33
11.3. Indoor Unit
11.3.1. HOW TO FIX INSTALLATION PLATE
The mounting wall is strong and solid enough to prevent it from
vibration.
The centre of installation plate should be at more than 551 mm
at right and left of the wall.
The distance from installation plate edge to ground should
more than 1550 mm.
• Always mount the installation plate horizontally by aligning
the marking thread and using a level gauge.
• Mount the installation plate on the wall with 6 sets of plug,
bolt and washer (all non-supply) with size M8.
11.3.2. TO DRILL A HOLE IN THE WALL
AND INSTALL A SLEEVE OF
PIPING
1. Insert the piping sleeve to the hole.
2. Fix the bushing to the sleeve.
3. Cut the sleeve until it extrudes about 15 mm from the
wall.
4. Finish by sealing the sleeve with putty or caulking
compound at the final stage.
11.3.3. INDOOR UNIT INSTALLATION
11.3.3.1. Install The Indoor Unit
1. When connecting solar pump station cable between
indoor unit and solar pump station, the distance between
both apparatuses shall be 2 ~ 8 meters and the length of
the said cable must be shorter than 10 meter. Failure to
do so may lead to abnormal operation to the system.
2. Engage the slots on the indoor unit to the hooks of
installation plate . Ensure the hooks are properly seated
on the installation plate by moving it left and right.
3. Fix the screws to the holes on the hooks of installation
plate , as illustrated below.
11.3.3.2. Water Piping Installation
• The minimum requirement of water in the system is 50 litres.
If this value could not be achieved, please install additional
buffer tank (field supply).
• Water inlet and water outlet in indoor unit are used for
connection to water circuit. Please request a licensed
technician to install this water circuit.
• This water circuit must comply with all relevant European
and national regulations, i.e. IEC/EN 61770.
• Be careful not to deform the piping with excessive force
when doing piping connection job.
• Use Rp 1¼” nut for both water inlet and outlet connection
and clean all pipings with tap water before install.
• Cover the pipe end to prevent dirt and dust when inserting it
through a wall.
• Choose proper sealer which can withstand the pressures
and temperatures of the system.
• If existing tank is to be connected to this indoor/outdoor unit,
ensure the pipes are clean before water pipe installation is
carries out.
• Install external filter (30 mesh or more, field supply) before
water inlet of indoor unit (with “WATER IN” indication).
When the wall is hollow, please be sure to use the sleeve for
tube assembly to prevent dangers caused by mice biting the
connecting cable.
Содержание WH-SXC09D3E5
Страница 10: ...10 4 Location of Controls and Components 4 1 Indoor Unit 4 1 1 Location of Control ...
Страница 11: ...11 ...
Страница 12: ...12 ...
Страница 13: ...13 4 1 2 Weekly Timer Setting ...
Страница 14: ...14 4 1 3 Setting Up The Special Functions ...
Страница 15: ...15 4 1 4 Main Components 4 2 Outdoor Unit ...
Страница 16: ...16 5 Dimensions 5 1 Indoor Unit ...
Страница 17: ...17 5 2 Outdoor Unit ...
Страница 19: ...19 ...
Страница 20: ...20 7 Block Diagram 7 1 WH UX09DE5 ...
Страница 21: ...21 7 2 WH UX12DE5 ...
Страница 22: ...22 8 Wiring Connection Diagram 8 1 Indoor Unit 8 1 1 WH SXC09D3E5 ...
Страница 23: ...23 8 1 2 WH SXC12D6E5 ...
Страница 24: ...24 8 2 Outdoor Unit ...
Страница 25: ...25 9 Electronic Circuit Diagram 9 1 Indoor Unit 9 1 1 WH SXC09D3E5 ...
Страница 26: ...26 9 1 2 WH SXC12D6E5 ...
Страница 27: ...27 9 2 Outdoor Unit ...
Страница 28: ...28 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board ...
Страница 29: ...29 10 1 2 Solar Printed Circuit Board Optional ...
Страница 30: ...30 10 2 Outdoor Unit 10 2 1 Main Printed Circuit Board ...
Страница 31: ...31 10 2 2 Capacitor Printed Circuit Board 10 2 3 Noise Filter Printed Circuit Board ...
Страница 45: ...45 Solar Priority is Set Solar Priority is Not Set ...
Страница 51: ...51 Heat Tank Mode Heating priority not set Under Solar Priority Not Set Condition ...
Страница 60: ...60 Solar Priority Not Set Heat Tank Mode Heating Priority Set ...
Страница 61: ...61 Tank Mode Solar Priority Set Solar Priority Not Set ...
Страница 109: ...109 17 3 To Remove Pressure Gauge 17 4 To Remove Control Panel ...
Страница 110: ...110 17 5 To Remove RCCB ELCB 17 6 To Remove Transformer and Electronic Controller Board ...
Страница 124: ...124 19 2 WH UX09DE5 WH UX12DE5 ...
Страница 125: ...125 ...