4. Select required direction and apply protective bushing provided in accessories to protect cables from sharp edges.
5. Once all wiring work has been completed, tie the cable and cord together with the binding strap so that they do not touch other

parts such as the compressor and bare copper pipes.

6. Install back the control board cover.

11.4.4.1. Wire Stripping and Connecting Requirement

• Same as indoor requirement. For details please refer the diagram on AIR-TO-WATER HEATPUMP INDOOR UNIT, section

11.3.4. (CONNECT THE CABLE TO THE INDOOR UNIT)

11.4.5. PIPE INSULATION

1. Please carry out insulation at pipe connection portion as mentioned in Indoor/Outdoor Unit Installation Diagram. Please wrap

the insulated piping end to prevent water from going inside the piping.

2. If drain hose or connecting piping is in the room (where dew may form), please increase the insulation by using POLY-E

FOAM with thickness 6 mm or above.

11.4.6. Disposal of Outdoor Unit Drain Water

• If a drain elbow is used, the unit should be placed on a stand which is taller than 50 mm.
• If the unit is used in an area where temperature falls below 0

°

C for 2 or 3 days in succession, it is recommended not to use a

drain elbow, for the drain water freezes and the fan will not rotate.

Содержание WH-SDF07C3E5

Страница 1: ...orized copying and distribution is a violation of law Order No PHAAM1006122C2 Air to Water Heatpump Indoor Unit Outdoor Unit WH SDF07C3E5 WH UD07CE5 A WH SDF09C3E5 WH UD09CE5 A WH SDF12C6E5 WH UD12CE5 A WH SDF14C6E5 WH UD14CE5 A WH SDF16C6E5 WH UD16CE5 A ...

Страница 2: ...cation Panel 70 13 9 Indoor Back Up Heater Control 70 13 10 Tank Booster Heater Control 71 13 11 Three Way Valve Control 71 13 12 Sterillization Mode 71 13 13 Quiet Operation 71 13 14 Solar operation Optional 72 13 15 External Room Thermostat Control Optional 75 14 Protection Control 76 14 1 Protection Control For All Operations 76 14 2 Protection Control For Heating Operation 77 15 Servicing Mode...

Страница 3: ...rcuit and single outlet must be used If electrical circuit capacity is not enough or defect found in electrical work it will cause electrical shock or fire 10 This equipment must be properly earthed Earth line must not be connected to gas pipe water pipe earth of lightning rod and telephone Otherwise it may cause electric shock in case equipment breakdown or insulation breakdown 11 Do not use join...

Страница 4: ...rson 4 Do not touch outdoor unit air inlet and aluminium fin It may cause injury 5 Select an installation location which is easy for maintenance 6 Pb free solder has a higher melting point than standard solder typically the melting point is 50 F 70 F 30 C 40 C higher Please use a high temperature solder iron In case of the soldering iron with temperature control please set it to 700 20 F 370 10 C ...

Страница 5: ... Height Difference m ft 20 65 6 Additional Gas Amount g m oz ft 30 0 3 Refrigeration Charge Less m ft 10 32 8 Compressor Type Hermetic Motor Motor Type Brushless 4 poles Rated Output kW 1 70 Fan Type Propeller Fan Material PP Motor Type Induction 8 poles Input Power W Output Power W 60 Fan Speed rpm 580 Heat Exchanger Fin material Aluminium Pre Coat Fin Type Corrugated Fin Row Stage FPI 2 30 17 Si...

Страница 6: ...re Differential kPa 22 0 Noise Level dB A 30 Power Level dB 43 Dimension Height mm inch 892 35 1 8 Width mm inch 502 19 3 4 Depth mm inch 353 13 29 32 Net Weight kg lbs 43 95 Refrigerant Pipe Diameter Liquid mm inch 6 35 1 4 Gas mm inch 15 88 5 8 Water Pipe Diameter Inlet mm inch 28 1 3 32 Outlet mm inch 28 1 3 32 Water Drain Hose Inner Diameter mm inch 15 00 19 32 Pump Motor Type Capacitor Run In...

Страница 7: ...nt g m oz ft 30 0 3 Refrigeration Charge Less m ft 10 32 8 Compressor Type Hermetic Motor Motor Type Brushless 4 poles Rated Output kW 1 70 Fan Type Propeller Fan Material PP Motor Type Induction 8 poles Input Power W Output Power W 60 Fan Speed rpm 640 Heat Exchanger Fin material Aluminium Pre Coat Fin Type Corrugated Fin Row Stage FPI 2 30 17 Size W H L mm 38 1 762 873 8 903 8 Item Unit Power So...

Страница 8: ...evel dB A 30 Power Level dB 43 Dimension Height mm inch 892 35 1 8 Width mm inch 502 19 3 4 Depth mm inch 353 13 29 32 Net Weight kg lbs 43 95 Refrigerant Pipe Diameter Liquid mm inch 6 35 1 4 Gas mm inch 15 88 5 8 Water Pipe Diameter Inlet mm inch 28 1 3 32 Outlet mm inch 28 1 3 32 Water Drain Hose Inner Diameter mm inch 15 00 19 32 Pump Motor Type Capacitor Run Induction Motor 2 5 μF No of Speed...

Страница 9: ...m oz ft 50 0 5 Refrigeration Charge Less m ft 30 98 4 Compressor Type Hermetic Motor Motor Type Brushless 4 poles Rated Output kW 3 00 Fan Type Propeller Fan Material PP Motor Type Induction 8 poles Input Power W Output Power W 60 Fan Speed rpm 510 Top Fan 550 Bottom Fan Heat Exchanger Fin material Aluminium Pre Coat Fin Type Corrugated Fin Row Stage FPI 2 51 18 Size W H L mm 881 5 1295 4 44 Item ...

