62
13.1.6 Low Frequency Protection Control 1
When the compressor continuously operates at frequency lower than 25 Hz for 240 minutes, the operation
frequency will change to 24 Hz for 2 minutes.
13.1.7 Low Frequency Protection Control 2
When all the below conditions comply, the compressor frequency will change to lower frequency.
Temperature, T, for:
Heating
Outlet water (°C)
T < 14 or T 48
Outdoor air (°C)
T < 4 or T 24
Indoor heat exchanger (°C)
T 0
13.1.8 High Pressure Sensor Control
Purpose:
- To protect the system operation.
Detection
period:
- After compressor on for 5 minutes.
Detection
conditions:
- When abnormal high voltage detection, 5V or when open circuit detection 0V for 5 seconds continuously.
After
detection:
- When abnormality is detected continue 5 seconds, unit stop operation.
- OFF/ON control panel LED will blink (H64 error occurs).
13.1.9 Outside Temperature Current Control
13.1.10 Crank Case Heater Control
Purpose:
- For compressor protection during low outdoor ambient operation (during heating low temperature operation).
Control
content:
a. Trigger heater START condition
o
When the outdoor air temperature is 4°C or below, and discharge temperature is 11.6°C or below.
b. Resetting heater STOP condition
1.
When the outdoor air temperature exceeds entry condition (6°C)
2.
When the discharge temperature exceeds entry condition (18.8°C)
13.2 Protection Control for Heating Operation
13.2.1 Outdoor Air Temperature Control
The maximum current value is regulated when the outdoor air temperature rises above 14°C in order to avoid
compressor overloading.
13.2.2 Deice Operation
When outdoor pipe temperature and outdoor air temperature is low, deice operation start where outdoor fan motor
stop.
Содержание WH-SDF09C3E8
Страница 14: ...14 4 Location of Controls and Components 4 1 Indoor Unit 4 1 1 Location of Control ...
Страница 15: ...15 ...
Страница 16: ...16 ...
Страница 17: ...17 4 1 2 Weekly Timer Setting ...
Страница 18: ...18 4 1 3 Setting Up the Special Functions ...
Страница 19: ...19 4 1 4 Main Components 4 2 Outdoor Unit ...
Страница 20: ...20 5 Dimensions 5 1 Indoor Unit ...
Страница 21: ...21 5 2 Outdoor Unit ...
Страница 23: ...23 ...
Страница 24: ...24 7 Block Diagram 7 1 WH UD09CE8 ...
Страница 25: ...25 7 2 WH UD12CE8 WH UD14CE8 WH UD16CE8 ...
Страница 26: ...26 8 Wiring Connection Diagram 8 1 Indoor Unit 8 1 1 WH SDF09C3E8 ...
Страница 27: ...27 8 1 2 WH SDF12C9E8 WH SDF14C9E8 WH SDF16C9E8 ...
Страница 28: ...28 8 2 Outdoor Unit ...
Страница 29: ...29 9 Electronic Circuit Diagram 9 1 Indoor Unit 9 1 1 WH SDF09C3E8 ...
Страница 30: ...30 9 1 2 WH SDF12C9E8 WH SDF14C9E8 WH SDF16C9E8 ...
Страница 31: ...31 9 2 Outdoor Unit ...
Страница 32: ...32 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board ...
Страница 33: ...33 10 1 2 Solar Printed Circuit Board Optional ...
Страница 34: ...34 10 2 Outdoor Unit 10 2 1 Main Printed Circuit Board ...
Страница 35: ...35 10 2 2 Noise Filter Printed Circuit Board ...
Страница 50: ...50 Under solar priority is not set condition solar 3WV only can ON during heating heat up interval ...
Страница 58: ...58 ...
Страница 59: ...59 ...
Страница 105: ...105 17 3 To Remove Pressure Gauge 17 4 To Remove Control Panel ...
Страница 106: ...106 17 5 To Remove RCCB 17 6 To Remove Transformer and Electronic Controller Board ...
Страница 121: ...121 19 2 WH UD09CE8 WH UD12CE8 WH UD14CE8 WH UD16CE8 ...
Страница 122: ...122 ...