92
16.5.22 Refrigeration Cycle Abnormality (F24)
Malfunction Decision Conditions:
1 During operation of cooling and heating, compressor frequency > Frated.
2 During operation of cooling and heating, running current: 0.65A < I < 1.65A.
3 During operation of cooling, water inlet temperature - indoor refrigerant liquid temperature < 5°C.
4 During operation of heating, indoor refrigerant liquid temperature - water inlet temperature < 5°C.
Malfunction Caused:
1 Faulty water inlet or indoor refrigerant liquid temperature sensors.
2 2/3 way valve closed.
3 Refrigerant shortage (refrigerant leakage).
4 Clogged expansion valve or strainer.
5 Faulty outdoor unit PCB (main).
6 Poor compression of compressor.
Abnormality Judgment:
Continue 2 times in 20 minutes.
Содержание WH-SDF09C3E8
Страница 14: ...14 4 Location of Controls and Components 4 1 Indoor Unit 4 1 1 Location of Control ...
Страница 15: ...15 ...
Страница 16: ...16 ...
Страница 17: ...17 4 1 2 Weekly Timer Setting ...
Страница 18: ...18 4 1 3 Setting Up the Special Functions ...
Страница 19: ...19 4 1 4 Main Components 4 2 Outdoor Unit ...
Страница 20: ...20 5 Dimensions 5 1 Indoor Unit ...
Страница 21: ...21 5 2 Outdoor Unit ...
Страница 23: ...23 ...
Страница 24: ...24 7 Block Diagram 7 1 WH UD09CE8 ...
Страница 25: ...25 7 2 WH UD12CE8 WH UD14CE8 WH UD16CE8 ...
Страница 26: ...26 8 Wiring Connection Diagram 8 1 Indoor Unit 8 1 1 WH SDF09C3E8 ...
Страница 27: ...27 8 1 2 WH SDF12C9E8 WH SDF14C9E8 WH SDF16C9E8 ...
Страница 28: ...28 8 2 Outdoor Unit ...
Страница 29: ...29 9 Electronic Circuit Diagram 9 1 Indoor Unit 9 1 1 WH SDF09C3E8 ...
Страница 30: ...30 9 1 2 WH SDF12C9E8 WH SDF14C9E8 WH SDF16C9E8 ...
Страница 31: ...31 9 2 Outdoor Unit ...
Страница 32: ...32 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board ...
Страница 33: ...33 10 1 2 Solar Printed Circuit Board Optional ...
Страница 34: ...34 10 2 Outdoor Unit 10 2 1 Main Printed Circuit Board ...
Страница 35: ...35 10 2 2 Noise Filter Printed Circuit Board ...
Страница 50: ...50 Under solar priority is not set condition solar 3WV only can ON during heating heat up interval ...
Страница 58: ...58 ...
Страница 59: ...59 ...
Страница 105: ...105 17 3 To Remove Pressure Gauge 17 4 To Remove Control Panel ...
Страница 106: ...106 17 5 To Remove RCCB 17 6 To Remove Transformer and Electronic Controller Board ...
Страница 121: ...121 19 2 WH UD09CE8 WH UD12CE8 WH UD14CE8 WH UD16CE8 ...
Страница 122: ...122 ...