Страница 10: ... 30 Power Level dB 43 Dimension Height mm inch 892 35 1 8 Width mm inch 502 19 3 4 Depth mm inch 353 13 29 32 Net Weight kg lbs 49 108 Refrigerant Pipe Diameter Liquid mm inch 9 52 3 8 Gas mm inch 15 88 5 8 Water Pipe Diameter Inlet mm inch 28 1 3 32 Outlet mm inch 28 1 3 32 Water Drain Hose Inner Diameter mm inch 15 00 19 32 Pump Motor Type Capacitor Run Induction Motor 5 μF No of Speed 3 Input P...

Страница 11: ... m oz ft 50 0 5 Refrigeration Charge Less m ft 30 98 4 Compressor Type Hermetic Motor Motor Type Brushless 4 poles Rated Output kW 3 00 Fan Type Propeller Fan Material PP Motor Type Induction 8 poles Input Power W Output Power W 60 Fan Speed rpm 540 Top Fan 580 Bottom Fan Heat Exchanger Fin material Aluminium Pre Coat Fin Type Corrugated Fin Row Stage FPI 2 51 18 Size W H L mm 881 5 1295 4 44 Item...

Страница 12: ... 30 Power Level dB 43 Dimension Height mm inch 892 35 1 8 Width mm inch 502 19 3 4 Depth mm inch 353 13 29 32 Net Weight kg lbs 49 108 Refrigerant Pipe Diameter Liquid mm inch 9 52 3 8 Gas mm inch 15 88 5 8 Water Pipe Diameter Inlet mm inch 28 1 3 32 Outlet mm inch 28 1 3 32 Water Drain Hose Inner Diameter mm inch 15 00 19 32 Pump Motor Type Capacitor Run Induction Motor 5 μF No of Speed 3 Input P...

Страница 13: ... m oz ft 50 0 5 Refrigeration Charge Less m ft 30 98 4 Compressor Type Hermetic Motor Motor Type Brushless 4 poles Rated Output kW 3 00 Fan Type Propeller Fan Material PP Motor Type Induction 8 poles Input Power W Output Power W 60 Fan Speed rpm 580 Top Fan 620 Bottom Fan Heat Exchanger Fin material Aluminium Pre Coat Fin Type Corrugated Fin Row Stage FPI 2 51 18 Size W H L mm 881 5 1295 4 44 Item...

Страница 14: ... 30 Power Level dB 43 Dimension Height mm inch 892 35 1 8 Width mm inch 502 19 3 4 Depth mm inch 353 13 29 32 Net Weight kg lbs 49 108 Refrigerant Pipe Diameter Liquid mm inch 9 52 3 8 Gas mm inch 15 88 5 8 Water Pipe Diameter Inlet mm inch 28 1 3 32 Outlet mm inch 28 1 3 32 Water Drain Hose Inner Diameter mm inch 15 00 19 32 Pump Motor Type Capacitor Run Induction Motor 5 μF No of Speed 3 Input P...

Страница 15: ...m auto restart after power failure for safety restart operation Gas leakage protection Prevent compressor reverse cycle Inner protector to protect compressor Serviceability Improvement Breakdown Self Diagnosis function System Status Check Buttons for servicing purpose System Pumpdown Button for servicing purpose Front maintenance design for outdoor unit Operation Condition NOTICE When the outdoor ...

Страница 16: ...16 4 Location of Controls and Components 4 1 Indoor Unit 4 1 1 Location of Control ...

Страница 17: ...17 ...

Страница 18: ...18 ...

Страница 19: ...19 4 1 2 Weekly Timer Setting ...

Страница 20: ...20 4 1 3 Setting Up The Special Functions ...

Страница 21: ...21 4 1 4 Main Components 4 2 Outdoor Unit ...

Страница 22: ...22 5 Dimensions 5 1 Indoor Unit ...

Страница 23: ...23 5 2 Outdoor Unit 5 2 1 WH UD07CE5 A WH UD09CE5 A ...

Страница 24: ...24 5 2 2 WH UD12CE5 A WH UD14CE5 A WH UD16CE5 A ...

Страница 25: ...wn in the table Piping size Rated Length m Common Length m Max Elevation m Min Piping Length m Max Piping Length m Additional Refrigerant g m Model Gas Liquid UD07CE5 A 5 8 1 4 7 10 20 3 30 30 UD09CE5 A 5 8 1 4 7 10 20 3 30 30 UD12CE5 A 5 8 3 8 7 30 30 3 40 50 UD14CE5 A 5 8 3 8 7 30 30 3 40 50 UD16CE5 A 5 8 3 8 7 30 30 3 40 50 ...

Страница 26: ...26 ...

Страница 27: ...27 7 Block Diagram 7 1 WH UD07CE5 A WH UD09CE5 A ...

Страница 28: ...28 7 2 WH UD12CE5 A WH UD14CE5 A WH UD16CE5 A ...

Страница 29: ...29 8 Wiring Connection Diagram 8 1 Indoor Unit 8 1 1 WH SDF07C3E5 WH SDF09C3E5 ...

Страница 30: ...30 8 1 2 WH SDF12C6E5 WH SDF14C6E5 WH SDF16C6E5 ...

Страница 31: ...31 8 2 Outdoor Unit 8 2 1 WH UD07CE5 A WH UD09CE5 A ...

Страница 32: ...32 8 2 2 WH UD12CE5 A WH UD14CE5 A WH UD16CE5 A ...

Страница 33: ...33 9 Electronic Circuit Diagram 9 1 Indoor Unit 9 1 1 WH SDF07C3E5 WH SDF09C3E5 ...

Страница 34: ...34 9 1 2 WH SDF12C6E5 WH SDF14C6E5 WH SDF16C6E5 ...

Страница 35: ...35 9 2 Outdoor Unit 9 2 1 WH UD07CE5 A WH UD09CE5 A ...

Страница 36: ...36 9 2 2 WH UD12CE5 A WH UD14CE5 A WH UD16CE5 A ...

