set Heat Tank Mode Heating Priority Set ...
Страница 61: ...61 Tank Mode Solar Priority Set Solar Priority Not Set ...
Страница 109: ...109 17 3 To Remove Pressure Gauge 17 4 To Remove Control Panel ...
Страница 110: ...110 17 5 To Remove RCCB ELCB 17 6 To Remove Transformer and Electronic Controller Board ...
Страница 124: ...124 19 2 WH UX09DE5 WH UX12DE5 ...
Страница 125: ...125 ...