69
13.1.6 Low
Frequency
Protection Control 1
When the compressor continuously operates at frequency lower than 25 Hz for 240 minutes, the operation
frequency will change to 24 Hz for 2 minutes.
13.1.7 Low
Frequency
Protection Control 2
When all the below conditions comply, the minimum compressor frequency will change to lower frequency.
Temperature, T, for:
Heating
Cooling
Outlet water (°C)
T < 14 or T 48
T < 14 or T 30
Outdoor air (°C)
T < 4 or T 24
T < 13 or T 38
Indoor heat exchanger (°C)
T 0
T < 30
13.1.8 High Pressure Sensor Control
Purpose:
- To protect the system operation.
Detection
period:
- After compressor on for 5 minutes.
Detection
conditions:
- When abnormal high voltage detection, 5V or when open circuit detection 0V for 5 seconds continuously.
After
detection:
- When abnormality is detected continue 5 seconds, unit stop operation.
- OFF/ON control panel LED will blink (H64 error occurs).
13.1.9 Outside Temperature Current Control
13.1.10 Crank Case Heater Control
Purpose:
- For compressor protection during low outdoor ambient operation (during heating low temperature operation).
Control
content:
a. Trigger heater START condition
o
When the outdoor air temperature is 4°C or below, and discharge temperature is 11.6°C or below.
b. Resetting heater STOP condition
1.
When the outdoor air temperature exceeds entry condition (6°C)
2.
When the discharge temperature exceeds entry condition (18.8°C)
Содержание WH-SDC09C3E8
Страница 14: ...14 4 Location of Controls and Components 4 1 Indoor Unit 4 1 1 Location of Control ...
Страница 15: ...15 ...
Страница 16: ...16 ...
Страница 17: ...17 4 1 2 Weekly Timer Setting ...
Страница 18: ...18 4 1 3 Setting Up the Special Functions ...
Страница 19: ...19 4 1 4 Main Components 4 2 Outdoor Unit ...
Страница 20: ...20 5 Dimensions 5 1 Indoor Unit ...
Страница 21: ...21 5 2 Outdoor Unit ...
Страница 23: ...23 ...
Страница 24: ...24 7 Block Diagram 7 1 WH UD09CE8 ...
Страница 25: ...25 7 2 WH UD12CE8 WH UD14CE8 WH UD16CE8 ...
Страница 26: ...26 8 Wiring Connection Diagram 8 1 Indoor Unit 8 1 1 WH SDC09C3E8 ...
Страница 27: ...27 8 1 2 WH SDC12C9E8 WH SDC14C9E8 WH SDC16C9E8 ...
Страница 28: ...28 8 2 Outdoor Unit ...
Страница 29: ...29 9 Electronic Circuit Diagram 9 1 Indoor Unit 9 1 1 WH SDC09C3E8 ...
Страница 30: ...30 9 1 2 WH SDC12C9E8 WH SDC14C9E8 WH SDC16C9E8 ...
Страница 31: ...31 9 2 Outdoor Unit ...
Страница 32: ...32 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board ...
Страница 33: ...33 10 1 2 Solar Printed Circuit Board Optional ...
Страница 34: ...34 10 2 Outdoor Unit 10 2 1 Main Printed Circuit Board ...
Страница 35: ...35 10 2 2 Noise Filter Printed Circuit Board ...
Страница 50: ...50 Solar Priority is Set Solar Priority is Not Set ...
Страница 53: ...53 Heat Tank Heating No Priority Solar Priority Set ...
Страница 54: ...54 Heat Tank Heating No Priority Solar Priority Not Set ...
Страница 64: ...64 Solar Priority Not Set Heat Tank Mode Heating Priority Set ...
Страница 65: ...65 Tank Mode Solar Priority Set Solar Priority Not Set ...
Страница 113: ...113 17 3 To Remove Pressure Gauge 17 4 To Remove Control Panel ...
Страница 114: ...114 17 5 To Remove RCCB 17 6 To Remove Transformer and Electronic Controller Board ...
Страница 137: ...137 19 2 WH UD09CE8 WH UD12CE8 WH UD14CE8 WH UD16CE8 ...
Страница 138: ...138 ...