Страница 37: ...37 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board ...

Страница 38: ...38 10 1 2 Solar Printed Circuit Board Optional ...

Страница 39: ...39 10 2 Outdoor Unit 10 2 1 WH UD07CE5 A WH UD09CE5 A 10 2 1 1 Main Printed Circuit Board ...

Страница 40: ...40 10 2 1 2 Capacitor Printed Circuit Board 10 2 1 3 Noise Filter Printed Circuit Board ...

Страница 41: ...41 10 2 2 WH UD12CE5 A WH UD14CE5 A WH UD16CE5 A 10 2 2 1 Main Printed Circuit Board ...

Страница 42: ...42 10 2 2 2 Capacitor Printed Circuit Board 10 2 2 3 Noise Filter Printed Circuit Board ...

Страница 43: ...T If an awning is built over the unit to prevent direct sunlight or rain be careful that heat radiation from the condenser is not obstructed Avoid location where ambient temperature is below 20 C Keep the spaces indicated by arrows from wall ceiling fence or other obstacles Do not place any obstacles which may cause a short circuit of the discharged air If outdoor unit installed near sea region wi...

Страница 44: ...on plate by moving it left and right 3 Fix the screws to the holes on the hooks of installation plate as illustrated below 11 3 3 2 Water Piping Installation The minimum requirement of water in the system is 30 litres If this value could not be achieved please install additional buffer tank field supply Water inlet and water outlet in indoor unit are used for connection to water circuit Please req...

Страница 45: ...g Flare nut may be broken and cause leakage Use proper spanner or ring wrench 3 Connect the piping Align the center of piping and sufficiently tighten the flare nut with fingers Further tighten the flare nut with torque wrench in specified torque as stated in the table 11 3 3 4 Drain Hose Installation Use inner diameter 15 mm drain hose in the market This hose must to be installed in a continuosly...

Страница 46: ...esignation 60245 IEC 57 or heavier or similarly double insulation sheathed cable note Should be CE marking compliance component It should be directed to heating mode when it is OFF Maximum load for the valve is 3VA 5 Receiver shall be connected to Room Thermostat refer to Field Supply Accessories table for details Receiver s cable must be 4 or 3 x min 0 5 mm2 double insulation layer of PVC sheathe...

Страница 47: ...47 11 3 4 1 Wire Stripping and Connecting Requirement Terminal screw Tightening torque Nlcm kgf cm M4 157 196 16 20 M5 196 245 20 25 ...

Страница 48: ...greater than or equal to 828 38kW The equipment s power supply 1 shall be connected to a suitable supply network having service current capacity 100A per phase Please liaise with supply authority to ensure that the service current capacity at the interface point is sufficient for the installation of the equipment The equipment s power supply 2 complies with IEC EN 61000 3 12 The equipment s power ...

Страница 49: ... torque wrench to the specified torque as stated in the table Local pipes can project in any of four directions Make holes in the pipe panels for the pipes to pass through Be sure to install the pipe panels to prevent rain from getting inside the outdoor unit Removing the service panel 1 Remove the three mounting screws 2 Slide the service panel downward to release the pawls After this pull the se...

Страница 50: ...ice port of the 3 way valve 6 Tighten the service port caps of the 3 way valve at a torque of 18 N m with a torque wrench 7 Remove the valve caps of both of the 2 way valve and 3 way valve Position both of the valves to OPEN using a hexagonal wrench 4 mm 8 Mount valve caps onto the 2 way valve and the 3 way valve Be sure to check for gas leakage 11 4 4 CONNECT THE CABLE TO THE OUTDOOR UNIT FOR DET...

Страница 51: ...BLE TO THE INDOOR UNIT 11 4 5 PIPE INSULATION 1 Please carry out insulation at pipe connection portion as mentioned in Indoor Outdoor Unit Installation Diagram Please wrap the insulated piping end to prevent water from going inside the piping 2 If drain hose or connecting piping is in the room where dew may form please increase the insulation by using POLY E FOAM with thickness 6 mm or above 11 4 ...

Страница 52: ...er the unit to prevent direct sunlight or rain be careful that heat radiation from the condenser is not obstructed Avoid location where ambient temperature is below 20 C Keep the spaces indicated by arrows from wall ceiling fence or other obstacles Do not place any obstacles which may cause a short circuit of the discharged air If outdoor unit installed near sea region with high content of sulphur...

Страница 53: ...by moving it left and right 3 Fix the screws to the holes on the hooks of installation plate as illustrated below 12 3 3 2 Water Piping Installation The minimum requirement of water in the system is 50 litres If this value could not be achieved please install additional buffer tank field supply Water inlet and water outlet in indoor unit are used for connection to water circuit Please request a li...

Страница 54: ...ken and cause leakage Use proper spanner or ring wrench 3 Connect the piping Align the center of piping and sufficiently tighten the flare nut with fingers Further tighten the flare nut with torque wrench in specified torque as stated in the table 12 3 3 4 Drain Hose Installation Use inner diameter 15 mm drain hose in the market This hose must to be installed in a continuosly downward direction an...

Страница 55: ... 0 5 mm2 of type designation 60245 IEC 57 or heavier or similarly double insulation sheathed cable note Should be CE marking compliance component It should be directed to heating mode when it is OFF Maximum load for the valve is 3VA 5 Receiver shall be connected to Room Thermostat refer to Field Supply Accessories table for details Receiver s cable must be 4 or 3 x min 0 5 mm2 double insulation la...

Страница 56: ...56 12 3 4 1 Wire Stripping and Connecting Requirement Terminal screw Tightening torque N cm kgf cm M4 157 196 16 20 M5 196 245 20 25 ...

Страница 57: ...5 UD16CE5 0 244Ω Please liaise with supply authority to ensure that the power supply 1 is connected only to a supply of that impedance or less The equipment s power supply 2 complies with IEC EN 61000 3 12 The equipment s power supply 2 shall be connected to a suitable supply network with the following maximum permissible system impedance Zmax at the interface for models WH SDF12C6E5 UD12CE5 WH SD...

Страница 58: ...fter inserting the flare nut locate at valve onto the copper pipe Align center of piping to valves and then tighten with torque wrench to the specified torque as stated in the table Local pipes can project in any of four directions Make holes in the pipe panels for the pipes to pass through Be sure to install the pipe panels to prevent rain from getting inside the outdoor unit Removing the service...

Страница 59: ...n evacuate the air approximately ten minutes 4 Close the Low side valve of the charging set and turn off the vacuum pump Make sure that the needle in the gauge does not move after approximately five minutes Note BE SURE TO FOLLOW THIS PROCEDURE IN ORDER TO AVOID REFRIGERANT GAS LEAKAGE 5 Disconnect the charging hose from the vacuum pump and from the service port of the 3 way valve 6 Tighten the se...

Страница 60: ...ontrol board cover 12 4 4 1 Wire Stripping and Connecting Requirement Same as indoor requirement For details please refer the diagram on AIR TO WATER HEATPUMP INDOOR UNIT section 12 3 4 CONNECT THE CABLE TO THE INDOOR UNIT 12 4 5 PIPE INSULATION 1 Please carry out insulation at pipe connection portion as mentioned in Indoor Outdoor Unit Installation Diagram Please wrap the insulated piping end to ...

Страница 61: ... used as internal water setting temperature and it is updated continuously whenever the electrical power is supplied to the unit 13 1 2 Heating Operation 13 1 2 1 Thermostat control Compressor is OFF when Water Outlet Temperature Internal Water Setting Temperature 2 C for continuously 3 minutes Compressor is ON after waiting for 3 minutes if the Water Outlet Temperature Water Inlet Temperature tem...

Страница 62: ...inlet during thermo off time 3 C 2 Water pump ON back when tank temp tank temp when heatpump thermo off 3 C 3 Heat pump only ON back after water outlet temperature Heat pump THERMO ON TEMP water pump ON for 3 minutes Booster heater control Booster heater turn On and Off follow normal operation Booster heater turn ON condition 1 During startup time initialization Booster heater turn ON after DELAY ...

Страница 63: ...Priority is set not set by control panel 1 3 ways valve control 3 ways valve switch to room side during heating heat up interval and switch to tank side during tank heat up interval Both mode will switch alternatively 2 Heat pump operation control During heating heat up interval Follow normal heating operation Under solar priority set condition Always detect the tank temperature after heating heat...

Страница 64: ...at up interval and start count heating heat up interval THERMO ON TEMP 1 THERMO ON TEMP Tank temp when heatump thermo off 3 C 2 After Heating heat up interval always detect tank temperature Switch to next tank heat up interval when tank temperature THERMO ON TEMP iv Case 4 Only during solar priority is set condition When solar pump ON tank heat up interval end early and 3 ways valve switch to room...

Страница 65: ...65 Under solar priority is not set condition solar 3WV only can ON during heating heat up interval ...

Страница 66: ... Outdoor temperature is updated every 30 minutes when operation ON 13 1 5 1 Heating Mode Operation Time Chart Example 1 3 ways valve control 3 ways valve switch and fix to heating side 2 Heat pump operate follow normal heating operation 3 Backup heater operate follow normal operation 4 Solar 3 way valve operates follow solar operation specification 13 1 6 Water Temperature Thermo Shift Setting Swi...

Страница 67: ...ng mode is used to easily shift the target water outlet temperature 13 1 7 Outdoor Fan Motor Operation Outdoor fan motor is adjusted according to operation condition It starts when compressor starts operation and it stops 30 seconds after compressor stops operation ...

Страница 68: ...ump will remain ON when compressor OFF due to thermostat OFF 13 3 Pump Down Operation Purpose Ensure the pump down operation when relocating or disposing of the unit The pump down operation will extract all refrigerant from the piping into the outdoor unit 1 Make sure the OFF ON control panel LED is OFF no operation 2 Press the Pump Down button to start the pump down operation 3 No low pressure pr...

Страница 69: ...tem will start checking flow switch status ON OFF 2 If the flow switch ON for 10 seconds the system will check on the water inlet temperature for 10 seconds If the water inlet temperature not exceeds 80 C the water pump shall be continuously running with normal mode If the water inlet temperature exceeds 80 C for continuously 10 seconds the water pump will be OFF immediately 3 After water pump OFF...

Страница 70: ...ion Heater Stop Condition a When outdoor set temperature outdoor set temperature 2 C for continuous 15 secs OR b When water out temp water set temperature 2 C for continuous 15 secs OR c Heater switch is Off OR d Heat pump thermo off or OFF condition 2 Force Heater Mode Heater On Condition a After water pump operate 9 mins b When water outlet temperature water set temperature 8 C c 20 minutes sinc...

Страница 71: ...de heat capacity to heating side 2 3 ways valve switch On During 3 ways valve switch On time the hot water will provide heat capacity to tank side 3 Stop condition During stop mode 3 ways valve will be in switch off position 13 12 Sterillization Mode 1 During Sterillization mode Tank will be heat up to the Sterillize Set temperature for a certain period of time also set by controller 2 The functio...

Страница 72: ...operation request from Solar pump station OR Tank hot water temp is above solar off upper limit temp EEPROM 2 77 C heat pump OFF OR operate to room side when solar pump operate during solar priority set booster heater OFF when solar pump operate during solar priority set When solar priority is NOT SET 1 Operation condition a Solar pump operates if all of the following conditions are fulfilled Powe...

Страница 73: ...73 ...

Страница 74: ...74 ...

Страница 75: ...connection select YES by Indoor control panel When indoor running heat mode refer thermo On Off from heating line feedback And when indoor running cool mode refer thermo On Off from cooling line feedback Heat pump Off immediately when receive thermo off feedback Maker Characteristic Siemen REV200 Touch panel Siemen RAA20 Analog Setting L L1 H Heat Thermo L L2 C Cool Thermo Set Temp Actual Temp Ope...

Страница 76: ... operation and OFF ON control panel LED will blink F22 error occurs B DC Peak Current Control 1 When the current to IPM exceeds set value of 40 1 5 0 A UD07CE and UD09CE 44 7 5 0 A UD12CE UD14CE and UD16CE compressor will stop Compressor will restart after three minutes 2 If the set value exceeds again for more than 30 seconds after the compressor restarts operation will restart after two minutes ...

Страница 77: ...ing low outdoor ambient operation during heating low temperature operation Control content a Trigger heater START conditon when the outdoor air temperature is 4 C or below and discharge temperature is 11 6 C or below b Resetting heater STOP condition 1 when the outdoor air temperature exceeds entry condition 6 C 2 when the discharge temperature exceeds entry condition 18 8 C 14 2 Protection Contro...

Страница 78: ...e 3 way valve 5 Press the OFF ON switch on control panel to stop PUMP DOWN mode 6 Remove the refrigerant piping 15 3 How To Adjust Water Flow Rate Before adjust the water flow rate make sure that the total water volume in the installation is 30 litres minimum 07C3 09C3 50 litres minimum 12C6 14C6 16C6 The water flow rate can be adjusted with select the water pump speed on the water pump The defaul...

Страница 79: ...r local authorized dealer 3 Indoor unit control board area Thorough visual inspection of the control board and look for defects i e loose connection melting of wire insulator and etc 4 RCCB Ensure the RCCB set to ON condition before check RCCB Turn on the power supply to the indoor unit This testing could only be done when power is supplied to the indoor unit Push the TEST button on the RCCB The l...

Страница 80: ...xternal water filter is located inside the tube connector which is before water inlet connector of indoor unit indicated with WATER IN Refer to figure below Use spanner to detach the tube connector nut Take out the filter carefully so that not deforms it shape Use tap water only to wash the residue on the filter If necessary gently use soft brush only to clean the hard dirt After clean put it back...

Страница 81: ...no electrical problems before inspecting the refrigeration cycle Such problems include insufficient insulation problem with the power source malfunction of a compressor and a fan The normal pressure of the refrigeration cycle depends on various conditions the standard values for them are shown in the table on the right ...

Страница 82: ...fifteen minutes after an operation is started Heating Mode Condition of the Air to Water Heatpump indoor and outdoor units Low Pressure High Pressure Electric current during operation Water leakage or insufficient water flow rate in the system Excessive amount of refrigerant Inefficient compression Insufficient refrigerant gas leakage Outdoor heat exchange deficiency Clogged expansion valve or Str...

Страница 83: ...IC memory To check the error code 1 When an abnormality occurs system will stop operation and OFF ON control panel LED will blink 2 Error code of the abnormality will display on the control panel Timer display LCD 3 To determine the abnormality description the Error Code Table needs to be referred To display past last error code 1 Turn ON power supply 2 Press and hold the CHECK button for more tha...

Страница 84: ...gh pressure sensor Water pump or water leakage Clogged expansion valve or strainer Excess refrigerant Outdoor PCB H99 Indoor heat exchanger freeze prevention Indoor heat exchanger Refrigerant shortage F12 Pressure switch activate 4 times occurrence within 20 minutes Pressure switch F14 Outdoor compressor abnormal revolution 4 times occurrence within 20 minutes Outdoor compressor F15 Outdoor fan mo...

Страница 85: ... disconnected F45 Indoor water outlet temperature sensor abnormality Continue for 5 sec Water outlet temperature sensor defective or disconnected F46 Outdoor Current Transformer open circuit Insufficient refrigerant Outdoor PCB Compressor low F95 Cooling high pressure overload protection Outdoor high pressure sensor Water pump or water leakage Clogged expansion valve or strainer Excess refrigerant...

Страница 86: ...ration of cooling and heating the capability rank of indoor checked by the outdoor is used to determine connection capability rank abnormality Malfunction Caused 1 Wrong model interconnected 2 Wrong indoor unit or outdoor unit PCB main used 3 Faulty indoor unit or outdoor unit PCB main Abnormality Judgment Continue for 90 seconds ...

Страница 87: ...During startup and operation of cooling and heating the temperatures detected by the compressor tank temperature sensor are used to determine sensor error Malfunction Caused 1 Faulty connector connection 2 Faulty sensor 3 Faulty outdoor unit PCB main Abnormality Judgment Continue for 5 seconds ...

Страница 88: ... During startup and operation of cooling and heating the temperatures detected by the indoor refrigerant liquid temperature sensor are used to determine sensor error Malfunction Caused 1 Faulty connector connection 2 Faulty sensor 3 Faulty indoor unit PCB main Abnormality Judgment Continue for 5 seconds ...

Страница 89: ...ove 26 C is detected by the outdoor pipe temperature sensor Malfunction Caused 1 Dust accumulation on the outdoor unit heat exchanger 2 Air short circuit at outdoor unit 3 2 way valve partially closed 4 Faulty outdoor unit fan motor 5 Refrigerant shortage refrigerant leakage 6 Clogged expansion valve or strainer 7 Faulty outdoor pipe temperature sensor 8 Faulty outdoor unit main PCB main ...

Страница 90: ...etected by the indoor water flow switch is used to determine water flow error Malfunction Caused 1 Faulty water pump 2 Water leak in system 3 Faulty connector connection 4 Faulty water flow switch 5 Faulty indoor unit PCB main Abnormality Judgment Continue for 10 seconds but no judgment for 9 minutes after compressor startup restart ...

Страница 91: ...n Conditions During operation of cooling and heating when the outdoor high pressure sensor output signal is 0Vdc or 5Vdc Malfunction Caused 1 Faulty connector connection 2 Faulty sensor 3 Faulty outdoor unit PCB main Abnormality Judgment Continue 4 times in 20 minutes ...

Страница 92: ...ndoor backup heater when no power supplies to indoor backup heater or OLP open circuit Malfunction Caused 1 Faulty power supply connector connection 2 Faulty connector connection 3 Faulty indoor backup heater overload protector OLP 4 Faulty indoor unit PCB main Abnormality Judgment Continue for 60 seconds ...

Страница 93: ...onditions When tank connection is set to ON the temperatures detected by the tank temperature sensor are used to determine sensor error Malfunction Caused 1 Faulty connector connection 2 Faulty sensor 3 Faulty indoor unit PCB main Abnormality Judgment Continue for 5 seconds ...

Страница 94: ...ation Abnormality H76 Malfunction Decision Conditions During standby and operation of cooling and heating indoor control panel error occur Malfunction Caused 1 Faulty connector connection 2 Faulty control panel 3 Faulty indoor unit PCB main ...

Страница 95: ...s normal Malfunction Caused 1 Faulty outdoor unit PCB main 2 Faulty indoor unit PCB main 3 Indoor outdoor signal transmission error due to wrong wiring 4 Indoor outdoor signal transmission error due to breaking of wire in the connection wires between the indoor and outdoor units 5 Indoor outdoor signal transmission error due to disturbed power supply waveform Abnormality Judgment Continue for 1 mi...

Страница 96: ...on Conditions During operation of tank booster heater and tank booster heater OLP open circuit Malfunction Caused 1 Faulty connector connection 2 Faulty tank booster heater overload protector OLP 3 Faulty indoor unit PCB main Abnormality Judgment Continue for 60 seconds ...

Страница 97: ...tween Indoor and Outdoor H95 Malfunction Decision Conditions The supply power is detected for its requirement by the indoor outdoor transmission Malfunction Caused 1 Insufficient power supply 2 Faulty outdoor unit PCB noise filter main ...

Страница 98: ...ssure 4 0 MPa and above is detected by outdoor high pressure sensor Malfunction Caused 1 Faulty water pump 2 Insufficient water flow rate in system 3 Water leak in system 4 2 3 way closed 5 Clogged expansion valve or strainer 6 Excessive refrigerant 7 Faulty outdoor high pressure sensor 8 Faulty outdoor unit PCB main ...

Страница 99: ...door refrigerant liquid temperature 0 C Malfunction Caused 1 Faulty water pump 2 Insufficient water flow rate in system 3 Water leak in system 4 2 way valve partially closed 5 Clogged expansion valve or strainer 6 Refrigerant shortage refrigerant leakage 7 Faulty indoor refrigerant liquid temperature sensor 8 Faulty indoor unit PCB main ...

Страница 100: ...lfunction Caused 1 Dust accumulation on the outdoor unit heat exchanger 2 Air short circuit at outdoor unit 3 Faulty water pump 4 Insufficient water flow rate in system 5 Water leak in system 6 2 3 way valve closed 7 Clogged expansion valve or strainer 8 Excessive refrigerant 9 Faulty outdoor high pressure sensor and switch 10 Faulty outdoor unit PCB Abnormality Judgment Continue 4 times in 20 min...

Страница 101: ... compressor rotation failure is detected by checking the compressor running condition through the position detection circuit Malfunction Caused 1 Compressor terminal disconnect 2 Faulty outdoor unit PCB main 3 Faulty compressor Abnormality Judgment Continue 4 times in 20 minutes ...

Страница 102: ...l fan motor feedback of rotation 2550rpm or 50rpm Malfunction Caused 1 Operation stop due to short circuit inside the fan motor winding 2 Operation stop due to breaking of wire inside the fan motor 3 Operation stop due to breaking of fan motor lead wires 4 Operation stop due to fan motor Hall IC malfunction 5 Operation error due to faulty outdoor unit PCB Abnormality Judgment Continue 2 times in 3...

Страница 103: ...itions During operation of cooling and heating when outdoor current above 27 9A is detected by the current transformer CT in the outdoor unit PCB Malfunction Caused 1 Excessive refrigerant 2 Faulty outdoor unit PCB main Abnormality Judgment Continue 3 times in 20 minutes ...

Страница 104: ...ve 112 C is detected by the compressor tank temperature sensor Malfunction Caused 1 Faulty compressor tank temperature sensor 2 2 3 way valve closed 3 Refrigerant shortage refrigerant leakage 4 Clogged expansion valve or strainer 5 Faulty outdoor unit PCB main 6 Faulty compressor Abnormality Judgment Continue 4 times in 30 minutes ...

Страница 105: ...onditions During operation of cooling and heating when temperature 95 C is detected by the outdoor IPM temperature sensor Malfunction Caused 1 Faulty outdoor unit fan motor 2 Faulty outdoor unit PCB main Abnormality Judgment Continue 3 times in 30 minutes ...

Страница 106: ...of cooling and heating when outdoor DC current is above 40 1 5 0A for UD07 09CE OR 44 7 5 0A for UD12 16CE is detected by the IPM DC Peak sensing circuitry in the outdoor unit PCB main Malfunction Caused 1 Faulty outdoor unit PCB main 2 Faulty compressor Abnormality Judgment Continue for 7 times ...

Страница 107: ...let temperature indoor refrigerant liquid temperature 5 C 4 During operation of heating indoor refrigerant liquid temperature water inlet temperature 5 C Malfunction Caused 1 Faulty water inlet or indoor refrigerant liquid temperature sensors 2 2 3 way valve closed 3 Refrigerant shortage refrigerant leakage 4 Clogged expansion valve or strainer 5 Faulty outdoor unit PCB main 6 Poor compression of ...

Страница 108: ... temperature of thermostat ON indoor unit 0 C 2 During cooling operation when the indoor pipe temperature of thermostat ON indoor unit 45 C Malfunction Caused 1 Faulty sensor 2 Faulty connector connection 3 Faulty outdoor unit PCB noise filter main 4 Faulty four way valve Abnormality Judgment Continue 4 times in 30 minutes ...

Страница 109: ...l F27 Malfunction Decision Conditions During compressor stop and outdoor high pressure switch is remain opened Malfunction Caused 1 Faulty connector connection 2 Faulty switch 3 Faulty outdoor unit PCB main Abnormality Judgment Continue for 1 minute ...

Страница 110: ... During startup and operation of cooling and heating the temperatures detected by the outdoor air temperature sensor are used to determine sensor error Malfunction Caused 1 Faulty connector connection 2 Faulty sensor 3 Faulty outdoor unit PCB main Abnormality Judgment Continue for 5 seconds ...

Страница 111: ...s During startup and operation of cooling and heating the temperatures detected by the indoor water inlet temperature sensor are used to determine sensor error Malfunction Caused 1 Faulty connector connection 2 Faulty sensor 3 Faulty indoor unit PCB main Abnormality Judgment Continue for 5 seconds ...

Страница 112: ... During startup and operation of cooling and heating the temperatures detected by the outdoor discharge pipe temperature sensor are used to determine sensor error Malfunction Caused 1 Faulty connector connection 2 Faulty sensor 3 Faulty outdoor unit PCB main Abnormality Judgment Continue for 5 seconds ...

Страница 113: ...ng operation of cooling and heating when the PFC protection circuitry in the outdoor unit PCB main senses abnormal high DC voltage level Malfunction Caused 1 Power supply surge 2 Compressor windings not uniform 3 Faulty outdoor unit PCB main Abnormality Judgment Continue 4 times in 10 minutes ...

Страница 114: ... During startup and operation of cooling and heating the temperatures detected by the outdoor pipe temperature sensor are used to determine sensor error Malfunction Caused 1 Faulty connector connection 2 Faulty sensor 3 Faulty outdoor unit PCB main Abnormality Judgment Continue for 5 seconds ...

Страница 115: ... During startup and operation of cooling and heating the temperatures detected by the outdoor defrost temperature sensor are used to determine sensor error Malfunction Caused 1 Faulty connector connection 2 Faulty sensor 3 Faulty outdoor unit PCB main Abnormality Judgment Continue for 5 seconds ...

Страница 116: ... During startup and operation of cooling and heating the temperatures detected by the indoor water outlet temperature sensor are used to determine sensor errors Malfunction Caused 1 Faulty connector connection 2 Faulty sensor 3 Faulty indoor unit PCB main Abnormality Judgment Continue for 5 seconds ...

Страница 117: ...rmer CT open circuit is detected by checking the compressor running frequency rated frequency and CT detected input current 0 65A for continuously 20 seconds Malfunction Caused 1 CT defective 2 Faulty outdoor unit PCB 3 Compressor defective low compression Abnormality Judgment Continue 3 times in 20 seconds ...

Страница 118: ... above is detected by outdoor high pressure sensor Malfunction Caused 1 Dust accumulation in the outdoor unit heat exchanger 2 Air short circuit at outdoor unit 3 2 way valve closed 4 Faulty outdoor unit fan motor 5 Clogged expansion valve or strainer 6 Excessive refrigerant 7 Faulty outdoor high pressure sensor 8 Faulty outdoor unit PCB main ...

Страница 119: ...ed at bottom of the front plate and 1 mounting screw at the front of the plate 2 Gently pull the lower section of the front plate towards you to remove the front plate from left and right hooks 3 Hold the left edge and right edge of front plate to lift up front plate from hooks 18 2 To Remove Cabinet WARNING High Voltage are generated in the electrical parts area by the capacitor Ensure that the c...

Страница 120: ...120 18 3 To Remove Pressure Gauge 18 4 To Remove Control Panel ...

Страница 121: ...121 18 5 To Remove RCCB 18 6 To Remove Transformer and Electronic Controller Board ...

Страница 122: ...122 18 7 To Remove Pressure Relief Valve Flow Switch Water Pump and Bottle Complete When reinstall the water pipe use grease or water at the joining ...

Страница 123: ...123 When reinstall the water pipe use grease or water at the joining When reinstall the water pipe use grease or water at the joining ...

Страница 124: ...cteristics 19 1 1 WH SDF07C3E5 WH UD07CE5 A Heating Characteristics at Different Outdoor Air Temperature Condition Outdoor air temperature 7 C DBT 6 C WBT Indoor water inlet temperature 30 C Indoor water outlet temperature 35 C Piping length 7m ...

Страница 125: ...125 Heating Characteristics at Different Piping Length Condition Outdoor air temperature 7 C DBT 6 C WBT Indoor water inlet temperature 30 C Indoor water outlet temperature 35 C Piping length 7m ...

Страница 126: ...9C3E5 WH UD09CE5 A Heating Characteristics at Different Outdoor Air Temperature Condition Outdoor air temperature 7 C DBT 6 C WBT Indoor water inlet temperature 30 C Indoor water outlet temperature 35 C Piping length 7m ...

Страница 127: ...127 Heating Characteristics at Different Piping Length Condition Outdoor air temperature 7 C DBT 6 C WBT Indoor water inlet temperature 30 C Indoor water outlet temperature 35 C Piping length 7m ...

Страница 128: ...2C6E5 WH UD12CE5 A Heating Characteristics at Different Outdoor Air Temperature Condition Outdoor air temperature 7 C DBT 6 C WBT Indoor water inlet temperature 30 C Indoor water outlet temperature 35 C Piping length 7m ...

Страница 129: ...129 Heating Characteristics at Different Piping Length Condition Outdoor air temperature 7 C DBT 6 C WBT Indoor water inlet temperature 30 C Indoor water outlet temperature 35 C Piping length 7m ...

Страница 130: ...4C6E5 WH UD14CE5 A Heating Characteristics at Different Outdoor Air Temperature Condition Outdoor air temperature 7 C DBT 6 C WBT Indoor water inlet temperature 30 C Indoor water outlet temperature 35 C Piping length 7m ...

Страница 131: ...131 Heating Characteristics at Different Piping Length Condition Outdoor air temperature 7 C DBT 6 C WBT Indoor water inlet temperature 30 C Indoor water outlet temperature 35 C Piping length 7m ...

Страница 132: ...6C6E5 WH UD16CE5 A Heating Characteristics at Different Outdoor Air Temperature Condition Outdoor air temperature 7 C DBT 6 C WBT Indoor water inlet temperature 30 C Indoor water outlet temperature 35 C Piping length 7m ...

Страница 133: ...133 Heating Characteristics at Different Piping Length Condition Outdoor air temperature 7 C DBT 6 C WBT Indoor water inlet temperature 30 C Indoor water outlet temperature 35 C Piping length 7m ...

Страница 134: ... 5 50 2 82 5 40 3 00 5 20 3 14 5 00 3 33 7 6 10 2 16 5 90 2 36 5 85 2 63 5 80 2 90 5 80 3 06 5 80 3 22 2 6 80 1 87 6 70 2 16 6 70 2 38 6 60 2 64 6 30 2 90 6 00 3 16 7 9 00 1 93 9 00 2 20 9 00 2 45 9 00 2 81 8 95 3 23 8 90 3 87 25 9 00 1 07 9 00 1 27 8 40 1 40 8 00 1 59 7 80 1 81 7 50 2 03 HC Heating Capacity kW IP Power Input kW LWC Leaving Water Condenser Temperature C Tamb Ambient Temperature C ...

Страница 135: ...0 2 45 14 00 2 80 14 00 3 05 14 00 3 44 HC Heating Capacity kW IP Power Input kW LWC Leaving Water Condenser Temperature C Tamb Ambient Temperature C LWC 30 35 40 45 50 55 Tamb HC IP HC IP HC IP HC IP HC IP HC IP 15 10 60 4 13 10 30 4 42 10 00 4 71 9 70 5 00 8 80 4 98 7 90 4 95 7 11 90 4 07 11 40 4 47 10 80 4 87 10 30 5 26 9 60 5 13 9 00 4 99 2 13 50 3 78 13 00 4 00 12 40 4 22 11 90 4 44 10 80 4 5...

Страница 136: ...ement Parts List 20 1 WH SDF07C3E5 WH SDF09C3E5 WH SDF12C6E5 WH SDF14C6E5 WH SDF16C6E5 Note The above exploded view is for the purpose of parts disassembly and replacement The non numbered parts are not kept as standard service parts ...

Страница 137: ...E 1 CWH90C0012 CWH90C0011 17 HEATER ASS Y 1 CWA34K1014 CWA34K1020 O 18 SOUND PROOF MATERIAL 1 CWG302544 CWG302575 19 THERMOSTAT 2 3 CWA151065 O 20 ELECTRONIC CONTROLLER MAIN 1 CWA73C4858 CWA73C4859 CWA73C4855 CWA73C4856 CWA73C4857 O 21 TERMINAL BOARD ASS Y 1 CWA28K1217 25 TERMINAL BOARD ASS Y 1 CWA28K1229 26 TERMINAL BOARD ASS Y 1 CWA28K1230 27 ELECTRO MAGNETIC SWITCH 1 K6C1AYY00004 O 28 TERMINAL ...

Страница 138: ...138 20 2 WH UD07CE5 A WH UD09CE5 A ...

Страница 139: ...139 ...

Страница 140: ...140 Note The above exploded view is for the purpose of parts disassembly and replacement The non numbered parts are not kept as standard service parts ...

Страница 141: ...THERMISTOR 1 CWA50C2665 28 CABINET REAR PLATE CO 1 CWE02C1058 29 CONTROL BOARD ASS Y 1 CWH10K1100 32 TERMINAL BOARD ASS Y 1 CWA28K1198 34 ELECTRONIC CONTROLLER CAPACITOR 1 CWA746184 O 38 ELECTRONIC CONTROLLER NOISE FILTER 1 CWA745745 O 44 ELECTRONIC CONTROLLER MAIN 1 CWA73C4833R CWA73C4834R O 46 REACTOR 2 G0C592J00003 48 TERMINAL COVER 1 CWH171039A 49 NUT FOR TERMINAL COVER 1 CWH7080300J 50 BRACKE...

Страница 142: ...142 20 3 WH UD12CE5 A WH UD14CE5 A WH UD16CE5 A ...

Страница 143: ...143 ...

Страница 144: ...144 Note The above exploded view is for the purpose of parts disassembly and replacement The non numbered parts are not kept as standard service parts ...

Страница 145: ...SENSOR COMP TOP 1 CWA50C2629 27a SENSOR COMP DEF 1 CWA50C2577 28 CABINET REAR PLATE 1 CWE02C1059 29 CONTROL BOARD CASING 1 CWH10K1049 31 TERMINAL BOARD ASS Y 1 CWA28K1213 36 ELECTRONIC CONTROLLER CAPACITOR 1 CWA746169 O 38 ELECTRONIC CONTROLLER NOISE FILTER 1 CWA745446 O 44 ELECTRONIC CONTROLLER MAIN 1 CWA73C4835R CWA73C4836R CWA73C4837R O 46 REACTOR 2 G0C592J00004 48 TERMINAL COVER 1 CWH171039A 4...

Страница 146: ...HAAM Malaysia Vendor Code 00029488 O marked parts are recommended to be kept in stock PHAAM Printed in Malaysia SFYW1004 00 72 ELECTRO MAGNETIC SWITCH 1 K6C1AYY00003 REF NO DESCRIPTION NAME QTY WH UD12CE5 A WH UD14CE5 A WH UD16CE5 A REMARKS ...

Отзывы: